COMMERCIAL FIRE INSPECTION - 1916 E MITCHELL AVE STE B
-03/10/26
FOR BILLING INQUIRY: (319)291-4323
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
FR #
G DATE;.
DAA
roil
24927
03/10/2026
04/14/2026
2026-00000375
$80.00
Less Prepayment
Total Due —
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Waterloo Fire Rescue
Inspection Report
Puff City Smoke Shop - 1916 E Mitchell AVE, BLDG 1916 E Mitchell Ave - STE B,
Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
03110/2026
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
cxo
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
21057
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
0 33
Passed codes
NEXT STEPS
0 7
Failed codes
36
N/A codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 03/1012026 @ 15:25
$80 annual inspection fee
BRAD BALDWIN - 03/1012026 @ 15:44
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
04/0912026
BRAD BALDWIN - 03/1012026 @ 15:44
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Asan Elzofri (2026) Date: BRAD BALDWIN 03110/2026
CHECKLISTS
Additional Codes
Status Code Description
Fail 603.1.1- Equipment and fixtureswiring.
OElectrical equipment and fixtures All electrical equipment, Location: Fridges (2) at front of building
wiring, devices and appliances shall be tested; and listed by Comments: Remove fridges from plugged to power strips, appliances
an approved agency and labeled; and installed, used and shall be plugged directly to permanent wall outlet.
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
GENERATED ON 3/18/26, 3:48 PM 1 OF 4
Electrical Safety
Status Code
Fail
Fail
Fail
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Description
Location: Back storage room
Comments: Clear obstructions and storage within 36 inches in front
of electric panel. Maintain proper clearance and access at all times.
Location: Entire space
Comments: Remove all extension cords, not approved for every day
usage. Several extension cords noted behind glass display cases,
window displays, and back storage room. May replace extension
cords with properly mounted power strips with manual resets for
light duty electric only.
Location: Behind cash register
Comments: Flexible cords across walkway shall be protected by
listed cord protector. See attachment.
d/
GENERATED ON 3/10/26, 3:48 PM 2 OF 4
Portable Fire Extingusihers
Status Code
Fail
Fail
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
906.5 - Conspicuous location.
Portable fire extinguishers shall be located in conspicuous
locations where they will have ready access and be
immediately available for use. These locations shall be along
normal paths of travel, unless the fire code official determines
that the hazard posed indicates the need for placement away
from normal paths of travel.
Description
Location: Fire extinguisher
Comments: Provide annually serviced fire extinguisher of minimum
size (2A:10BC) mounted on wall bracket in required location. If self -
purchasing, tape receipt of purchase to bottom of extinguisher.
Location: Back storage
Comments: Provide annual service to spare extinguisher or remove
from building.
Location: Fire extinguisher
Comments: Remove obstructions covering extinguisher signage.