COMMERCIAL FIRE INSPECTION - 735 LOGAN AVE - 02/25/2026
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
14476
03/02/2026
04/06/2026
2026-00000359
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
sek,
Waterloo Fire Rescue
Inspection Report
Logan Convenience Store - 735 Logan AVE, BLDG 735 Logan Ave, Waterloo IA
50703
INSPECTION DETAILS
inspection Date Inspection Type
02/25/2026 Annual Inspection (1Yr)
Lead Inspector
BRAD BALDWIN
Other Inspectors
NIA
42S E. 3rd Street.
Inspection Number
16415
Shift Station Unit
N/A N/A N/A
SUMMARY OF INSPECTION
0 30
Passed codes
NEXT STEPS
0 7
Failed codes
0 36
N/A codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 02/27/2026 @ 13:15
• $80 annual inspection fee
BRAD BALDWIN - 02/27/2026 @ 13:28
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291.4319 (#5) - Cell: 319-230-1224
Reinspection Date
03/20/2026
BRAD BALDWIN - 02/27/2026 @ 13:28
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 02/27/2026 @ 13:28
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Muhammad Bhatti Date:
CHECKLISTS
BRAD BALDWIN 02/27/2026
GENERATED ON 2/27/26, 1:30 PM
1 OF 7
0016241'. _
,
Means of Egress
Fail
Code
Description
1032.2 - Reliability.
Required exit accesses, exits and exit discharges shall be
continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
Emergency Equipment
Fail
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required Toad for a duration of not less than 90 minutes.
General Housekeeping
Status
Fail
Location: Back exit
Comments: Remove boxes of beer from egress exit path, maintain
clear path to exit at all times.
Description
Location: Front exit
Comments: Repair or replace exit sign and egress lights that failed to
illuminate during test
Code (; _ cri
315.3.1- Ceiling clearance.
Storage shall be maintained 2 feet (610 mm) or more below
the ceiling in nonsprinklered areas of buildings or not less
than 18 inches (457 mm) below sprinkler head deflectors in
sprinklered areas of buildings. Exceptions: 1.The 2-foot (610
mm) ceiling clearance is not required for storage along walls
in nonsprinklered areas of buildings. 2.The 18-inch (457 mm)
ceiling clearance is not required for storage along walls in
areas of buildings equipped with an automatic sprinkler
system in accordance with Section 903.3.1.1, 903.3.1.2 or
903.3.1.3.
Location: Storage room
Comments: Lower storage within 24 inches below ceiling
GENERATED ON 2/27/26, 1:30 PM
2 OF 7
Electrical Safety
Status C
Fail
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Description
Location: Near ATM machine
Comments: Remove incense sticks from outlet cover. Burning of
incense in building is NOT allowed.
GENERATED ON 2/27/26, 1:30 PM
3 OF 7
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Near register counter security cameras
Comments: Flexible cords (not including low voltage cords) shall be
removed from above drop ceiling.
GENERATED ON 2/27/26, 1:30 PM
4 OF 7
Fire Resistant Construction Maintenance
Status Code
Fail
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Description
Location: Bathroom
Comments: Replace damaged ceiling tile surrounding exhaust fan
GENERATED ON 2/27/26, 1:30 PM
5 OF 7
Portable Fire Extingusihers
,tatus Code
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
oescription
Location: Fire Extinguishers
Comments: Provide annual service to extinguishers, currently due for
service in March 2026
GENERATED ON 2/27/26, 1:30 PM
6 OF 7
Statement of Fees
FEE
Invoice Date Inspection Fee
NIA $80.00
Date Paid Amount Paid
Invoice Number
NIA
Check Number
N/A
Transaction Number
N/A
GENERATED ON 2/27/26, 1:30 PM