COMMERCIAL FIRE INSPECTION - 2000 HAWTHORNE AVE -
02/ 18/2026
FOR BILLING INQUIRY: (319)291-4323
Description
REINSPECTION 1
Total Price
$100.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
20795
02/24/2026
03/31/2026
2026-00000348
$100.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
2O15 $loo
Waterloo Fire Rescue
Inspection Report
S.A.C's Neighborhood Bar - 2000 Hawthorne AVE, BLDG 2000 Hawthorne Ave,
Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
02/18/2026
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr) REINSPECTION J
Other lnspectors
N/A
425 E. 3rd Street
Inspection Number
15773-R2
Shift Station Unit
NIA N/A N/A
SUMMARY OF INSPECTION
0 0 0 5 0 5
Passed codes
NEXT STEPS
Resolved violations Failed codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 02/19/2026 @ 15:39
$100 re -inspection fee, failure to complete corrections as of 2/19/26
BRAD BALDWIN - 01128/2026 @ 07:35
$80 annual inspection fee
BRAD BALDWIN - 01/28/2026 @ 07:35
Christmas lighting approved for temporary usage (90) days.
BRAD BALDWIN - 01/28/2026 @ 07:35
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
03/13/2026
BRAD BALDWIN - 01128/2026 @ 07:35
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 01128/2026 @ 07:35
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 01128/2026 @ 07:35
withholding re -inspection fee today, complete corrections to avoid possible fees. 1/23/26
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
GENERATED ON 2/19/26, 3:40 PM
1 OF 4
Randy Soper
CHECKLISTS
Additional Codes
Status Code
Date:
Fail 102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
BRAD BALDWIN
Fail 310.2 - Prohibited areas.
Smoking shall be prohibited where conditions are such as to
make smoking a hazard, and in spaces where flammable or
combustible materials are stored or handled. Exception: In
Group 1-2 occupancies, patients shall be permitted to smoke
in designated patient care areas based on the clinical needs
of the patient.
Description
02/19/2026
Location: Outlet added near main exit
Comments: Contractor (Chapman Electric) shall obtain permit and
inspection of outlet added on east wall near pool table.
Location: South enclosed patio
Comments: No smoking in enclosed south patio, see attachment per
State Of Iowa. Sign complying with State requirements shall be
posted on doors leading to enclosed south patio stating "No
Smoking". Patrons actively smoking in patio during 2/18/26
inspection.
GENERATED ON 2/19/26, 3:40 PM
2 OF 4
Reinspection
St to<, Cade
Fail
Fail
Fail
606.1- General.
Commercial kitchen exhaust hoods shall comply with the
requirements of the International Mechanical Code .
606.3.3 - Cleaning.
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be cleaned at intervals as required by
Sections 606.3.3.1 through 606.3.3.3.
606.3.3.1 - Inspection.
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be inspected at intervals specified in
Table 606.3.3.1 or as approved by the fire code official.
Inspections shall be completed by qualified individuals.
Descru do
Location: Kitchen
Comments: Repair or replace exhaust to comply with Mechanical
Code. Code questions shall be directed to Chief Mechanical
Inspector, Brian Baker.
Location: Kitchen exhaust hood
Comments: Exhaust system cleaning 10 days past due as of 1/2/26.
Provide cleaning and report to be uploaded to Compliance Engine
with any deficiencies corrected.
Additional comments: No progress made as of 2/19/26
Location: Kitchen exhaust hood suppression
Comments: Provide suppression system inspection report with any
deficiencies corrected. Contractor must upload report to Compliance
Engine. Currently 50 days past due with (1) deficiency/
Additional comments: Heavy grease accumulation noted today on
suppression system. Cleaning of excess grease shall be completed
immediately and inspection completed.