COMMERCIAL FIRE INSPECTION - 212 W RIDGEWAY AVE -
02/23/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
6081
02/26/2026
04/02/2026
2026-00000352
$80.00
Less Prepayment
Total Due —�
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
tfV)
Waterloo Fire Rescue
Inspection Report 425 E. 3rd Street
Village Inn - 212 W Ridgeway AVE, BLDG 212 W Ridgeway Ave, Waterloo IA 50701
INSPECTION DETAILS
lnspection Date
02/23/2026
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
N/A
Inspection Number
1494
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
0 42
Passed codes
NEXT STEPS
11
Failed codes
Q 25
N/A codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 02/24/2026 @ 13:34
S80 annual inspection fee
BRAD BALDWIN - 02/24/2026 @ 14:12
Corrected during 2/23/26 - Extension cord unplugged from under food counter
BRAD BALDWIN - 0212412026 @ 14:40
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
03/26/2026
BRAD BALDWIN - 02/24/2026 @ 14:40
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Mike Claney (2026)
CHECKLISTS
Date: BRAD BALDWIN 02124/2026
GENERATED ON 2/24/26, 2:42 PM
1 OF 7
Emergency Equipment
Status Code
Fail
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
General Housekeeping
Status Code
Fail
304.3.1 - Spontaneous ignition.
Materials susceptible to spontaneous ignition, such as oily
rags, shall be stored in a listed disposal container. Contents
of such containers shall be removed and disposed of daily.
Fail 305.1- Clearance from ignition sources.
Clearance between ignition sources, such as luminaires,
heaters, flame -producing devices and combustible materials,
shall be maintained in an approved manner.
Description
Location: Kitchen above coffee makers
Comments: Repair or replace egress light that failed to illuminate
during test.
Description
Location: Kitchen
Comments: Provide listed container to dispose of oily rags.
Location: Mechanical room
Comments: Remove storage from room not applicable to mechanical
equipment.
GENERATED ON 2/24/26, 2:42 PM
2 CF 1
Electrical Safety
Status Code
Fail
Fail
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Description
Location: Office
Comments: Provide missing outlet cover near ceiling above safe
Location: Walk-in fridge
Comments: Provide moisture proof cover to light fixture
Location: Mechanical room (west wall)
Comments: Provide appropriate cover to avoid exposed wires.
GENERATED ON 2/24/26, 2:42 PM
3 OF 7
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Location: North exterior by transformer
Comments: Provide proper exterior rated cover
GENERATED ON 2/24/26, 2:42 PM
4 OF 7
Fail
Fail
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Electric panel room
Comments: Remove storage from room not applicable to electrical
equipment.
Location: Kitchen "cold table"
Comments: Remove appliance from plugged to extension cord.
Appliance shall plug directly to wall outlet. Adding outlet requires
obtaining permit and inspection.
GENERATED ON 2/24/26, 2:42 PM
5 OF 7
Additional Codes
Status Code
Fail
606.3.1 - Ventilation system.
The ventilation system in connection with hoods shall be
operated at the required rate of air movement, and grease
filters listed and labeled in accordance with UL 1046 shall be
in place where equipment under a kitchen grease hood is
used.
Fail 606.3.3.2 - Grease accumulation.
If during the inspection it is found that hoods, grease -removal
devices, fans, ducts or other appurtenances have an
accumulation of grease, such components shall be cleaned in
accordance with ANSIIIKECA C10.
Description
Location: Kitchen exhaust hood filters
Comments: Damaged filters shall be replaced. Filters installed
incorrectly shall be installed vertically to allow grease to drain
properly in the collection trough. Gaps in filters shall be corrected to
avoid grease build up in ductwork and on fire suppression cables.
Location: Fryer cabinet 1 kitchen appliances
Comments: Remove excess grease accumulation on and around
cooking equipment.