COMMERCIAL FIRE INSPECTION - 1331 FLAMMING DR -
03/06/2026
FOR BILLING INQUIRY: (319)291-4323
Descrap
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
23044
L!
DATE
03/10/2026
DUE DA
04/14/2026
INVOICE #
2026-00000372
Less Prepayment
Total Due -->
City of Waterloo
$80.00
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
A
is() 23c1
Waterloo Fire Rescue
Inspection Report
Chick-Fil-A - 1331 Flammang DR, BLDG 1331 Flammang Dr, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
03/06/2026
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
N/A
425 E. 3rd Street
Inspection Number
21024
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
049 018 010
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 03/1012026 @ 09:46
$80 annual inspection fee
BRAD BALDWIN - 03/1012026 @ 09:46
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
04/09/2026
BRAD BALDWIN - 03/1012026 @ 09:46
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
Beau Duncan 2026
CHECKLISTS
No signature
Report completed post inspection
Date: BRAD BALDWIN 03110/2026
GENERATED ON 3/10/26, 9:49 AM 1 OF 8
Means of Egress
Status Code
Fail
1032.2 - Reliability.
Required exit accesses, exits and exit discharges shall be
continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
Emergency Equipment
Status Code
Fail
Fail
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Fire Alarm System
Status Code
Fail
Chapter 14 - Inspection, testing, and maintenance
Fire alarm system tested at least annually by licensed
contractor
Description
Location: Northeast dining exit
Comments: All obstructions in hallway path of exit egress shall be
removed including staff seated in chairs noted during inspection.
Description
Location: All emergency egress lights
Comments: Provide documentation of testing all emergency egress
lighting in building including repairs made to maintain working
properly, documentation shall include signature and date of
responsible person.
Location: All exit signs
Comments: Provide documentation of testing all exit signs in
building including repairs made to maintain working properly,
documentation shall include signature and date of responsible
person.
Description
Location: Fire alarm
Comments: Provide required annual inspection and report including
any deficiencies corrected to be uploaded by contractor to
Compliance Engine. Currently 2125 days past due.
GENERATED ON 3/10/26, 9:49 AN
2 OF 8
Additional Codes
Status Code
Fail
Fail
Fail
2015 IPMC 704.1.1- Automatic sprinkler systems
Inspection, testing and maintenance of automatic sprinkler
systems shall be in accordance with NFPA 25.
5303.5.3 - Securing compressed gas containers, cylinders
and tanks.
Compressed gas containers, cylinders and tanks shall be
secured to prevent falling caused by contact, vibration or
seismic activity. Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers, cylinders and tanks to a fixed object
with one or more restraints. 2.Securing containers, cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers, cylinders or tanks.
3. Nesting of compressed gas containers, cylinders and tanks
at container filling or servicing facilities or in sellers'
warehouses not open to the public. Nesting shall be allowed
provided that the nested containers, cylinders or tanks, if
dislodged, do not obstruct the required means of egress.
4.Securing of compressed gas containers, cylinders and
tanks to or within a rack, framework, cabinet or similar
assembly designed for such use. Exception: Compressed gas
containers, cylinders and tanks in the process of
examination, filling, transport or servicing.
603.1.1- Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
Description
Location: Sprinkler 5 year inspection
Comments: Provide required inspection with report of contractor's
inspection uploaded to Compliance Engine including any
deficiencies corrected. Currently 644 days past due.
Location: The cage
Comments: Secure compressed gas cylinders with chain to avoid tip
over.
Location: West exterior electric panel
Comments: Replace broken panel cover latch, currently unable to
open and access panel.
GENERATED ON 3/10/26, 9:49 AN
30F8
Fail
903.3.1.1- NFPA 13 sprinkler systems.
Where the provisions of this code require that a building or
portion thereof be equipped throughout with an automatic
sprinkler system in accordance with this section, sprinklers
shall be installed throughout in accordance with NFPA 13
except as provided in Sections 903.3.1.1.1 and 903.3.1.1.2.
General Housekeeping
Status Code
Fail
Fail
Fail
304.3.1- Spontaneous ignition.
Materials susceptible to spontaneous ignition, such as oily
rags, shall be stored in a listed disposal container. Contents
of such containers shall be removed and disposed of daily.
315.3.1- Ceiling clearance.
Storage shall be maintained 2 feet (610 mm) or more below
the ceiling in nonsprinklered areas of buildings or not less
than 18 inches (457 mm) below sprinkler head deflectors in
sprinklered areas of buildings. Exceptions: 1.The 2-foot (610
mm) ceiling clearance is not required for storage along walls
in nonsprinklered areas of buildings. 2.The 18-inch (457 mm)
ceiling clearance is not required for storage along walls in
areas of buildings equipped with an automatic sprinkler
system in accordance with Section 903.3.1.1, 903.3.1.2 or
903.3.1.3.
315.3.2 - Means of egress.
Combustible materials shall not be stored in exits or
enclosures for stairways and ramps. Combustible materials in
the means of egress during construction, demolition,
remodeling or alterations shall comply with Section 3312.3.
Location: Sprinkler riser room
Comments: Water softener equipment obstructing sprinkler riser and
valves shall be corrected.
Description
Location: Kitchen
Comments: Provided listed container for oily rags, see attachment.
Location: Kitchen
Comments: Remove storage on shelving within 18 inches of ceiling.
Location: Northeast dining exit
Comments: Remove cans of diesel and heaters containing diesel fuel
from exit hallway immediately.
GENERATED ON 3/10/26, 9:49 AN
4 OF 8
Fire Sprinkler System
Status Code
Fail
Fail
4.9 - Support of nonsprinkler system components
Sprinkler system components shall not be used to support
non -sprinkler system components unless expressly permitted
by NFPA 13.
5.2.1- Annual sprinkler system inspection
Sprinklers shall be inspected at least annually by licensed
contractor
Description
Location: Roof (north) shed
Comments: Remove light fixture and wiring from sprinkler pipe.
Location: Sprinkler system
Comments: Provide required annual inspection and report including
any deficiencies corrected to be uploaded by contractor to
Compliance Engine. Currently 2125 days past due.
GENERATED ON 3/10/26, 9:49 AM
5 OF 8
Electrical Safety
Status Code
Fail
Fail
Fail
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
603.4.1- Labeling.
Doors into electrical control panel rooms shall be marked
with a plainly visible and legible sign stating "ELECTRICAL
ROOM" or similar approved wording. The disconnecting
means for each service, feeder or branch circuit originating
on a switchboard or panelboard shall be legibly and durably
marked to indicate its purpose unless such purpose is clearly
evident. Where buildings or structures are supplied by more
than one power source, markings shall be provided at each
service equipment location and at all interconnected electric
power production sources identifying all electric power
sources at the premises in accordance with NFPA 70.
603.5 - Relocatable power taps and current taps.Multiplug
adapters.
Multiplug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
Description
Location: The cage
Comments: Remove storage in panel room and maintain clear at all
times.
Location: The cage
Comments: Provide permanent sign on panel room door, laminated
paper will not be accepted.
Location: Manager's stand
Comments: Remove multi -plug adapter. May replace with properly
mounted power strip with manual reset for Tight duty electric only.
GENERATED ON 3/10/26, 9:49 AN
6 OF 8
Fail
Fail
603.5.2 - Application and usePower supply.
Relocatable power taps and current taps shall be directly
connected to a permanently installed receptacle. Exceptions:
1. Where approved for use in a Group A occupancy or in a
meeting room in a Group B occupancy, not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Kitchen middle aisles
Comments: Remove power strip plugged to extension cord. Power
strips shall plug directly to wall outlet used for light duty electric
only.
Location: Kitchen middle aisle
Comments: Remove orange extension cord on shelving
GENERATED ON 3/10/26, 9:49 AM 7 OF 8