COMMERCIAL FIRE INSPECTION - 218 E 4TH ST - 03/06/2026
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
24926
03/09/2026
04/13/2026
2026-00000366
$80.00
Less Prepayment
Total Due —+
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
#� 249Z(o
Waterloo Fire Rescue
Inspection Report
Savvy Bean
INSPECTION DETAILS
Inspection Date
03/06/2026
•218E4thST,BLDG218E
Lead lnspector
BRAD BALDWIN
4th St, Waterloo IA 50703
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
N/A
425 E. 3rd Street
Inspection Number
21002
Shift Station Unit
NIA NIA N/A
SUMMARY OF INSPECTION
0 46 0 6 ® 22
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 03/09/2026 @ 07:58
$80 annual inspection fee
BRAD BALDWIN - 03/09/2026 @ 08:27
Christmas lighting approved for temporary usage (max 90 days). 2021 IFC: 603.8
BRAD BALDWIN - 03/09/2026 @ 08:28
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
04/08/2026
BRAD BALDWIN - 03/09/2026 @ 08:28
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
John Warren (Building)
CHECKLISTS
Date: BRAD BALDWIN 03109/2026
GENERATED ON 3/9/26, 8:32 AM
1 OF 4
Means of Egress
Status Code
Fail
1032.2 - Reliability.
Required exit accesses, exits and exit discharges shall be
continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
General Housekeeping
Status Code
Fail
305.1- Clearance from ignition sources.
Clearance between ignition sources, such as luminaires,
heaters, flame -producing devices and combustible materials,
shall be maintained in an approved manner.
Additional Codes
Status Code
Fail
V
603.1- General.
Electrical equipment, wiring and systems required by this
code or the International Building Code shall be installed,
used and maintained in accordance with NFPA 70 and
Sections 603.2 through 603.10.
Electrical Safety
Status
Failai�
tt0
Code
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Description
Location: Front exit
Comments: Remove obstructions to clear path of egress to exit.
Description
Location: Mechanical room
Comments: Remove storage from room, maintain 36" clearance from
fuel fired appliances.
Description
Location: Basement water softener
Comments: Water softener shall plug directly to permanent outlet,
currently plugged to light fixture plug. If adding new outlet, licensed
electrical contractor shall obtain permit and inspection.
Description
Location: Basement
Comments: Provide clear path of access to electric and gas services
for fire fighters, maintain clear path and proper clearances at all
times.
GENERATED ON 3/9/26, 8:32 AM
2 OF 4
Fire Resistant Construction Maintenance
Status Code
Fail
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Portable Fire Extingusihers
Status Code
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Etectronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Location: Employee service room near bathroom hallway
Comments: Replace missing ceiling tiles.
Description
Location: All fire extinguishers
Comments: Provide annual service to extinguishers. Install properly
mounted extinguisher in basement, extinguisher shall be located to
not exceed 75 feet of travel to access.