COMMERCIAL FIRE INSPECTION - 1237/1239 ANSBOROUGH -
02/26/2026
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
BILLINGDATE
DUE DATE
INVOICE #
9180
03/02/2026
04/06/2026
2026-00000355
CHARGES
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Subway - 1239 Ansborough AVE, BLDG 1239 Ansborough Ave, Waterloo IA 50701
1151 C.et �
INSPECTION DETAILS
Inspection Date
02/26/2026
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other lnspectors
NIA
425 E. 3rd Street
Inspection Number
621
Shift Station Unit
N/A NIA N/A
SUMMARY OF INSPECTION
033
Passed codes
NEXT STEPS
0 5
Failed codes
36
N/A codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 02/26/2026 @ 11:15
S80 annual inspection fee
BRAD BALDWIN - 02126/2026 @ 15:23
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
03/27/2026
BRAD BALDWIN - 02/26/2026 @ 15:23
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and 5200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Rob Pruitt (2026) Date: BRAD BALDWIN 02/26/2026
CHECKLISTS
GENERATED ON 2/26/26, 3:25 PM
1 OF 6
Additional Codes
Status Code
Fail
0
1010.2.1- Unlatching.
The unlatching of any door or leaf for
egress shall require not require more than one operation
motion in a single linear or rotational direction to release all
latching and all locking devices. Exceptions: 1.Places of
detention or restraint. 2.Where manually operated bolt locks
are permitted by Section 1010.2.5. 3.Doors with automatic
flush bolts as permitted by Section 1010.2.4, Item 3 4. 4.Doors
from individual dwelling units and sleeping units of Group R
occupancies as permitted by Section 1010.2.4, Item 4 5.
Description
Location: Back exit
Comments: Remove deadbolt hardware from door, exit door allowed
nor more than a single motion to unlatch and unlock door. Owner
stated hardware is currently inoperable so will remove.
GENERATED ON 2/26/26, 3:25 PM
2 OF 6
Electrical Safety
Status Code
Fail
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 min) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not Tess than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Description
Location: Near back exit
Comments: Provide 36" clear space around and in front of electric
panel.
GENERATED ON 2/26/26, 3:25 PM
3 OF 6
Fail 603.5 - Relocatable power taps and current taps.Multiplug
adapters.
Multipiug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Above walk-in fridge
Comments: Remove 3-way multi plug adapter from outlet.
Location: Above walk-in fridge
Comments: Remove extension cord plugged to TV. May replace with
power strip with manual reset properly mounted for Tight duty electric
only. Flexible cords shall not be installed in concealed area (above
drop ceiling).
GENERATED ON 2/26/26, 3:25 PM
4 OF 6
Portable Fire Extingusihers
Status Code
Fail
O
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Location: Extinguisher
Comments: Provide annual service to extinguisher, last recorded
service February 2025.