KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION - 1451 ANSBOROUGH AVE -
03/11/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
6280
03/16/2026
04/20/2026
City of Waterloo
2026-00000382
Less Prepayment
Total Due -*
$80.00
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Domino's Pizza - 1451 Ansborough AVE, BLDG 1451 Ansborough Ave, Waterloo IA
50701
INSPECTION DETAILS
Inspection Date
03/11/2026
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
613
Shift Station Unit
NIA NIA N/A
SUMMARY OF INSPECTION
0 40
Passed codes
NEXT STEPS
0 7
Failed codes
0 28
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 0311212026 @ 14:03
• $80 annual inspection fee
BRAD BALDWIN - 03/12/2026 @ 14:16
Fire extinguishers due annually serviced in July 2026
BRAD BALDWIN - 03/12/2026 @ 14:30
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 03/12/2026 @ 14:31
Reinspection Date
04/1012026
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 03/12/2026 @ 14:31
• Request of specific time on scheduled inspection date or change of inspection date shall be made by business representative prior to scheduled
inspection date. Failure to request time or change of date will result in failed inspection.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Kelly (2026) Date: BRAD BALDWIN 03/12/2026
CHECKLISTS
GENERATED ON 3/12/26, 2:33 PM 1 OF 7
Means of Egress
Status Code
Fail
1032.2 - Reliability.
Required exit accesses, exits and exit discharges shall be
continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
Description
Location: North exit door
Comments: Repair or replace door that failed to open during
inspection. Staff actively working on door closure during inspection.
GENERATED ON 3/12/26, 2:33 PM
2 OF 7
General Housekeeping
Status Code
Description
Fail 315.3 - Storage in buildings.
0 Storage of materials in buildings shall be orderly and stacks Location: Mechanical room
shall be stable. Storage of combustible materials shall be Comments: Remove storage from within 36 inches of furnace.
separated from heaters or heating devices by distance or
shielding so that ignition cannot occur.
Fail 315.3.1- Ceiling clearance.
0 Storage shall be maintained 2 feet (610 mm) or more below Location: Laundry room
the ceiling in nonsprinklered areas of buildings or not less Comments: Remove storage from within 24 inches of ceiling
than 18 inches (457 mm) below sprinkler head deflectors in
sprinklered areas of buildings. Exceptions: 1.The 2-foot (610
mm) ceiling clearance is not required for storage along walls
in nonsprinklered areas of buildings. 2.The 18-inch (457 mm)
ceiling clearance is not required for storage along walls in
areas of buildings equipped with an automatic sprinkler
system in accordance with Section 903.3.1.1, 903.3.1.2 or
903.3.1.3.
GENERATED ON 3/12/26, 2:33 PM
3 OF 7
Fail
O
315.3.3 - Equipment rooms.
Combustible material shall not be stored in boiler rooms,
mechanical rooms, electrical equipment rooms or in fire
command centers as specified in Section 508.1.5.
Location: Back furnace room
Comments: Remove combustible material (boxes and paperwork)
from mechanical room.
GENERATED ON 3/12/26, 2:33 PM
4 OF 7
Electrical Safety
Status Code
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Description
Location: Office
Comments: Remove cord from above drop ceiling, shall not be
installed in concealed area.
GENERATED ON 3/12/26, 2:33 PM 5 OF 7
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Additional Codes
Status
Fail
Code
610.1.2 - Maintenance.
The lint trap, mechanical and heating components, and the
exhaust duct system of a clothes dryer shall be maintained in
accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that
prevents the exhaust of air and products of combustion.
Location: Laundry room
Comments: Remove cords from above drop ceiling, shall not be
installed in concealed space. Installing new outlet requires licensed
electrical contractor obtaining proper permit and inspection.
Description
Location: Clothes dryer
Comments: Provide documentation of cleaning of dryer vent from
appliance to the outside of the building with signature and date.
Email documentation to fire inspector.