COMMERCIAL FIRE INSPECTION - 4045 HAMMOND AVE -
02/27/2026
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
24925
03/09/2026
04/13/2026
2026-00000361
$80.00
Less Prepayment
Total Due —�
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Perkins - 4045 Hammond AVE, BLDG 4045 Hammond Ave, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
02/27/2026
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
N/A
425 E. 3rd Street
Inspection Number
1320
Shift Station Unit
NIA N/A NIA
SUMMARY OF INSPECTION
0 49
Passed codes
NEXT STEPS
O 19
Failed codes
10
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 03/0512026 @ 07:32
$80 annual inspection fee
BRAD BALDWIN - 03/05/2026 @ 07:37
Fire extinguishers due annually serviced September 2026
BRAD BALDWIN - 03/0512026 @ 09:01
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
04/03/2026
BRAD BALDWIN - 03/05/2026 @ 09:01
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Annie Smith 2026 Date: BRAD BALDWIN 03/05/2026
CHECKLISTS
GENERATED ON 3/5/26, 9:04 AM 1 OF 9
Means of Egress
Status Code
Fail
1010.1.3 - Door opening force Forces to unlatch and open
doors.
The force for pushing or pulling open interior swinging
egress doors, other than fire doors, shall not exceed 5
pounds (22 N). These forces do not apply to the force
required to retract latch bolts or disengage other devices that
hold the door in a closed position. For other swinging doors,
as well as sliding and folding doors, the door latch shall
release when subjected to a 15-pound (67 N) force. The door
shall be set in motion when subjected to a 30-pound (133 N)
force. The door shall swing to a full -open position when
subjected to a 15-pound (67 N) force. The forces to unlatch
doors shall comply with the following: 1.Where door
hardware operates by push or pull, the operational force to
unlatch the door shall not exceed 15 pounds (66.7 N). 2.Where
door hardware operates by rotation, the operational force to
unlatch the door shall not exceed 28 inch -pounds (315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated, other than doors required to be fire rated, the force
for pushing or pulling open the door shall not exceed 5
pounds (22 N). 2.For other swinging doors, sliding doors or
folding doors, and doors required to be fire rated, the door
shall require not more than a 30-pound (133 N) force to be set
in motion and shall move to a full -open position when
subjected to not more than a 15-pound (67 N) force.
Additional Codes
-"talus Code
Fail
Fail
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
606.3.1- Ventilation system.
The ventilation system in connection with hoods shall be
operated at the required rate of air movement, and grease
filters listed and labeled in accordance with UL 1046 shall be
in place where equipment under a kitchen grease hood is
used.
Emergency Equipment
Status Code
Fail
Fail
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Description
Location: Kitchen (south) exit door
Comments: Repair or replace door to allow door to open with less
than 15 lbs of force. Door opened forcefully during inspection .
Description
Location: South kitchen exterior door frame
Comments: Contractor (Allied Glass) shall obtain permit and
inspection of door frame recently replaced without permit.
Location: Main kitchen exhaust hood
Comments: Close gaps in grease filters. Filters not in place cause
more grease in ductwork and on cables for fire suppression
Description
Location: Men's & women's bathrooms
Comments: Repair or replace egress emergency lights that failed to
illuminate during test
Location: Kitchen south exit
Comments: Repair or replace exit signiegress lights combo that
failed to illuminate during test.
GENERATED ON 3/5/26, 9:04 AM 2 OF 9
General Housekeeping
Status Cole
Fail
Fail
Fail
304.3.1 - Spontaneous ignition.
Materials susceptible to spontaneous ignition, such as oily
rags, shall be stored in a listed disposal container. Contents
of such containers shall be removed and disposed of daily.
315.3.1 - Ceiling clearance.
Storage shall be maintained 2 feet (610 mm) or more below
the ceiling in nonsprinklered areas of buildings or not less
than 18 inches (457 mrn) below sprinkler head deflectors in
sprinklered areas of buildings. Exceptions: 1.The 2-foot (610
mm) ceiling clearance is not required for storage along walls
in nonsprinklered areas of buildings. 2.The 18-inch (457 mm)
ceiling clearance is not required for storage along walls in
areas of buildings equipped with an automatic sprinkler
system in accordance with Section 903.3.1.1, 903.3.1.2 or
903.3.1.3.
315.3.1- Ceiling clearance.
Storage shall be maintained 2 feet (610 mm) or more below
the ceiling in nonsprinklered areas of buildings or not less
than 18 inches (457 mrn) below sprinkler head deflectors in
sprinklered areas of buildings. Exceptions: 1.The 2-foot (610
mm) ceiling clearance is not required for storage along walls
in nonsprinklered areas of buildings. 2.The 18-inch (457 mm)
ceiling clearance is not required for storage along walls in
areas of buildings equipped with an automatic sprinkler
system in accordance with Section 903.3.1.1, 903.3.1.2 or
903.3.1.3.
Fire Sprinkler System
Status Code
Fail
5.2.1.1.5 - Missing escutcheons
Escutcheons and coverplates for recessed, flush, and
concealed sprinklers shall be replaced if found missing
during the inspection.
n
Location: Kitchen
Comments: Provide listed oily rag container, see attachment.
Location: Kitchen dry storage
Comments: Remove storage within 18 inches of ceiling.
Location: Storage closet near bathrooms
Comments: Remove storage within 18 inches of ceiling.
Description
Location: Storage closet by bathrooms
Comments: Repair escutcheon loose to ceiling, escutcheon shall be
tight to ceiling.
GENERATED ON 3/5/26, 9:04 AM
3 OF 9
Fire Service Features
=„aau< Code
Fail
Fail
Fail
505.1 - Address identification.
New and existing buildings shall be provided with approved
address identification. The address identification shall be
legible and placed in a position that is visible from the street
or road fronting the property. Address identification
characters shall contrast with their background. Address
numbers shall be Arabic numbers or alphabetical letters.
Numbers shall not be spelled out. Each character shall be not
Tess than 4 inches (102 mm) high with a minimum stroke
width of 112 inch (12.7 mm). Where required by the fire code
official, address identification shall be provided in additional
approved locations to facilitate emergency response. Where
access is by means of a private road and the building cannot
be viewed from the public way, a monument, pole or other
sign or means shall be used to identify the structure. Address
identification shall be maintained.
506.2 - Key box maintenance.
The operator of the building shall immediately notify the fire
code official and provide the new key where a lock is changed
or rekeyed. The key to such lock shall be secured in the key
box.
509.1- Identification.
Fire protection equipment shall be identified in an approved
manner. Rooms containing controls for air-conditioning
systems, sprinkler risers and valves, or other fire detection,
suppression or control elements fire protection systems shall
be identified for the use of the fire department. Approved
signs required to identify fire protection system equipment
and equipment location shall be constructed of durable
materials, permanently installed and readily visible.
Location: Hammond side of building
Comments: Address number identification in contrast to the building
shall be properly installed to face Hammond Blvd. Current address
numbers of "4101" on kitchen exit door is old, invalid number shall
be removed.
Location: Sprinkler riser room
Comments: Contact fire department (319) 291-4460 to update key in
Knox Box to Riser Room.
Location: Sprinkler riser room (North side of building)
Comments: "Electrical Room" and "Sprinkler Riser Room' signage
faded, shall be replaced.
GENERATED ON 3/5/26, 9:04 AM
4 OF 9
Fail
509.2 - Equipment access.
Approved access shall be provided and maintained for all fire
protection system equipment to permit immediate safe
operation and maintenance of such equipment. Storage, trash
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
Location: Sprinkler riser room (North side of building)
Comments: Remove storage (shelving, racking) from room.
GENERATED ON 3/5/26, 9:04 AM
5 OF 9
Electrical Safety
Status Code
Fail 603.2 - Abatement of unsafe conditions and electrical
(0 hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Description
Location: Electric panel by walk-in fridge
Comments: Provide blank covers to openings in panel.
GENERATED ON 3/5/26, 9:04 AM
6 OF 9
Fail
Fail
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.5.3 - Installation.
Relocatable power tap cords shall not extend through walls,
ceilings, floors, under doors or floor coverings, or be subject
to environmental or physical damage.
Commercial Cooking Hood Suppression System
status Code
Fail
606.3.3.1- Inspection.
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be inspected at intervals specified in
Table 606.3.3.1 or as approved by the fire code official.
Inspections shall be completed by qualified individuals.
Location: Parking lot (north) at flag pole
Comments: Deteriorated box shall be replaced.
Location: Kitchen coffee station
Comments: Properly mount power strip to wall to avoid hanging by
wires.
Description
Location: Hood exhaust suppression system
Comments: Provide suppression system inspection report with any
deficiencies corrected. Contractor must upload report to Compliance
Engine. Currently 156 days past due per Compliance Engine.
GENERATED ON 3/5/26, 9:04 AM
7 OF 9
Fire Resistant Construction Maintenance
status codt.
Fail
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
rooflceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Portable Fire Extingusihers
tt,G Code
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Location: Kitchen
Comments: Replace missing or loose ceiling tiles.
Description
Location: Main electric room (North side of building)
Comments: Provide annual service to fire extinguisher, last recorded
service October 2024
GENERATED ON 3/5/26, 9:04 AM 8 OF 9