COMMERCIAL INSPECTION - 2808 UNIVERSITY AVE - 03/17/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
21329
LUNG DATE
DUE DATE
INVOICE #
CIIARGE
03/20/2026
04/24/2026
2026-00000398
City of Waterloo
Less Prepayment
Total Due —*
$80.00
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
AR) 24g3Co
Waterloo Fire Rescue
Inspection Report
Maid -Rite Diner - 2808 University AVE, BLDG 2808 University Ave, Waterloo IA 50701
INSPECTION DETAILS
Inspection Date
03/17/2026
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
N/A
425 E. 3rd Street
Inspection Number
21223
Shift Station Unit
NIA N/A N/A
SUMMARY OF INSPECTION
G 44
Passed codes
NEXT STEPS
0 10
Failed codes
25
N/A codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 03/17/2026 @ 11:49
• $80 annual inspection fee
BRAD BALDWIN - 03/17/2026 @ 11:52
Kitchen hood exhaust cleaning and hood suppression system inspection due in April 2026
BRAD BALDWIN - 03/17/2026 @ 11:52
Fire extinguishers due annually serviced in April 2026
BRAD BALDWIN - 03/1712026 @ 12:24
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
04/16/2026
BRAD BALDWIN - 03/17/2026 @ 12:24
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 03/17/2026 @ 12:24
• Request of specific time on scheduled inspection date or change of inspection date shall be made by business representative prior to scheduled
inspection date. Failure to request time or change of date will result in failed inspection.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
RIT
Chris Kolling (2026) Date: BRAD BALDWIN 03/17/2026
GENERATED ON 3/17/26, 12:34 PM 1 OF 8
CHECKLISTS
GENERATED ON 3/17/26, 12:34 PM
2 OF 8
Additional Codes
Status Corse
Fail
102.4 - Application of budding code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
(11lu
Intertek_,
SBvz049:4
Description
Location: Air conditioner unit (west side)
Comments: Licensed mechanical contractor shall obtain permit and
inspection for A/C installed without permit.
DAIMN COMF'CiRt I[C HNCit�c.ETiAS�
l9OOi RERM�ER RG WAtLER. TY 51
AC
ASXNMNi1AP
APRASE
vaLiiiS 21k114'
LiRA FOR
MAX FORE AMPS
M Ai:
PS MA% CACUM
C�0.WBREAt'
ROAD DELAY FOE OR HACK 4t BPEARENRE
NW. LIAL,At AMPS as 0.g. Iri
VAN MOT OR PLA 23 LnA
COMARE SSOR ALA 2i'
SHORT CIRCUR CURRE MI SAA Ala SVAMAtTRICAL, PAW kt
MAa(IMUM ALLOWABLE PRESSURF PS* t . ,.
IMPS} �t t}t'�i
ACTOR', CRAROE 02. (KO} R4S0 f S fa. re
Eat PRESSURE IG RANI S7,Y
VJ+1kt;Ih.0
>n•ADVE.R1t.. M}
wA...Q
,0DVERTCNIA,
.
If' RA
PART
Location: Water heater
Comments: Licensed plumbing contractor shall obtain permit and
inspection of water heater (Manufactured October 2025) installed
without permit.
GENERATED ON 3/17/26, 12:34 PM
3 OF 8
Fail 5303.5.3 - Securing compressed gas containers, cylinders
and tanks.
Compressed gas containers, cylinders and tanks shall be
secured to prevent falling caused by contact, vibration or
seismic activity. Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers, cylinders and tanks to a fixed object
with one or more restraints. 2.Securing containers, cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers, cylinders or tanks.
3. Nesting of compressed gas containers, cylinders and tanks
at container filling or servicing facilities or in sellers'
warehouses not open to the public. Nesting shall be allowed
provided that the nested containers, cylinders or tanks, if
dislodged, do not obstruct the required means of egress.
4.Securing of compressed gas containers, cylinders and
tanks to or within a rack, framework, cabinet or similar
assembly designed for such use. Exception: Compressed gas
containers, cylinders and tanks in the process of
examination, filling, transport or servicing.
Fail
610.1.1 - Installation.
Clothes dryer exhaust duct systems shall be installed in
accordance with the International Mechanical Code or the
International Fuel Gas Code , and the manufacturer's
installation instructions.
Location: Top of basement stairs
Comments: Secure compressed gas cylinders with chain to avoid tip
over.
Location: Basement laundry dryer vent
Comments: Remove all screws in dryer vent piping and replace all
piping that previously screwed together. All dryer vent piping
connections shall be made per manufacturers guidelines. Annual
cleaning of vent piping from the appliance to the exterior shall be
documented, kept and provided to inspector at time of request.
GENERATED ON 3/17/26, 12:34 PM
4 OF 8
Emergency Equipment
Status Code
Fail
Fail
Fail
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
Description
Location: North dining exit
Comments: Repair or replace emergency egress Tight that failed to
illuminate during test. Lights shall be directed downwards to
illuminate path of exit.
Location: South dining exit
Comments: Repair or replace egress lighting that failed to illuminate
during test.
Location: West exit by office
Comments: Repair or replace egress lighting that failed to illuminate
during test.
GENERATED ON 3/17/26, 12:34 PM
5 OF 8
Electrical Safety
Status Code
Fail 603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Description
Location: Light fixture at top of basement stairs
Comments: Provide knockout plug to opening in bottom of box
GENERATED ON 3/17/26, 12.:34 PM 6 OF 8
Fail
Fail
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
603.4.1- Labeling.
Doors into electrical control panel rooms shall be marked
with a plainly visible and legible sign stating "ELECTRICAL
ROOM" or similar approved wording. The disconnecting
means for each service, feeder or branch circuit originating
on a switchboard or panelboard shall be legibly and durably
marked to indicate its purpose unless such purpose is clearly
evident. Where buildings or structures are supplied by more
than one power source, markings shall be provided at each
service equipment location and at all interconnected electric
power production sources identifying all electric power
sources at the premises in accordance with NFPA 70.
Location: Electric panel closet
Comments: Remove obstructions (boxes) impeding 3E," clear access
space in front of electric panels.
Location: Electric panel closet
Comments: Install permanent signage "Electrical Room" on door for
firefighters. Laminated paper will not be accepted.
GENERATED ON 3/17/26, 12:34 PM
7 OF B