RENTAL INSPECTION - 516 STRATFORD AVE - 03/16/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
NO SHOW INSPECTION FEE
REINSPECTION FEE 3RD
$100.00
$250.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
24911
03/16/2026
04/20/2026
2026-00000080
$350.00
Less Prepayment
Total Due —*
City of Waterloo
$0.00
$350.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
3S0
Waterloo Fire Rescue
Inspection Report
BLDG 516 Stratford - 516 Stratford AVE, Waterloo IA 50701-5832
INSPECTION DETAILS
Inspection Date
03/1612026
Inspection Type
Rental Inspection l REINSPECTION
425 E. 3rd Street
Inspection Number
15981-R4
Lead Inspector Shift Station Unit
Randy Girsch N/A N/A NIA
Other lnspectors
NIA
SUMMARY OF INSPECTION
00 056
Passed codes Failed codes
NEXT STEPS
Please direct questions about your Inspection to:
Randy Girsch
randy.girsch@waterloo-ia.org
GENERAL NOTES
Randy Girsch - 02/16/2026 @ 11:31
Property Safety Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-464-5605
Reinspection Date
04/13/2026
Randy Girsch - 02/16/2026 @ 11:31
-Re-inspection date is as posted on the inspection report given, the rental unit's responsible personls shall reach out prior to set time of that re -
inspection. If all corrections are made before the scheduled inspection, you can call to set up an earlier re -inspection. Appropriate notices shall be given
to occupants of the units. Owner or owner's agent must be present during inspections. Failure to schedule a time on the date given or failure to keep the
inspection will result in a $100 fee. *****Re inspection fees may be assessed for re -inspections. Re -inspection fees start at $50, then $150, and $250 for all
subsequent re -inspections. All appropriate keys to gain entry to locked units shall be readily available during re -inspection.
Randy Girsch - 0211612026 @ 11:31
Exterior surfaces repairs and corrections that do not cause an unsafe condition to the building or occupants of the building will be allowed to be made in
spring time when weather permits such work to be made.
Randy Girsch - 02116/2026 @ 11:31
4/17 - $100 No show fee for scheduled inspection, $50 re -inspection fee for corrections incomplete.
Randy Girsch - 02/16/2026 @ 11:31
Tree west of house split at base with potential to break off towards house noted.
GENERATED ON 3/16/26, 10:11 AM 1 OF 13
Randy Girsch - 02/16/2026 @ 11:31
$100.00 No show fee for scheduled inspection, $100.00 re -inspection fee for corrections incomplete.
Randy Girsch - 03116/2026 @ 09:53
03-16-2026 - Randy Girsch $100 No Show fee for scheduled inspection, $250 re -inspection fee for corrections incomplete. Re -inspection will be set for
Monday April 13th @ 9:00 am.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Cheryl Hill Date:
CHECKLISTS
Randy Girsch 03116/2026
GENERATED ON 3/16/26, 10:11 AM 2 OF 13
Reinspection
siaitos Code
Fail
Fail
Fail
Fail
Fail
Fail
1010.2 - Door operations.
Except as specifically permitted by this section, egress doors
shall be readily openable from the egress side without the
use of a key or special knowledge or effort.
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Description
Location: 2nd floor bedroom doors
Comments: Locking devices on outside of bedroom doors shall be
removed.
Location: 2nd floor toilet room
Comments: Electrical box on wall open without cove' and loose wires
uncapped or connected. 605.1 Installation. Electrical equipment,
wiring and appliances shall be properly installed and maintained in a
safe and approved manner.
Location: Main floor bedroom outlets
Comments: Outlet south of doorway (per tenant) "sparks and
smokes". Outlets shall be secured tightly in place and have
appropriate covers installed.
Location: Living room outlet below window
Comments: Outlet missing cover shall be corrected. IPMC 605.2 - All
receptacle outlets shall have the appropriate faceplate cover for the
location.
Location: Dining room outlets
Comments: Missing covers shall be corrected. 605.2 Receptacles All
receptacle outlets shall have the appropriate faceplate cover for the
location.
Location: Laundry washer outlet
Comments: Outlet shows sign of damage, shall be replaced. 604.3
Electrical system hazards. Where it is found that the electrical system
in a structure constitutes a hazard to the occupants or the structure
by reason of inadequate service, improper fusing, insufficient
receptacle and lighting outlets, improper wiring or installation,
deterioration or damage, or for similar reasons, the code official shall
require the defects to be corrected to eliminate the hazard.
GENERATED ON 3/16/26, 10:11 AM 3 OF 13
Fail
O
Fail
Fail
Fail
O
Fail
O
Fail
®
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Location: Main floor bath Tight switch
Comments: Light switch loose shall be tightly fastened.
Location: Main floor bedroom extension cords
Comments: Multiple extension cords noted shall not be used for
permanent wiring. Informed tenants of hazards of. 605.4 Wiring.
Flexible cords shall not be used for permanent wiring, or for running
through doors, windows, or cabinets, or concealed within walls,
floors, or ceilings
Location: Ceiling fan
Comments: Fan and electrical wiring shall be installed as
manufactured to be installed.
Location: Kitchen light fixture
Comments: Light fixture hanging by wires shall be corrected to be
installed as manufactured.
Location: Main floor bathroom light/electrical wiring
Comments: Wiring for light fixture shall be installed to code. Permit
and inspection shall be obtained
Location: 2nd floor bedroom #1 (clockwise)
Comments: Broken light switch cover shall be replaced.
GENERATED ON 3/16/26, 10:11 AM 4 OF 13
Fail
Fail
Fail
Fail
Fail
Fail
907.2.11.2 - Groups R-2, R-3, R-4 and 1-1.
Single- or multiple -station smoke alarms shall be installed
and maintained in Groups R-2, R-3, R-4 and 1-1 regardless of
occupant load at all of the following locations: 1.On the
ceiling or wall outside of each separate sleeping area in the
immediate vicinity of bedrooms. 2.ln each room used for
sleeping purposes. 3.In each story within a dwelling unit,
including basements but not including crawl spaces and
uninhabitable attics. In dwellings or dwelling units with split
levels and without an intervening door between the adjacent
levels, a smoke alarm installed on the upper level shall suffice
for the adjacent lower level provided that the lower level is
less than one full story below the upper level.
907.2.11.2 - Groups R-2, R-3, R-4 and 1-1.
Single- or multiple -station smoke alarms shall be installed
and maintained in Groups R-2, R-3, R-4 and 1-1 regardless of
occupant load at all of the following locations: 1.On the
ceiling or wall outside of each separate sleeping area in the
immediate vicinity of bedrooms. 2.In each room used for
sleeping purposes. 3.In each story within a dwelling unit,
including basements but not including crawl spaces and
uninhabitable attics. In dwellings or dwelling units with split
levels and without an intervening door between the adjacent
levels, a smoke alarm installed on the upper level shall suffice
for the adjacent lower level provided that the lower level is
less than one full story below the upper level.
915.2.1- Dwelling units.
Carbon monoxide detection shall be installed in dwelling
units outside of each separate sleeping area in the immediate
vicinity of the bedrooms. Where a fuel -burning appliance is
located within a bedroom or its attached bathroom, carbon
monoxide detection shall be installed within the bedroom.
R2 - Unsafe Equipment
Was the presence of unsafe equipment noted during the
inspection? Equipment may include boilers, heating
equipment, elevator, moving stairways, electrical wiring, and
flammable liquid containers. (IPMC 108.1.2)
R5 - Exterior Structure
Is the exterior of the structure maintained in good repair,
structurally sound and sanitary state? (IPMC 304)
R5 - Exterior Structure
Is the exterior of the structure maintained in good repair,
structurally sound and sanitary state? (IPMC 304)
Location: 2nd floor bedrooms
Comments: Smoke detectors required installed properly in
accordance to manufactures guidelines in bedrooms and in good
working condition.
Location: Main floor bedroom smoke detector
Comments: Missing detector shall be corrected. Smoke detectors
required installed properly in accordance to manufactures guidelines
in bedrooms and in good working condition.
Location: Outside 2nd floor bedrooms
Comments: Carbon monoxide detector shall be properly installed in
near proximity to bedrooms.
Location: Electrical panel (basement)
Comments: Panel cover not installed shall be corrected ASAP.
Location: South entry storm & main doors
Comments: Doors missing latching hardware shall be corrected.
304.15 Doors. Exterior doors, door assemblies, operator systems if
provided, and hardware shall be maintained in good condition. Locks
at all entrances to dwelling units and sleeping units shall tightly
secure the door. Locks on means of egress doors shall be in
accordance with Section 702.3.
Location: Kitchen entry door
Comments: Door unable to lock shall be corrected ASAP. Nails bent
over currently holding door in "shut" position. 304.15 Doors. Exterior
doors, door assemblies, operator systems if provided, and hardware
shall be maintained in good condition. Locks at all entrances to
dwelling units and sleeping units shall tightly secure the door. Locks
on means of egress doors shall be in accordance with Section 702.3.
GENERATED ON 3/16/26, 10:11 AM 5 OF 13
Fail
Fail
Fail
Fail
Fail
Fail
O
Fail
0
R5 - Exterior Structure
Is the exterior of the structure maintained in good repair,
structurally sound and sanitary state? (IPMC 304)
R5 - Exterior Structure
Is the exterior of the structure maintained in good repair,
structurally sound and sanitary state? (IPMC 304)
R5 - Exterior Structure
Is the exterior of the structure maintained in good repair,
structurally sound and sanitary state? (IPMC 304)
R5 - Exterior Structure
Is the exterior of the structure maintained in good repair,
structurally sound and sanitary state? (IPMC 304)
R5 - Exterior Structure
Is the exterior of the structure maintained in good repair,
structurally sound and sanitary state? (IPMC 304)
R5 - Exterior Structure
Is the exterior of the structure maintained in good repair,
structurally sound and sanitary state? (IPMC 304)
R5 - Exterior Structure
Is the exterior of the structure maintained in good repair,
structurally sound and sanitary state? (IPMC 304)
Location: Kitchen windows
Comments: North kitchen window failed to open easily shall be
corrected. 304.13.2 Openable Windows. Every window, other than a
manufactured fixed window, shall be easily openable and capable of
being held in position by the originally intended means of window
hardware.
Location: 2nd floor bedroom window
Comments: Cracked window shall be corrected. 304.13.1 Glazing.
Glazing materials shall be maintained free from cracks and holes.
Location: West side stairs
Comments: Stairs missing guardraillhandrail shall be corrected. Prior
to installation requires building permit and inspection to follow. 307.1
General. Every exterior and interior flight of stairs having more than
four risers shall have a handrail on one side of the stair and every
open portion of a stair, landing, balcony, porch, deck, ramp or other
walking surface that is more than 30 inches (762 mm) above the floor
or grade below shall have guards.
Location: Roof
Comments: Metal roof overlay installation incomplete, contractor is
waiting for parts on order. Building inspection shall be obtained when
work completed.
Location: SW corner foundation wall
Comments: Openings in foundation wall shall be corrected by means
of tuck -pointing. 304.5 Foundation walls. Foundation walls shall be
maintained plumb and free from open cracks and breaks and shall be
kept in such condition so as to prevent the entry of rodents and other
pests.
Location: Windows & north door installations.
Comments: Missing trim on doors & windows, interior framing
unprotected from exterior elements shall be corrected. 304.2
Protective treatment. Exterior surfaces, including but not limited to,
doors, door and window frames, cornices, porches, trim, balconies,
decks and fences, shall be maintained in good condition. Exterior
wood surfaces, other than decay -resistant woods, shall be protected
from the elements and decay by painting or other protective covering
or treatment. Peeling, flaking and chipped paint shall be eliminated
and surfaces repainted. Siding and masonry joints, as well as those
between the building envelope and the perimeter of windows, doors
and skylights, shall be maintained weather resistant and water tight.
Metal surfaces subject to rust or corrosion shall be coated to inhibit
such rust and corrosion, and surfaces with rust or corrosion shall be
stabilized and coated to inhibit future rust and corrosion.
Location: Vent discharge covers
Comments: Appropriate vent discharge covers shall be installed
where missing. Pics of attached.
GENERATED ON 3/16/26, 10:11 AM 6 OF 13
Fail
Fail
Fail
O
Fail
O
Fail
Fail
O
R5 - Exterior Structure
Is the exterior of the structure maintained in good repair,
structurally sound and sanitary state? (IPMC 304)
R5 - Exterior Structure
Is the exterior of the structure maintained in good repair,
structurally sound and sanitary state? (IPMC 304)
R5 - Exterior Structure
Is the exterior of the structure maintained in good repair,
structurally sound and sanitary state? (IPMC 304)
R5 - Exterior Structure
Is the exterior of the structure maintained in good repair,
structurally sound and sanitary state? (IPMC 304)
R5 - Exterior Structure
Is the exterior of the structure maintained in good repair,
structurally sound and sanitary state? (IPMC 304)
R5 - Exterior Structure
Is the exterior of the structure maintained in good repair,
structurally sound and sanitary state? (IPMC 304)
Location: NE broken window
Comments: Broken window shall be replaced. 304.13.1 Glazing.
Glazing materials shall be maintained free from cracks and holes
Location: North deck guardrail
Comments: Missing spindles in guardrail shall be corrected. 304.12
Handrails and guards. Every handrail and guard shall be firmly
fastened and capable of supporting normally imposed loads and
shall be maintained in good condition
Location: South porch decking
Comments: Deteriorated or defective decking floor boards shall be
replaced. 305.4 Stairs and walking surfaces. Every stair, ramp,
landing, balcony, porch, deck or other walking surface shall be
maintained in sound condition and good repair.
Location: South corners of building
Comments: Openings to exterior elements allowing weather shall be
corrected 304.6 Exterior walls. Exterior walls shall be free from holes,
breaks, and loose or rotting materials; and maintained weatherproof
and properly surface coated where required to prevent deterioration
Location: West exterior door
Comments: Untreated plywood in place of glass shall be corrected.
Door shall maintain weather -tight, exterior of door shall maintain
protected from elements. (IPMC) - 304.2 Protective treatment. Exterior
surfaces, including but not limited to, doors, door and window
frames, cornices, porches, trim, balconies, decks and fences, shall be
maintained in good condition. Exterior wood surfaces, other than
decay -resistant woods, shall be protected from the elements and
decay by painting or other protective covering or treatment. Peeling,
flaking and chipped paint shall be eliminated and surfaces repainted.
Siding and masonry joints, as well as those between the building
envelope and the perimeter of windows, doors and skylights, shall be
maintained weather resistant and water tight.
Location: East side window coverings
Comments: Untreated window coverings shall maintain weather -tight,
exterior of door shall maintain protected from elements. (IPMC) -
304.2 Protective treatment. Exterior surfaces, including but not
limited to, doors, door and window frames, cornices, porches, trim,
balconies, decks and fences, shall be maintained in good condition.
Exterior wood surfaces, other than decay -resistant woods, shall be
protected from the elements and decay by painting or other
protective covering or treatment. Peeling, flaking and chipped paint
shall be eliminated and surfaces repainted. Siding and masonry
joints, as well as those between the building envelope and the
perimeter of windows, doors and skylights, shall be maintained
weather resistant and water tight.
GENERATED ON 3/16/26, 10:11 AM 7 OF 13
Fail
O
Fail
O
Fail
O
R5 - Exterior Structure
Is the exterior of the structure maintained in good repair,
structurally sound and sanitary state? (IPMC 304)
R5 - Exterior Structure
Is the exterior of the structure maintained in good repair,
structurally sound and sanitary state? (IPMC 304)
R5 - Exterior Structure
Is the exterior of the structure maintained in good repair,
structurally sound and sanitary state? (IPMC 304)
Location: North deck guardrail.
Comments: Deck guardrail (east side) has become loose from
framing and unable to support imposed Toads. 304.12 Handrails and
guards. Every handrail and guard shall be firmly fastened and
capable of supporting normally imposed loads and shall be
maintained in good condition
Location: Chimney
Comments: Chimney lacks maintenance, shall be inspected by
professional contractor for necessary repairs.
Location: West side exterior entry door.
Comments: Plywood in place of window untreated shall be treated to
protect from weather elements or glass installed.
GENERATED ON 3/16/26, 10:11 AM
8 OF 13
Fail
Fail
Fail
Fail
Fail
Fail
R5 - Exterior Structure
Is the exterior of the structure maintained in good repair,
structurally sound and sanitary state? (IPMC 304)
R5 - Exterior Structure
Is the exterior of the structure maintained in good repair,
structurally sound and sanitary state? (IPMC 304)
R6 - Interior Structure
Has the interior of the structure and equipment inside been
maintained in good repair, structurally sound, and in a
sanitary condition? (IPMC 305)
R6 - Interior Structure
Has the interior of the structure and equipment inside been
maintained in good repair, structurally sound, and in a
sanitary condition? (IPMC 305)
R6 - Interior Structure
Has the interior of the structure and equipment inside been
maintained in good repair, structurally sound, and in a
sanitary condition? (IPMC 305)
R6 - Interior Structure
Has the interior of the structure and equipment inside been
maintained in good repair, structurally sound, and in a
sanitary condition? (IPMC 305)
Location: East side basement window coverings
Comments: Plywood window coverings untreated shall be treated to
protect from weather elements or glass in good condition installed.
Location: North side deck guardrail
Comments: Guardrail on east side of deck unable to withstand
imposed force, loose from framing shall be corrected.
Location: Kitchen vanity cabinets
Comments: Holes in, damaged, defective vanity cabinets shall be
repaired or replaced.
Location: Wall surface near 2nd floor closet (top of stairs)
Comments: Wall covering missing around doorway shall be
corrected.
Location: 2nd floor bedroom ceiling surfaces
Comments: Peeling paint and all loose surfaces shall be
removed/repaired. 305.3 Interior surfaces. Interior surfaces, including
windows and doors, shall be maintained in good, clean and sanitary
condition. Peeling, chipping, flaking or abraded paint shall be
repaired, removed or covered. Cracked or loose plaster, decayed
wood and other defective surface conditions shall be corrected.
Location: Dining room ceiling
Comments: Loose surfaces shall be corrected, ceiling surface shall
be repaired. 305.3 Interior surfaces. Interior surfaces, including
windows and doors, shall be maintained in good, clean and sanitary
condition. Peeling, chipping, flaking or abraded paint shall be
repaired, removed or covered. Cracked or loose plaster, decayed
wood and other defective surface conditions shall be corrected.
GENERATED ON 3/16/26, 10:11 AM
9 OF 13
Fail
Q
Fail
Fail
O
Fail
0
Fail
R6 - Interior Structure
Has the interior of the structure and equipment inside been
maintained in good repair, structurally sound, and in a
sanitary condition? (IPMC 305)
R6 - Interior Structure
Has the interior of the structure and equipment inside been
maintained in good repair, structurally sound, and in a
sanitary condition? (IPMC 305)
R6 - Interior Structure
Has the interior of the structure and equipment inside been
maintained in good repair, structurally sound, and in a
sanitary condition? (IPMC 305)
R6 - Interior Structure
Has the interior of the structure and equipment inside been
maintained in good repair, structurally sound, and in a
sanitary condition? (IPMC 305)
R6 - Interior Structure
Has the interior of the structure and equipment inside been
maintained in good repair, structurally sound, and in a
sanitary condition? (IPMC 305)
Fail R6.C. - Mechanical Eqiupment
OAre mechanical appliances properly installed and maintained
in good working condition? (IPMC 603.1)
Fail R6.C. - Mechanical Eqiupment
OAre mechanical appliances properly installed and maintained
in good working condition? (IPMC 603.1)
Location: 2nd floor toilet room
Comments: Door missing to toilet room and openings in walls fail to
provide privacy required. [P] 503.1 Privacy. Toilet rooms and
bathrooms shall provide privacy and shall not constitute the only
passageway to a hall or other space, or to the exterior. A door and
interior locking device shall be provided for all common or shared
bathrooms and toilet rooms in a multiple dwelling.
Location: Stairway to 2nd floor handrail.
Comments: Handrail loose shall be fastened tightly. 304.12 Handrails
and guards. Every handrail and guard shall be firmly fastened and
capable of supporting normally imposed loads and shall be
maintained in good condition
Location: 2nd floor flooring
Comments: Carpet tack strips are present without carpet attached.
Tack strips shall either be removed or carpet installed. 305.4 Stairs
and walking surfaces. Every stair, ramp, landing, balcony, porch,
deck or other walking surface shall be maintained in sound condition
and good repair.
Location: Stairway to basement handrail
Comments: Missing guardrail & handrail shall be corrected. Building
permit and inspections shall be obtained. 307.1 General. Every
exterior and interior flight of stairs having more than four risers shall
have a handrail on one side of the stair and every open portion of a
stair, landing, balcony, porch, deck, ramp or other walking surface
that is more than 30 inches (762 mm) above the floor or grade below
shall have guards.
Location: Main floor bathroom door
Comments: Door hinges loose to jamb and door fails to latch, shall
be corrected.
Location: Main floor HVAC registers
Comments: Appropriate register covers shall be installed/ 607.1
General. Duct systems shall be maintained free of obstructions and
shall be capable of performing the required function.
Location: Main floor bathroom exhaust
Comments: Window in bathroom taped shut. Window shall be easily
openable and hold in such position by original hardware or
mechanical exhaust fan installed by licensed contractor with permits
and inspections. 403.2 Bathrooms and toilet rooms. Every bathroom
and toilet room shall comply with the ventilation requirements for
habitable spaces as required by Section 403.1, except that a window
shall not be required in such spaces equipped with a mechanical
ventilation system. Air exhausted by a mechanical ventilation system
from a bathroom or toilet room shall discharge to the outdoors and
shall not be recirculated.
GENERATED ON 3/16/26, 10:11 AM 10 OF 13
Fail
O
Fail
O
Fail
O
Fail
O
Fail
O
R6.E. - Plumbing System and Fixtures
Plumbing fixtures shall be properly installed and maintained
in working order, and shall be kept free from obstructions,
leaks and defects and be capable of performing the function
for which such plumbing fixtures are designed. Plumbing
fixtures shall be maintained in a safe, sanitary and functional
condition. (IPMC 504.1)
R6.E. - Plumbing System and Fixtures
Plumbing fixtures shall be properly installed and maintained
in working order, and shall be kept free from obstructions,
leaks and defects and be capable of performing the function
for which such plumbing fixtures are designed. Plumbing
fixtures shall be maintained in a safe, sanitary and functional
condition. (IPMC 504.1)
R6.E. - Plumbing System and Fixtures
Plumbing fixtures shall be properly installed and maintained
in working order, and shall be kept free from obstructions,
leaks and defects and be capable of performing the function
for which such plumbing fixtures are designed. Plumbing
fixtures shall be maintained in a safe, sanitary and functional
condition. (IPMC 504.1)
R6.E. - Plumbing System and Fixtures
Plumbing fixtures shall be properly installed and maintained
in working order, and shall be kept free from obstructions,
leaks and defects and be capable of performing the function
for which such plumbing fixtures are designed. Plumbing
fixtures shall be maintained in a safe, sanitary and functional
condition. (IPMC 504.1)
R6.E. - Plumbing System and Fixtures
Plumbing fixtures shall be properly installed and maintained
in working order, and shall be kept free from obstructions,
leaks and defects and be capable of performing the function
for which such plumbing fixtures are designed. Plumbing
fixtures shall be maintained in a safe, sanitary and functional
condition. (IPMC 504.1)
Location: Main floor vanity faucet
Comments: Faucet spout loose and handles installed backwards.
Location: Kitchen sink drain piping.
Comments: Improper drainage ("s trap" not allowed) installation shall
be corrected. Installation of waste/vent piping shall be done by
licensed plumber with permit and inspections obtained. [P] 504.3
Plumbing system hazards. Where it is found that a plumbing system
in a structure constitutes a hazard to the occupants or the structure
by reason of inadequate service, inadequate venting, cross
connection, backsiphonage, improper installation, deterioration or
damage or for similar reasons, the code official shall require the
defects to be corrected to eliminate the hazard.
Location: 2nd floor toilet
Comments: Tenant has stated toilet is not functional due to defective
parts. Repairs shall be made to rectify if necessary. [P] 504.1 General.
Plumbing fixtures shall be properly installed and maintained in
working order, and shall be kept free from obstructions, leaks and
defects and be capable of performing the function for which such
plumbing fixtures are designed. Plumbing fixtures shall be
maintained in a safe, sanitary and functional condition.
Location: Basement laundry drainage
Comments: Laundry drainage shall be properly connected to building
sewer system or laundry washer removed from basement.
Connection to sewer system shall be installed by licensed plumber
with permit and inspections obtained. [P] 504.3 Plumbing system
hazards. Where it is found that a plumbing system in a structure
constitutes a hazard to the occupants or the structure by reason of
inadequate service, inadequate venting, cross connection,
backsiphonage, improper installation, deterioration or damage or for
similar reasons, the code official shall require the defects to be
corrected to eliminate the hazard.
Location: Main floor shower walls
Comments: OSB plywood water soaked and shows signs of mold like
substance shall be removed and replaced. Per IRC Code - "Shower
walls shall be a nonabsorbent surface and extend not less than 6ft
above the floor"
GENERATED ON 3/16/26, 10:11 AM
11 OF 13
Fail R6.E. - Plumbing System and Fixtures
Plumbing fixtures shall be properly installed and maintained
in working order, and shall be kept free from obstructions,
leaks and defects and be capable of performing the function
for which such plumbing fixtures are designed. Plumbing
fixtures shall be maintained in a safe, sanitary and functional
condition. (IPMC 504.1)
Fail R6.E. - Plumbing System and Fixtures
Plumbing fixtures shall be properly installed and maintained
in working order, and shall be kept free from obstructions,
leaks and defects and be capable of performing the function
for which such plumbing fixtures are designed. Plumbing
fixtures shall be maintained in a safe, sanitary and functional
condition. (IPMC 504.1)
Fail R6.E. - Plumbing System and Fixtures
Plumbing fixtures shall be properly installed and maintained
in working order, and shall be kept free from obstructions,
leaks and defects and be capable of performing the function
for which such plumbing fixtures are designed. Plumbing
fixtures shall be maintained in a safe, sanitary and functional
condition. (IPMC 504.1)
Fail R6.E. - Plumbing System and Fixtures
Plumbing fixtures shall be properly installed and maintained
in working order, and shall be kept free from obstructions,
leaks and defects and be capable of performing the function
for which such plumbing fixtures are designed. Plumbing
fixtures shall be maintained in a safe, sanitary and functional
condition. (IPMC 504.1)
Location: 2nd floor bathroom sink drainage
Comments: Improper drainage ("s trap" & flexible piping not
approved by code) installation shall be corrected. Installation of
wastelvent piping shall be done by licensed plumber with permit and
inspections obtained. [P] 504.3 Plumbing system hazards. Where it is
found that a plumbing system in a structure constitutes a hazard to
the occupants or the structure by reason of inadequate service,
inadequate venting, cross connection, backsiphonage, improper
installation, deterioration or damage or for similar reasons, the code
official shall require the defects to be corrected to eliminate the
hazard.
Location: Main floor bathroom sink drainage
Comments: Improper drainage ("s trap" not allowed) installation shall
be corrected. Installation of wastelvent piping shall be done by
licensed plumber with permit and inspections obtained. [P] 504.3
Plumbing system hazards. Where it is found that a plumbing system
in a structure constitutes a hazard to the occupants or the structure
by reason of inadequate service, inadequate venting, cross
connection, backsiphonage, improper installation, deterioration or
damage or for similar reasons, the code official shall require the
defects to be corrected to eliminate the hazard.
Location: Water heater
Comments: Pressure relief valve missing drain tubing. Installation
shall be up to plumbing code.
Location: Main floor sink drain
Comments: Pop up assembly sealed shut with silicone, not as
manufactured. Corrections shall be made to be installed as
manufactured.
GENERATED ON 3/16/26, 10:11 AM