HomeMy WebLinkAbout4015 LOWES BLVDINVOICE DATE
DUE DATE
INVOICE #
TOTAL DUE
02/24/2026
03/31/2026
2026-00000346
$100.00
Customer #: 14472
POPEYE'S CHICKEN & BISCUITS
1151 W 15th ST
Unit 405
CHICAGO, IL 60608
Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
715 Mulberry St
WATERLOO, IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION - 4015 LOWES BLVD -
02/ 19/2026
Description
FOR BILLING INQUIRY: (319)291-4323
REINSPECTION 1
CUSTOMER #
14472
Total Price
$100.00
BILLING DATE
02/24/2026
DUE DATE
03/31/2026
INVOICE #
2026-00000346
CHARGES
Less Prepayment
Total Due - >
City of Waterloo
$100.00
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
14412. ►oo
Waterloo Fire Rescue
Inspection Report
Popeye's Chicken - 4015 Lowes BLVD, BLDG 4015 Lowes Blvd, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
02/19/2026
425 E. 3rd Street
Inspection Type Inspection Number
Annual Inspection (1Yr) REINSPECTION 17976-R4
Lead Inspector Shift
BRAD BALDWIN NIA
Other Inspectors
N/A
Station
NIA
Unit
N/A
SUMMARY OF INSPECTION
0 0
Passed codes
NEXT STEPS
cx) 7
Failed codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
Reinspection Date
03/25/2026
BRAD BALDWIN - 02/23/2026 @ 07:41
$200 re -inspection fee, failure to complete corrections as of 2120126. Staff indicated district manager (Danielle) would be on -site at llam, came back at
that time but she was not present. Gave staff my contact info to have Danielle contact me, have not received communication at this time.
BRAD BALDWIN - 01/22/2026 @ 13:14
$80 annual inspection fee
BRAD BALDWIN - 01/22/2026 @ 13:14
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 01/22/2026 @ 13:14
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 01/22/2026 @ 13:14
$100 re -inspection fee, failure to complete corrections as of 12/18/25
BRAD BALDWIN - 01122/2026 @ 13:14
Bathroom hallway extinguisher serviced October 2025. Kitchen extinguishers serviced September 2025. Extinguishers shall be serviced annually.
BRAD BALDWIN - 01/22/2026 @ 13:14
$150 re -inspection fee, failure to complete corrections as of 1/22126
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
GENERATED ON 2/23/26, 7:44 AM
1 OF 6
Asif Poonja - Owner Date:
CHECKLISTS
Additional Codes
Status Code
Fail 1032.2 - Reliability.
Required exit accesses, exits and exit discharges shall be
continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
Fail 606.3.3 - Cleaning.
OHoods, grease -removal devices, fans, ducts and other
appurtenances shall be cleaned at intervals as required by
Sections 606.3.3.1 through 606.3.3.3.
z!z
BRAD BALDWIN 0212312026
Description
Location: Back exit
Comments: Remove obstructions in clear path of egress to exit.
Maintain clear at all times.
Location: Kitchen exhaust hood
Comments: Provide hood bi-annual cleaning and report to be
uploaded to Compliance Engine with any deficiencies corrected.
GENERATED ON 2/23/26, 7:44 AM
2 OF 6
Reinspection
Status Code
Fail
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Description
Location: Exterior sign
Comments: Properly contain open wires in box with appropriate
cover or permanently remove wires.
Location: Exterior lights near flag pole
Comments: Repair damaged lights exposing wiring.
GENERATED ON 2/23/26, 7:44 AM
3 OF 6
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Fail 603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Parking lot side of building (west)
Comments: Repair or replace light fixture hanging by wires
Location: Above fryer
Comments: Remove flexible wiring concealed in above ceiling space,
staff currently unaware of what cord is servicing. Adding permanent
wiring or outlet requires licensed electrical contractor to obtain
proper permit and inspection.
GENERATED ON 2/23/26, 7:44 AM
4 OF 6
Fail
606.3.4 - Extinguishing system service.
Automatic fire -extinguishing systems protecting commercial
cooking systems shall be serviced as required in Section
904.13.5.
Location: Fryers hood suppression system
Comments: Suppression system nozzle caps shall be installed at all
times to avoid grease accumulation that may result in delay or alter
activation of system.
Additional comments: Suppression system due bi-annual service on
3/22/26. Nozzle caps still not installed today.
GENERATED ON 2/23/26, 7:44 AM
5 OF 6
Statement of Fees
FEE
Invoice Date Inspection Fee
NIA $200.00
Invoice Number
NIA
Date Paid Amount Paid
Check Number Transaction Number
NIA NIA
GENERATED ON 2/23/26, 7:44 AM
6 OF 6