COMMERCIAL FIRE INSPECTION - 117 E SAN MARNAN DR -
02/18/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
24676
02/24/2026
03/31/2026
2026-00000345
$80.00
Less Prepayment
Total Due
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Leo
Waterloo Fire Rescue
Inspection Report
425 E. 3rd Street
The Spot #3 - 117 E San Marnan DR, BLDG 117 E San Marnan Dr, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
02/18/2026
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Inspection Number
17913
Other Inspectors
N/A
Shift
NIA
Station
NIA
Unit
NIA
SUMMARY OF INSPECTION
0 32
Passed codes
NEXT STEPS
17
Failed codes
36
N/A codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 02/19/2026 @ 13:01
$80 annual inspection fee
BRAD BALDWIN - 02119/2026 @ 14:54
Ceiling tiles noted missing today during active remodel, all ceiling tiles shall be re -installed after project is complete.
BRAD BALDWIN - 0211912026 @ 14:57
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
03/12/2026
BRAD BALDWIN - 02119/2026 @ 14:57
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 02/19/2026 @ 14:57
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 02119/2026 @ 14:58
Staff member removed propane tank from building as directed by inspector today 2/18126.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Malik (2025)
Date: BRAD BALDWIN 02/19/2026
GENERATED ON 2/19/26, 3:01 PM
1 OF 11
CHECKLISTS
GENERATED ON 2/19/26, 3:01 PM
2 OF 11
Additional Codes
Status Code
Fail
Fail
Fail
Fail
0
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
2303.2 - Emergency disconnect switches.
An approved emergency disconnect switch shall be provided
at an approved location to stop the transfer of fuel to the fuel
dispensers in the event of a fuel spill or other emergency. The
emergency disconnect switch for exterior fuel dispensers
shall be provided with ready access and shall be located
within 100 feet (30 480 mm) of, but not less than 20 feet (6096
mm) from, the fuel dispensers. For interior fuel -dispensing
operations, the emergency disconnect switch shall be
provided with ready access and be installed at an approved
location. Such devices shall be distinctly labeled as:
"EMERGENCY FUEL SHUTOFF." Signs shall be
provided in approved locations.
603.1- General.
Electrical equipment, wiring and systems required by this
code or the International Building Code shall be installed,
used and maintained in accordance with NFPA 70 and
Sections 603.2 through 603.10.
603.1.1 - Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
Desrriy
Location: Remodel project
Comments: All necessary permits shall be obtained including
inspections completed for active remodel project.
Location: Emergency fuel shut-off switch
Comments: Unable to find emergency switch. Locate switch and
provide easy access to or install emergency switch to referenced
code standards.
Location: Multiple large beverage fridges
Comments: Each individual fridge shall plug to a permanent outlet or
with a single extension cord if an outlet is not within reach of
aplliance for temporary (90 days) during remodel project. Noted
approximately 8 fridges powered by a single extension cord plugged
to a multi -plug adapter and then 2 power strips during inspection.
Location: Window LED lighting
Comments: Provide documentation of proper listing of LED lighting
and usage is compliant with the listing.
GENERATED ON 2/19/26, 3:01 PM
3 OF 11
Fail 603.1.1 - Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
0
Fail 603.1.1 - Equipment and fixtureswiring.
0 Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
Location: Honeycomb ceiling lighting
Comments: Provide documentation of proper listing of LED lighting
and usage is compliant with the listing.
Location: "Venom" and "Red Bull" beverage fridges near counter
Comments: Remove fridges from plugged to power strip, fridges
shall plug directly to permanent outlet. Adding outlet requires
obtaining proper permit and inspection.
GENERATED ON 2/19/26, 3:01 PM
4 OF 11
Fail
O
603.1.1- Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
Emergency Equipment
Status Code
Fail
O
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
Location: Honeycomb lighting and "C4 Energy" Fridge
Comments: Provide documentation lighting and fridge is approved to
plug to power strip or remove from power strip and plug to
permanent outlet. Power strips shall be properly mounted to avoid
hanging by wires.
Description
Location: Emergency egress light above front exit
Comments: Repair or replace egress lighting that failed to illuminate
during test.
GENERATED ON 2/19/26, 3:G1 PM
5 OF 11
Electrical Safety
Siidu Code
Fail 603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Description
Location: Behind counter to Liquor storage
Comments: IMMEDIATELY remove modified cord exposing wires to
box that has food warmer and microwave plugged in. Appliances
shall plug directly to a properly wired permanent outlet.
GENERATED ON 2/19/26, 3:01 PM
6 OF 11
Fail
Fail
{IX)
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Location: Liquor storage room
Comments: Blue extension cord noted under shelving altered to
exposing bare wires shall be removed from building or licensed
electrician shall make necessary repair. Obtain copy of receipt of
repair by electrician.
Location: Bathroom by register counter
Comments: Install missing switch cover.
GENERATED ON 2/10/26, 3:01 PM
7 OF 11
Fail 603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for ail switch
and electrical outlet boxes.
Fail
(%)
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Location: Electric panel near back door
Comments: Provide blank cover to opening in panel.
Location: North exterior
Comments: Provide proper cover to conduit elbow exposing wires
GENERATED ON 2/19/26, 3:01 PM
8 OF 11
Fail
Fail
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Back storage
Comments: Remove obstructions to clear path of access to electric
panel. Maintain 36" clearance in front of panel at all times.
Location: Slushie machines
Comments: Remove appliances plugged to extension cord.
Appliances shall plug directly to permanent outlet.
GENERATED ON 2/19/26, 3:01 PM
9 OF 11
Portable Fire Extingusihers
Status Code
Fail 906.7 - Hangers and brackets.
OHand-held portable fire extinguishers, not housed in cabinets,
shall be installed on the hangers or brackets supplied.
Hangers or brackets shall be securely anchored to the
mounting surface in accordance with the manufacturer's
installation instructions.
Fail 906.7 - Hangers and brackets.
OHand-held portable fire extinguishers, not housed in cabinets,
shall be installed on the hangers or brackets supplied.
Hangers or brackets shall be securely anchored to the
mounting surface in accordance with the manufacturer's
installation instructions.
Description
Location: Back storage near back door
Comments: Multiple extinguishers sitting on floor. Extinguishers
shall be annually serviced and mounted on wall brackets in required
locations. Spare extinguishers shall be removed from building.
Location: Aisles
Comments: Extinguisher shall be annually serviced and mounted on
wall brackets in required location. Currently sitting on floor.
GENERATED ON 2/19/26, 3:01 PM
10 OF 11
Statement of Fees