COMMERCIAL FIRE INSPECTION - 307 VAUGHN ST- 02/24/2026
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
24921
02/26/2026
04/02/2026
2026-00000351
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
$$b 2ygZ1
HWI Company - 307 Vaughn ST, BLDG 307 Vaughn St, Waterloo IA 50701
INSPECTION DETAILS
Inspection Date
02/24/2026
Lead Inspector
JEREMIAH VANDYKE
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
N/A
425 E. 3rd Street
Inspection Number
20805
Shif Station
Unit
N/A N/A N/A
SUMMARY OF INSPECTION
43 Os
Passed codes
NEXT STEPS
Failed codes
24
N/A codes
Please direct questions about your Inspection to:
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
GENERAL NOTES
JEREMIAH VANDYKE - 02/24/2026 @ 13:38
Fire alarm and Sprinkler system under the 324 Duryea that are compliant.
Reinspection Date
03/26/2026
JEREMIAH VANDYKE - 02/24/2026 @ 14:26
Re -inspection dates are automatically generated 30 days out from the initial inspection. Normal operating hours for inspections & re -inspections are
Monday - Friday, 8:00 a.m. - 5:00 p.m. If the automatically generated re -inspection date lands on a weekend, the re -inspection will typically be performed
the following Monday or Tuesday. If all corrections are made before the 30 days, you can call to set up an earlier re -inspection. *****Re inspection fees
may be assessed for subsequent re -inspections. Re -inspection fees start at $100, then $150, and $200 for all subsequent re-inspections.-
JEREMIAH VANDYKE - 02/24/2026 @ 14:26
Lt. Van Dyke - jeremiah.vandyke@waterloo-ia.org - Work: 319-291-4460 - Cell: 319-883-1615
JEREMIAH VANDYKE - 02/24/2026 @ 14:30
Inspection Fee = $80.00 (To be mailed out by City via snail mail.) Send to Pat Buchanan HWI company.
SIGNATURES
Contact signature
No signature
Report completed post inspection
Pat Buchanan
CHECKLISTS
Inspector signature
Date: JEREMIAH VANDYKE 02/24/2026
GENERATED ON 2/24/26, 2:32 PM
1 OF 5
Additional Codes
Status Code
Fail
5003.5 - Hazard identification signs.
Unless otherwise exempted by the fire code official, visible
hazard identification signs as specified in NFPA 704 for the
specific material contained shall be placed on stationary
containers and above -ground tanks and at entrances to
locations where hazardous materials are stored, dispensed,
used or handled in quantities requiring a permit and at
specific entrances and locations designated by the fire code
official.
Fail 5003.5 - Hazard identification signs.
Unless otherwise exempted by the fire code official, visible
hazard identification signs as specified in NFPA 704 for the
specific material contained shall be placed on stationary
containers and above -ground tanks and at entrances to
locations where hazardous materials are stored, dispensed,
used or handled in quantities requiring a permit and at
specific entrances and locations designated by the fire code
official.
Fail 5003.5 - Hazard identification signs.
Unless otherwise exempted by the fire code official, visible
hazard identification signs as specified in NFPA 704 for the
specific material contained shall be placed on stationary
containers and above -ground tanks and at entrances to
locations where hazardous materials are stored, dispensed,
used or handled in quantities requiring a permit and at
specific entrances and locations designated by the fire code
official.
Fire Service Features
Status Code
Fail 505.1- Address identification.
New and existing buildings shall be provided with approved
address identification. The address identification shall be
legible and placed in a position that is visible from the street
or road fronting the property. Address identification
characters shall contrast with their background. Address
numbers shall be Arabic numbers or alphabetical letters.
Numbers shall not be spelled out. Each character shall be not
less than 4 inches (102 mm) high with a minimum stroke
width of 112 inch (12.7 mm). Where required by the fire code
official, address identification shall be provided in additional
approved locations to facilitate emergency response. Where
access is by means of a private road and the building cannot
be viewed from the public way, a monument, pole or other
sign or means shall be used to identify the structure. Address
identification shall be maintained.
Fail 509.1 - Identification.
Fire protection equipment shall be identified in an approved
manner. Rooms containing controls for air-conditioning
systems, sprinkler risers and valves, or other fire detection,
suppression or control elements fire protection systems shall
be identified for the use of the fire department. Approved
signs required to identify fire protection system equipment
and equipment location shall be constructed of durable
materials, permanently installed and readily visible.
Description
Location: Remove 704 Diamond Placard from tool shed.
Comments: Remove 704 Diamond Placard from tool shed.
Location: Yellow cabinet for Propane storage near coal storage silo.
Comments: Update and install new NFPA 704 diamond placard on
yellow cabinet.
Location: COAL Silo.
Comments: Need clearer location for "COAL" signage and NFPA 704
Diamond Placard on Silo. Check SDS sheets for NFPA 704
numbering.
Description
Location: Address needed on outside door for 307 Vaughn.
Comments: Call my work cell if you have any questions on locaton.
319-883-1615
Location: Signage X2 stating "Main Fire Alarm Panel" on cupboard
door in office and outside above office door in warehouse area.
Comments: Call my work cell if you have any questions. 319-883-
1615.
GENERATED ON 2/24/26, 2:32 PM
2 OF 5
Electrical Safety
Status Code
Fail
Fail
603.4.1 - Labeling.
Doors into electrical control panel rooms shall be marked
with a plainly visible and legible sign stating "ELECTRICAL
ROOM" or similar approved wording. The disconnecting
means for each service, feeder or branch circuit originating
on a switchboard or panelboard shall be legibly and durably
marked to indicate its purpose unless such purpose is clearly
evident. Where buildings or structures are supplied by more
than one power source, markings shall be provided at each
service equipment location and at all interconnected electric
power production sources identifying all electric power
sources at the premises in accordance with NFPA 70.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Fire Resistant Construction Maintenance
Status Cade
Fail
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Description
Location: Silo with main electrical shut off.
Comments: Signage needed on the outside of the silo stating "MAIN
ELECTRICAL PANEL & SHUT OFF"
Location: Batch Room
Comments: Black extension cord needs to be removed along with
Daisy chain to power strip. Discussed getting longer cord bigger
powerstrip to use.
De
Location: Back officellT area.
Comments: Ceiling tiles missing and need to be re installed.
GENERATED ON 2/24/26, 2:32 PM
3 OF 5
Portable Fire Extingusihers
Status Code
Fail 906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.1n Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Location: Office area and outside shed areas.
Comments: All fire extinguishers are past due and need to be
serviced and tagged by fire extinguisher contractor.
GENERATED ON 2/24/26, 2:32 PM