COMMERCIAL INSPECTION - 602 BROADWAY ST - 03/13/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
24931
BILLING DATE
03/16/2026
DUE DATE
04/20/2026
INVOICE #
2026-00000386
CI3ARGES
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
A
•
So 2L4951
Waterloo Fire Rescue
Inspection Report
Tortas Tacos - 602 Broadway ST, BLDG 602 Broadway St, Waterloo IA 50703
INSPECTION DETAILS
Inspection Date
0311312026
Lead lnspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other lnspectors
NIA
425 E. 3rd Street
Inspection Number
21158
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
043 08 ®26
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 03/1312026 @ 14:03
• $80 annual inspection fee
BRAD BALDWIN - 03/1312026 @ 14:07
Christmas lights approved for temporary usage (90 days).
BRAD BALDWIN - 0311312026 @ 14:28
Fire extinguishers due annually service in May 2026
BRAD BALDWIN - 0311312026 @ 14:38
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 0311312026 @ 14:38
Reinspection Date
04/1012026
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Fermin Miranda Date:
CHECKLISTS
BRAD BALDWIN 03113/2026
GENERATED ON 3/13/26, 2:40 PM 1 OF 7
Additional Codes
Scat <s Cod
Fail
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
Description
Location: Water heater
Comments: Licensed plumbing contractor shall obtain permit and
inspection for water heater installed not to code and without permit
GENERATED ON 3/13/26, 2:40 PM
2 OF 7
Fail
5303.5.3 - Securing compressed gas containers, cylinders
and tanks.
Compressed gas containers, cylinders and tanks shall be
secured to prevent falling caused by contact, vibration or
seismic activity. Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers, cylinders and tanks to a fixed object
with one or more restraints. 2.Securing containers, cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers, cylinders or tanks.
3. Nesting of compressed gas containers, cylinders and tanks
at container filling or servicing facilities or in sellers'
warehouses not open to the public. Nesting shall be allowed
provided that the nested containers, cylinders or tanks, if
dislodged, do not obstruct the required means of egress.
4.Securing of compressed gas containers, cylinders and
tanks to or within a rack, framework, cabinet or similar
assembly designed for such use. Exception: Compressed gas
containers, cylinders and tanks in the process of
examination, filling, transport or servicing.
Location: Basement
Comments: Secure compressed gas cylinders with chain to avoid tip
over.
GENERATED ON 3/13/26, 2:40 PM
3 OF 7
Fail
606.2 - Where required.
A Type 1 hood shall be installed at or above all commercial
cooking appliances and domestic cooking appliances used
for commercial purposes that produce grease vapors.
Exceptions: 1.Factory-built commercial exhaust hoods that
are listed and labeled in accordance with UL 710, and
installed in accordance with Section 304,1 of the International
Mechanical Code, shall not be required to comply with
Sections 507.1.5, 507.2.3, 507.2.5, 507.2.8, 507.3.1, 507.3.3,
507.4 and 507.5 of the International Mechanical Code.
2.Factory-built commercial cooking recirculating systems that
are listed and labeled in accordance with UL 7108, and
installed in accordance with Section 304.1 of the International
Mechanical Code, shall not be required to comply with
Sections 507.1.5, 507.2.3, 507.2.5, 507.2.8, 507.3.1, 507.3.3,
507.4 and 507.5 of the International Mechanical Code. Spaces
in which such systems are located shall be considered to be
kitchens and shall be ventilated in accordance with Table
403.3.1.1 of the International Mechanical Code. For the
purpose of determining the floor area required to be
ventilated, each individual appliance shall be considered as
occupying not less than 100 square feet (9.3 m2). 3.Where
cooking appliances are equipped with integral down -draft
exhaust systems and such appliances and exhaust systems
are listed and labeled for the application in accordance with
NFPA 96, a hood shall not be required at or above them. 4.A
Type 1 hood shall not be required for an electric cooking
appliance where an approved testing agency provides
documentation that the appliance effluent contains 5 mglm3
or less of grease when tested at an exhaust flow rate of 500
cfm (0.236 m3/s) in accordance with UL 7108.
General Housekeeping
Statue Code
Fail
304.3.1 - Spontaneous ignition.
Materials susceptible to spontaneous ignition, such as oily
rags, shall be stored in a listed disposal container. Contents
of such containers shall be removed and disposed of daily.
Comments: Cooktop must be under Type 1 hood with at least a 6"
overlap and protected by fire suppression system. Move appliance
under hood.
Description
Location: Oily Rags
Comments: Provide listed container for oily rag disposal. See
attachment
GENERATED ON 3/13/26, 2:40 PM
4 OF 7
Electrical Safety
Staint4_ Code
Fail
Fail
603.5 - Relocatable power taps and current taps.Muliiplug
adapters.
Multiplug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Description
Location: Ice machine, slushie machine, fridges
Comments: Remove multi -plug adapters behind multiple appliances.
Relocate appliances to individually plug directly to wall outlet or
licensed electrical contractor shall add outlets by obtaining permits
and inspections.
Location: Between register counter and kitchen
Comments: Remove green extension cord to security cameras. May
replace with properly mounted power strip with manual reset for light
duty electric only.
GENERATED ON 3/13/26, 2:40 PM
5 OF 7
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Commercial Cooking Hood Suppression System
Sti A+s3 Code
Fail 606.3.3.2 - Grease accumulation.
If during the inspection it is found that hoods, grease -removal
devices, fans, ducts or other appurtenances have an
accumulation of grease, such components shall be cleaned in
accordance with ANSIAKECA C10.
Location: South kitchen door
Comments: Remove brown extension cord wrapped around door
closure hardware.
Description
Location: Kitchen exhaust hood
Comments: Clean excess grease in hood, filters currently dripping
grease.