COMMERCIAL INSPECTION - 2040 KIMBALL AVE - 03/11/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
15150
03/16/2026
04/20/2026
2026-00000380
$80.00
Less Prepayment
Total Due --÷
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
,sgp 15150
Waterloo Fire Rescue
Inspection Report
Cabin Coffee Co. - 2040 Kimball AVE, BLDG 2040 Kimball Ave, Waterloo IA 50701
INSPECTION DETAILS
Inspection Date
03/11/2026
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
4600
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
33
Passed codes
NEXT STEPS
7
Failed codes
37
N/A codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 03/11/2026 @ 15:40
$80 annual inspection fee
BRAD BALDWIN - 03/12/2026 @ 07:34
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
04/1012026
BRAD BALDWIN - 03/1212026 @ 07:34
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Grant Rothweiler (2026)
CHECKLISTS
Date: BRAD BALDWIN 03/12/2026
GENERATED ON 3/12/26, 7:36 AM 1 OF 5
Emergency Equipment
Status Code
Fail
O
Fail
O
Fail
O
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required Toad for a duration of not less than 90 minutes.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not Tess than 90 minutes.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Description
Location: Front exit
Comments: Repair or replace exit sign, very dull during testing.
Location: Exit near bathrooms
Comments: Repair or replace exit sign and egress lights that failed to
illuminate during test.
Location: Exit near office
Comments: Repair or replace exit sign and egress lights that failed to
illuminate during test.
Additional Codes
Status Code Description
Fail 603.1.1- Equipment and fixtureswiring.
xO Electrical equipment and fixtures All electrical equipment, Location: Coffee grinder
wiring, devices and appliances shall be tested; and listed by Comments: Remove appliance from power strip, shall plug directly to
an approved agency and labeled; and installed, used and wall outlet.
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
GENERATED ON 3/12/26, 7:36 AM
2 OF 5
Electrical Safety
Status Code Description
Fail 603.6 - Extension cords.
OExtension cords and flexible cordsshall not be a substitute Location: Mechanical room
for permanent wiring and shall be listed and labeled in Comments: Remove brown extension cord plugged to security
accordance with UL 817. Extension cords and flexible camera.
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Below register
Comments: Remove brown extension cord below counter
GENERATED ON 3/12/26, 7:36 AM 3 OF 5
Portable Fire Extingusihers
Status Code
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Location: Fire extinguishers
Comments: Provide annual service to all extinguishers, last recorded
service completed in 2021
GENERATED ON 3/12/26, 7:36 AM