COMMERCIAL INSPECTION - 3045 KIMBALL AVE - 03/17/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
6018
03/20/2026
04/24/2026
2026-00000397
$80.00
Less Prepayment
Total Due —
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
ffi�o 6201'S
Waterloo Fire Rescue
Inspection Report
Sub City - 3045 Kimball AVE, BLDG 3045 Kimball Ave, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
03/17/2026
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
1327
Shift Station Unit
NIA NIA N/A
SUMMARY OF INSPECTION
0 32
Passed codes
NEXT STEPS
7 ®36
Failed codes NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 03/18/2026 @ 08:24
• $80 annual inspection fee
BRAD BALDWIN - 03/18/2026 @ 08:39
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
04/16/2026
BRAD BALDWIN - 03/18/2026 @ 08:39
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Andy Holbach (2026) Date: BRAD BALDWIN 03/18/2026
CHECKLISTS
GENERATED ON 3/18/26, 8:42 AM
1 OF 5
Means of Egress
Status Code
Fail 1010.1.3 - Door opening force Forces to unlatch and open
doors.
The force for pushing or pulling open interior swinging
egress doors, other than fire doors, shall not exceed 5
pounds (22 N). These forces do not apply to the force
required to retract latch bolts or disengage other devices that
hold the door in a closed position. For other swinging doors,
as well as sliding and folding doors, the door latch shall
release when subjected to a 15-pound (67 N) force. The door
shall be set in motion when subjected to a 30-pound (133 N)
force. The door shall swing to a full -open position when
subjected to a 15-pound (67 N) force. The forces to unlatch
doors shall comply with the following: 1.Where door
hardware operates by push or pull, the operational force to
unlatch the door shall not exceed 15 pounds (66.7 N). 2.Where
door hardware operates by rotation, the operational force to
unlatch the door shall not exceed 28 inch -pounds (315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated, other than doors required to be fire rated, the force
for pushing or pulling open the door shall not exceed 5
pounds (22 N). 2.For other swinging doors, sliding doors or
folding doors, and doors required to be fire rated, the door
shall require not more than a 30-pound (133 N) force to be set
in motion and shall move to a full -open position when
subjected to not more than a 15-pound (67 N) force.
Emergency Equipment
Status Code
Fail
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
General Housekeeping
Status Code
Fail 305.1 - Clearance from ignition sources.
Clearance between ignition sources, such as luminaires,
heaters, flame -producing devices and combustible materials,
shall be maintained in an approved manner.
Description
Location: Back exit door
Comments: Repair or replace door that failed to easily open today.
Replacing door would require obtaining permit with City Building
Inspections Dept.
Description
Location: Bathroom hallway
Comments: Repair or replace egress light that failed to illuminate
during test
Location: Back exit
Comments: Repair or replace exit sign that failed to illuminate during
test
Description
Location: Water heater
Comments: Remove combustible material within 36" of appliance.
Maintain proper clearance at all times.
GENERATED ON 3/18/26, 8:42 AM
2 OF 5
Additional Codes
Status Coder
Fail
5303.5.3 - Securing compressed gas containers, cylinders
and tanks.
Compressed gas containers, cylinders and tanks shall be
secured to prevent falling caused by contact, vibration or
seismic activity. Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers, cylinders and tanks to a fixed object
with one or more restraints. 2.Securing containers, cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers, cylinders or tanks.
3. Nesting of compressed gas containers, cylinders and tanks
at container filling or servicing facilities or in sellers'
warehouses not open to the public. Nesting shall be allowed
provided that the nested containers, cylinders or tanks, if
dislodged, do not obstruct the required means of egress.
4.Securing of compressed gas containers, cylinders and
tanks to or within a rack, framework, cabinet or similar
assembly designed for such use. Exception: Compressed gas
containers, cylinders and tanks in the process of
examination, filling, transport or servicing.
Description
Location: All tanks
Comments: Tanks by fridge and below microwave beiind counter
shall be chained to avoid tip -over hazard
GENERATED ON 3/18/26, 8:42 AM
3 OF 5
Fail 603.1.1 - Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
Portable Fire Extingusihers
Status Code
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Location: Behind counter
Comments: All appliances that produce heat or include motors shall
be plugged directly to wall outlet. Relocate cooking equipment to
plug to outlet or add outlet by licensed electrical contractor by
obtaining permit and inspection.
Description
Location: All extinguishers
Comments: Provide annual service to extinguishers, last recorded
service in July 2024.