DCOMMERCIAL INSPECTION - 620 COMMERCIAL ST - 03/19/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE
CHARGES
24939
03/27/2026
05/01/2026
2026-00000406
$80.00
Less Prepayment
Total Due —
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
k 8d 2ya3q
Waterloo Fire Rescue
Inspection Report
Lustre Event Venue - 620 Commerical ST, BLDG 620 Commerical St, Waterloo IA
50701
INSPECTION DETAILS
Inspection Date
03/19/2026
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
N/A
425 E. 3rd Street
Inspection Number
1015
Shift Station Unit
NIA NIA N/A
SUMMARY OF INSPECTION
0 43 0 7
Passed codes
NEXT STEPS
Failed codes
25
N/A codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 03/20/2026 @ 14:43
• $80 annual inspection fee
BRAD BALDWIN - 03/2012026 @ 14:43
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
04/1012026
BRAD BALDWIN - 03/2012026 @ 14:43
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 03120/2026 @ 14:43
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Heidi Fordyce (2026)
CHECKLISTS
Date: BRAD BALDWIN 03/20/2026
GENERATED ON 3/20/26, 2:46 PM
1 OF 5
Means of Egress
Status Code
Fail
1004.9 - Posting of occupant load.
Every room or space that is an assembly occupancy shall
have the occupant load of the room or space posted in a
conspicuous place, near the main exit or exit access doorway
from the room or space, for the intended configurations.
Posted signs shall be of an approved legible permanent
design and shall be maintained by the owner or the owner's
authorized agent.
Fire Alarm System
Status Code
Fail
Chapter 14 - Inspection, testing, and maintenance
Fire alarm system tested at least annually by licensed
contractor
General Housekeeping
Status Code
Fail
315.3.1- Ceiling clearance.
Storage shall be maintained 2 feet (610 mm) or more below
the ceiling in nonsprinklered areas of buildings or not less
than 18 inches (457 mm) below sprinkler head deflectors in
sprinklered areas of buildings. Exceptions: 1.The 2-foot (610
mm) ceiling clearance is not required for storage along walls
in nonsprinklered areas of buildings. 2,The 18-inch (457 mm)
ceiling clearance is not required for storage along walls in
areas of buildings equipped with an automatic sprinkler
system in accordance with Section 903.3.1.1, 903.3.1.2 or
903.3.1.3.
Fire Sprinkler System
Status Code
Fail
5.2.1- Annual sprinkler system inspection
Sprinklers shall be inspected at least annually by licensed
contractor
Description
Location: Front exit
Comments: Occupant Toad sign shall be permanently posted near
main exit.
Description
Comments: Provide annual fire alarm inspection report including any
deficiencies corrected to be uploaded to Compliance Engine.
Inspection due 4t1t26.
Description
Location: 3rd floor storage areas behind curtains
Comments: Lower all storage within 18inches below sprinkler heads
Description
Comments: Provide annual sprinkler system inspection report
including any deficiencies corrected to be uploaded to Compliance
Engine. Inspection due April 2026.
GENERATED ON 3/20/26, 2:46 PH
2 OF 5
Electrical Safety
Status Code
Fail
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum dear opening of 22 inches (559 mm) by 30
inches (762 min).
Description
Location: 3rd floor electric panel room
Comments: Clearance of 36 inches in front of panel including down
to floor and 30 inches in width to panel shall be maintained. Remove
all storage within clearances.
GENERATED ON 3/20/26, 2:46 PM
3 OF 5
Portable Fire Extingusihers
Status Cain
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Location: All fire extinguishers
Comments: Provide annual service to extinguishers, currently due in
April 2026
Additional Codes
Status Cods Description
Fail 912.7 - Inspection, testing and maintenance.
OFire department connections shall be periodically inspected, Location: Front of building
tested and maintained in accordance with NFPA 25. Records Comments: Provide missing cap to Fire Department Connection.
of inspection, testing and maintenance shall be maintained.
GENERATED ON 3/20/26, 2:46 PM