COMMERCIAL INSPECTION - 3015 KIMBALL AVE - 03/17/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
13976
03/20/2026
04/24/2026
2026-00000396
$80.00
Less Prepayment
Total Due —
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Hansen's Dairy - 3015 Kimball AVE, BLDG 3015 Kimball Ave, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
03/17/2026
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
N/A
425 E. 3rd Street
Inspection Number
1325
Shift Station Unit
NIA N/A NIA
SUMMARY OF INSPECTION
036
Passed codes
NEXT STEPS
Failed codes
30
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 03/18/2026 @ 08:47
• $80 annual inspection fee
BRAD BALDWIN - 03/18/2026 @ 09:04
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 0311812026 @ 09:05
Reinspection Date
04/16/2.026
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Jordan Hansen 2026 HR Date: BRAD BALDWIN 03/18/2026
CHECKLISTS
GENERATED ON 3/18/26, 9:06 AM 1 OF 8
Emergency Equipment
Status Code
Fail
Fail
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
General Housekeeping
statue Code
Fail
305.1 - Clearance from ignition sources.
Clearance between ignition sources, such as luminaires,
heaters, flame -producing devices and combustible materials,
shall be maintained in an approved manner.
Description
Location: Back exit
Comments: Repair or replace exit sign that failed to illuminate during
test
Location: Above pasta display shelf
Comments: Repair or replace exit sign that failed to illuminate during
test
Description
Location: Mechanical room near back exit
Comments: Remove all combustible material on and within 36" of
water heater. Maintain proper clearances at all times.
GENERATED ON 3/18/26, 9:06 AM 2 OF 8
Electrical Safety
Status Code
Fail
Fail
603.4.1 - Labeling.
Doors into electrical control panel rooms shall be marked
with a plainly visible and legible sign stating "ELECTRICAL
ROOM" or similar approved wording. The disconnecting
means for each service, feeder or branch circuit originating
on a switchboard or panelboard shall be legibly and durably
marked to indicate its purpose unless such purpose is clearly
evident. Where buildings or structures are supplied by more
than one power source, markings shall be provided at each
service equipment location and at all interconnected electric
power production sources identifying all electric power
sources at the premises in accordance with NFPA 70.
603.5 - Relocatable power taps and current taps.Multiplug
adapters.
Multiplug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
Description
Location: Mechanical room near back exit
Comments: Install permanent sign "Electrical Room" on door for fire
fighters, laminated paper will not be accepted.
Location: Near meat cooler and Coke fridge
Comments: Remove multi -plug adapter. May replace with properly
mounted power strip with manual reset for low wattage items only.
Appliances with a motor or heat or cooling producing shall plug
directly to wall outlet.
GENERATED ON 3/18/26, 9:06 AM
3 OF 8
Fail
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Mixer machine
Comments: Remove extension cords. Appliance shall plug directly to
wall outlet, relocate or licensed electrical contractor shall add outlets
by obtaining permit and inspection.
Location: Behind ice cream freezer at front of store
Comments: Remove orange extension cord.
GENERATED ON 3/16/26, 9:06 AM 4 OF 8
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Near chicken cooler
Comments: Remove extension cord.
GENERATED ON 3/18/26, 9:06 AM
5 OF 8
Fire Resistant Construction Maintenance
Status Code
Fail
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
rooflceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Description
Location: Mechanical room near back exit
Comments: Replace missing ceiling tiles.
GENERATED ON 3/18/26, 9:06 AM
6 OF 8
Portable Fire Extingusihers
strmc; writ
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Location: All extinguishers
Comments: Provide annual service to extinguishers, last recorded
service completed in September 2022.
GENERATED ON 3/18/26, 9:06 AM 7 OF 8