HomeMy WebLinkAbout703 PROGRESS AVEINVOICE DATE
DUE DATE
INVOICE #
TOTAL DUE
03/16/2026
04/20/2026
2026-00000376
$80.00
Customer #: 23046
JIMMY JOHN'S
703 PROGRESS AVE
WATERLOO, IA 50701
Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
715 Mulberry St
WATERLOO, IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION - 703 PROGRESS AVE - 03/16/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER # BILLING DATE
23046
03/16/2026
DUE DATE
04/20/2026
City of Waterloo
INVOICE #
2026-00000376
Less Prepayment
Total Due —
CHARGES
$80.00
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
sFA /..N)LiLo
Waterloo Fire Rescue
Inspection Report
Jimmy Johns - 703 Progress AVE, BLDG 703 Progress Ave, Waterloo IA 50701
INSPECTION DETAILS
Inspection Date
0311612026
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
1115
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
039
Passed codes
NEXT STEPS
0 7
Failed codes
30
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 03/16/2026 @ 12:29
• $80 annual inspection fee
BRAD BALDWIN - 03/1612026 @ 12:36
Fire extinguisher due annually serviced in December 2026
BRAD BALDWIN - 03116/2026 @ 12:40
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
0411512026
BRAD BALDWIN - 03/16/2026 @ 12:40
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Jeff Marsh (2026)
CHECKLISTS
E __
Date: BRAD BALDWIN 0311612026
GENERATED ON 3/16/26, 12:43 PM
1 OF 4
Emergency Equipment
Status Code
Fail
O
Fail
O
Fail
O
Fail
®
Fail
O
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Fire Service Features
Status
Fail
O
Code
506.2 - Key box maintenance.
The operator of the building shall immediately notify the fire
code official and provide the new key where a lock is changed
or rekeyed. The key to such lock shall be secured in the key
box.
Description
Location: Egress lights (2) above dining tables
Comments: Repair or replace emergency egress lights (2) that failed
to illuminate during test.
Location: Men's bathroom
Comments: Repair or replace egress Tight that failed to illuminate
during test.
Location: Women's bathroom
Comments: Repair or replace egress light that failed to illuminate
during test.
Location: Front exit
Comments: Repair or replace exit sign that failed to illuminate during
test.
Location: Back exit
Comments: Repair or replace exit sign that failed to illuminate during
test.
Description
Location: Knox Box
Comments: Notify Waterloo Fire Department if master keys have
changed to update Knox Box. Notify inspector if no changes are
necessary.
GENERATED ON 3/16/26, 12:43 PM
2 OF 4
Electrical Safety
Status Code
Fail 603.4 - Working space and clearancesclearance.
Ox A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
Tess, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Description
Location: Electric panel
Comments: Remove obstruction (rag bag) from accessing panel,
maintain 36" clear path of access at all times.
GENERATED ON 3/16/26, 12:43 PM
3 OF 4
ro
FEE
Statement of Fees
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $80.00
Invoice Number
NIA
Check Number Transaction Number
NIA NIA
GENERATED ON 3/16/26, 12:43 PM
4 OF 4