HomeMy WebLinkAbout2313 LOGAN AVEINVOICE DATE
DUE DATE
INVOICE #
TOTAL DUE
03/20/2026
04/24/2026
2026-00000392
$80.00
Customer #: 24067
GREENLEAF TOBACCO AND E-CIGS
1503 E SAN MARNAN DR SUITE C
WATERLOO, IA 50701
Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
715 Mulberry St
WATERLOO, IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION - 2313 LOGAN AVE - 03/18/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
24067
BILLING DATE
03/20/2026
DUE DATE
04/24/2026
INVOICE #
2026-00000392
CHARGES
$80.00
Less Prepayment
Total Due -*
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
1
Waterloo Fire Rescue
Inspection Report
Greenleaf Vape & Tobacco - 2313 Logan AVE, BLDG 2313 Logan Ave, Waterloo IA
50703
INSPECTION DETAILS
Inspection Date
03/18/2026
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
$bp 24ocs1
Other lnspectors
NIA
425 E. 3rd Street
Inspection Number
21242
Shift Station Unit
NIA N/A N/A
SUMMARY OF INSPECTION
032
Passed codes
NEXT STEPS
14
Failed codes
36
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 03/1812026 @ 14:59
• $80 annual inspection fee
BRAD BALDWIN - 03/19/2026 @ 08:42
Fire extinguishers due annually serviced in September 2026
BRAD BALDWIN - 03/19/2026 @ 09:05
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (45) - Cell: 319-230-1224
Reinspection Date
04/1712026
BRAD BALDWIN - 03119/2026 @ 09:05
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 03/19/2026 @ 09:05
• Request of specific time on scheduled inspection date or change of inspection date shall be made by business representative prior to scheduled
inspection date. Failure to request time or change of date will result in failed inspection.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
MO (2026) Date: BRAD BALDWIN 03/19/2026
CHECKLISTS
GENERATED ON 3/19/26, 9:08 AM
1 OF 9
Means of Egress
Status Code
Fail 1010.1.3 - Door opening force Forces to unlatch and open
doors.
The force for pushing or pulling open interior swinging
egress doors, other than fire doors, shall not exceed 5
pounds (22 N). These forces do not apply to the force
required to retract latch bolts or disengage other devices that
hold the door in a closed position. For other swinging doors,
as well as sliding and folding doors, the door latch shall
release when subjected to a 15-pound (67 N) force. The door
shall be set in motion when subjected to a 30-pound (133 N)
force. The door shall swing to a full -open position when
subjected to a 15-pound (67 N) force. The forces to unlatch
doors shall comply with the following: 1.Where door
hardware operates by push or pull, the operational force to
unlatch the door shall not exceed 15 pounds (66.7 N). 2.Where
door hardware operates by rotation, the operational force to
unlatch the door shall not exceed 28 inch -pounds (315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated, other than doors required to be fire rated, the force
for pushing or pulling open the door shall not exceed 5
pounds (22 N). 2.For other swinging doors, sliding doors or
folding doors, and doors required to be fire rated, the door
shall require not more than a 30-pound (133 N) force to be set
in motion and shall move to a full -open position when
subjected to not more than a 15-pound (67 N) force.
Description
Location: Front exit door
Comments: Repair door to open without special force, door shall
open with less than 151bs of force.
GENERATED ON 3/19/26, 9:08 AM
2 OF 9
Additional Codes
Status t'orie
Fail
Fail
Fail
Fail
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
Description
Location: Cigar room
Comments: Building and electrical permits and inspections shall be
obtained for cigar room built without permits.
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
308.1.5 - Location near combustibles.
Open flames such as from candles, lanterns, kerosene
heaters and gas -fired heaters shall not be located on or near
decorative material or similar combustible materials.
603.1.1 - Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
Emergency Equipment
Status Code
Fail
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Location: Water heater
Comments: Licensed plumbing contractor shall obtain permit and
inspection of water heater installed without permit.
Location: Burning incense
Comments: Burning of incense or candles is prohibited. Incense was
noted burning during 3118126 inspection, stop all burn ng
immediately.
Location: Window LED lighting
Comments: Provide documentation of proper listing and use of
listing of lighting.
Description
Location: Front exit
Comments: Repair or replace exit sign and lights that failed to
illuminate during test.
GENERATED ON 3/19/26, 9:08 AM
3 OF 9
Electrical Safety
Sloths Code
Fail
Fail
Fail
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.5.3 - Installation.
Relocatable power tap cords shall not extend through walls,
ceilings, floors, under doors or floor coverings, or be subject
to environmental or physical damage.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Description
Location: Display cases near front wall
Comments: Provide further information to inspector of nature of
white cords extending from under display cases. If extension cords,
remove.
Location: Front window above fridge
Comments: Properly mount power strip to avoid hanging by wires,
Location: Front wall
Comments: Remove extension cord plugged to power strip. Power
strip shall be properly mounted to wall to avoid hanging by wires and
plugged directly to outlet.
GENERATED ON 3/19/26, 9:08 AM
40F 9
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Front window
Comments: Remove extension cord plugged to power strip
GENERATED ON 3/19/26, 9:08 AM
5 OF 9
Fail 603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Front wall behind display cases
Comments: Remove white extension cord taped to floor. Cords
running across walkway shall be protected by listed floor cord
protector.
GENERATED ON 3/19/26, 9:08 AM
6 OF 9
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Behind counter below register counter
Comments: Provide further information regarding use of white cord
extending from below cabinet plugged to power strip.
GENERATED ON 3/19/26, 9:08 AM
7 OF 9
Fail 603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Portable Fire Extingusihers
Co
Fail 906.5 - Conspicuous location.
Portable fire extinguishers shall be located in conspicuous
locations where they will have ready access and be
immediately available for use. These locations shall be along
normal paths of travel, unless the fire code official determines
that the hazard posed indicates the need for placement away
from normal paths of travel.
Location: Behind register, cigarette shelving
Comments: Remove white cord extending through above ceiling.
Description
Location: Below register counter
Comments: Fire extinguisher shall be relocated to a conspicuous
location. Currently covered by bags and hidden.
GENERATED ON 3/19/26, 9:08 AM
8 OF 9
rO
FEE
Statement of Fees
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $80.00
Invoice Number
NIA
Check Number Transaction Number
NIA NIA
GENERATED ON 3/19/26, 9:08 AM 9 OF 9