COMMERCIAL INSPECTION - 2034 LA PORTE RD - 03/20/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 50,000
OCCUPANCY FEE
$225.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
12855
03/27/2026
05/01/2026
2026-00000404
$235.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$235.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
235
I Z8 65
Waterloo Fire Rescue
Inspection Report
Hampton Inn & Suites - 2034 La Porte RD, BLDG 2034 La Porte Rd, Waterloo IA
50702
INSPECTION DETAILS
Inspection Date
03/20/2026
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NATE BEUSELING
425 E. 3rd Street
Inspection Number
21295
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
049
Passed codes
NEXT STEPS
0 48
Failed codes
20
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 03123/2026 @ 12:38
$235 annual inspection fee
BRAD BALDWIN - 03/23/2026 @ 12:56
Private hydrants due inspected by 7/3126. Reports including deficiencies corrected shall be uploaded to Compliance Engine.
BRAD BALDWIN - 03/2312026 @ 12:57
Sprinkler system inspection due 7/3/26. Reports including deficiencies corrected shall be uploaded to Compliance Engine.
BRAD BALDWIN - 03/23/2026 @ 12:57
Sprinkler standpipe inspection due 7/3126. Reports including deficiencies corrected shall be uploaded to Compliance Engine.
BRAD BALDWIN - 03/2312026 @ 13:07
Fire extinguishers due annually serviced in January 2027
BRAD BALDWIN - 03/2412026 @ 15:13
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
04/1712026
BRAD BALDWIN - 03/24/2026 @ 15:13
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 03/2412026 @ 15:13
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then S150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 03/24/2026 @ 15:13
• Request of specific time on scheduled inspection date or change of inspection date shall be made by business representative prior to t cheduled
inspection date. Failure to request time or change of date will result in failed inspection.
GENERATED ON 3/26/26, 7:31 AM 1 OF 18
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Cayenne Adams - Manager (2025) Date:
CHECKLISTS
BRAD BALDWIN 0312612026
GENERATED ON 3/26/26, 7:31 AM
2 OF 18
Additional Codes
Status Code
Fail
Fail
Fail
Fail
Fail
Fail
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
2015 IPMC 704.1.1 - Automatic sprinkler systems
Inspection, testing and maintenance of automatic sprinkler
systems shall be in accordance with NFPA 25.
Description
Location: Room #130
Comments: Obtain building permit and inspection of replacement of
door. Door has arrived and on -site.
Location: 1st floor laundry furnace room
Comments: Obtain building permit and inspection of replacement of
door. Door has arrived and on -site.
Location: 4th floor housekeeping laundry closet
Comments: Obtain building permit and inspection of replacement of
door. Door has arrived and on -site.
Location: Replacement of Gas Furnace #6
Comments: Electric permit and inspection shall be obtained for
replacement. Mechanical permit obtained, but no inspection on
record as of 3/23/26.
Location: Remodel
Comments: Obtain final building inspection for remodel project,
permit obtained April 18 2024. Contact Brian Wirtz (3:19-291-4319) to
schedule inspection.
Location: Pool equipment room
Comments: Licensed sprinkler contractor shall inspect corroded
head and establish whether it should be replaced or is compliant.
Documentation from contractor shall be obtained and provided to
inspector
GENERATED ON 3/26/26, 7:31 AM
3 OF 18
Fail
Fail
Fail
Fail
2015 IPMC 704.1.1- Automatic sprinkler systems
Inspection, testing and maintenance of automatic sprinkler
systems shall be in accordance with NFPA 25.
603.1.1 - Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
603.1.1 - Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
603.1.1- Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
Location: Room 218 bathroom
Comments: Licensed sprinkler contractor shall inspect head and
piping for proper installation, make any necessary repairs. Obtain
contractor documentation of inspection to provide to inspector.
Location: Occupant rooms microwaves and fridges
Comments: Remove all microwaves and fridges plugged to power
strips and multi -plug adapters. Majority of rooms noted with
violation. Appliances that produce heat or contain motors shall plug
directly to permanent wall outlet. Will need to verify all appliances are
powered properly.
Location: New occupant room TV & bed furniture
Comments: Provide documentation of listing of furniture including
built-in receptacles
Location: 1st floor employee break room
Comments: Remove microwave from extension cord. Appliance shall
plug directly to permanent wall outlet.
GENERATED ON 3/26/26, 7:31 AM 4 OF 18
Fail
Fail
lJ
Fail
0
603.5.1- ListingPower tap design.
Relocatable power taps shall be of the polarized or grounded
type, equipped with overcurrent protection, and shall be
listed in accordance with UL 1363. Current taps shall be listed
and labeled in accordance with UL 498A .
610.1.2 - Maintenance.
The lint trap, tnechanical and heating components, and the
exhaust duct system of a clothes dryer shall be maintained in
accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that
prevents the exhaust of air and products of combustion.
907.10 - Smoke alarm maintenance.
Smoke alarms shall be tested and maintained in accordance
with the manufacturer's instructions. Smoke alarms shall be
replaced when they fail to respond to operability tests, or
when they exceed 10 years from the date of manufacture,
unless an earlier replacement is specified in the
manufacturer's published instructions.
Emergency Equipment
Status Code
Fail
Fail
O
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Location: Multi -plug adapters
Comments: Provide documentation of listing conforms to UL 498A.
Location: Guest and House laundry dryer vents
Comments: Provide documentation of cleaning of dryer vents from
appliances to the exterior of the building with signature and date.
Email documentation to fire inspector.
Location: All occupant rooms
Comments: Provide document of testing all room smoke detection
devices and are working properly. Document shall include date,
location and person completing testing.
Description
Location: Emergency egress lights
Comments: Provide documentation of testing all emergency egress
lighting in building including repairs made to maintain working
properly, documentation shall include signature and date of
responsible person.
Location: Exit signs
Comments: Provide documentation of testing all exit signs including
repairs made to maintain working properly, documem:ation shall
include signature and date of responsible person.
GENERATED ON 3/26/26, 7:31 AM 5 OF 18
General Housekeeping
Stag. code
Fail
Fail
Fail
315.3.1 - Ceiling clearance.
Storage shall be maintained 2 feet (610 mm) or more below
the ceiling in nonsprinklered areas of buildings or not less
than 18 inches (457 mm) below sprinkler head deflectors in
sprinklered areas of buildings. Exceptions: 1.The 2-foot (610
mm) ceiling clearance is not required for storage along walls
in nonsprinklered areas of buildings. 2.The 18-inch (457 mm)
ceiling clearance is not required for storage along walls in
areas of buildings equipped with an automatic sprinkler
system in accordance with Section 903.3.1.1, 903.3.1.2 or
903.3.1.3.
315.3.1 - Ceiling clearance.
Storage shall be maintained 2 feet (610 mm) or more below
the ceiling in nonsprinklered areas of buildings or not less
than 18 inches (457 mm) below sprinkler head deflectors in
sprinklered areas of buildings. Exceptions: 1.The 2-foot (610
mm) ceiling clearance is not required for storage along walls
in nonsprinklered areas of buildings. 2.The 18-inch (457 mm)
ceiling clearance is not required for storage along walls in
areas of buildings equipped with an automatic sprinkler
system in accordance with Section 903,3.1.1, 903.3.1.2 or
903.3.1.3.
315.3.1- Ceiling clearance.
Storage shall be maintained 2 feet (610 mm) or more below
the ceiling in nonsprinklered areas of buildings or not less
than 18 inches (457 mm) below sprinkler head deflectors in
sprinklered areas of buildings. Exceptions: 1.The 2-foot (610
mm) ceiling clearance is not required for storage along walls
in nonsprinklered areas of buildings. 2.The 18-inch (457 mm)
ceiling clearance is not required for storage along walls in
areas of buildings equipped with an automatic sprinkler
system in accordance with Section 903.3.1.1, 903.3.1.2 or
903.3.1.3.
Description
Location: 4th floor (east end) electrical room
Comments: Lower storage in housekeeping area within 18" below
sprinkler heads.
Location: 2nd floor (eat end) electric room
Comments: Lower storage within 18" below sprinkler heads.
Location: Cayenne's office closet
Comments: Lower storage within 18" below sprinkler head.
GENERATED ON 3/26/26, 7:31 AM 6 OF 18
Fire Sprinkler System
Code
Fail
Fail
Fail
5.2.1.1.5 - Missing escutcheons
Escutcheons and coverplates for recessed, flush, and
concealed sprinklers shall be replaced if found missing
during the inspection.
5.2.1.1.5 - Missing escutcheons
Escutcheons and coverplates for recessed, flush, and
concealed sprinklers shall be replaced if found missing
during the inspection.
5.2.1.1.5 - Missing escutcheons
Escutcheons and coverplates for recessed, flush, and
concealed sprinklers shall be replaced if found missing
during the inspection.
Description
Location: All fire sprinkler escutcheons
Comments: After interior remodel, several escutcheons noted loose
to wall and ceiling surfaces. All escutcheons shall be repaired to be
installed flush to ceiling or wall surface. Provide document to
inspector that all escutcheons are compliant to installation
standards.
Location: Room 202
Comments: Provide missing escutcheon in bathroom
Location: 1st floor (east end) electric room
Comments: Replace missing escutcheon
GENERATED ON 3/26/26, 7:31 AM
7 OF 18
Fail
903.3.3 - Obstructed locations.
Automatic sprinklers shall be installed with regard to
obstructions that will delay activation or obstruct the water
distribution pattern and shall be in accordance with the
applicable automatic sprinkler system standard that is being
used. Automatic sprinklers shall be installed in or under
covered kiosks, displays, booths, concession stands or
equipment that exceeds 4 feet (1219 mm) in width. Not less
than a 3-foot (914 mm) clearance shall be maintained between
automatic sprinklers and the top of piles of combustible
fibers. Exception: Kitchen equipment under exhaust hoods
protected with a fire -extinguishing system in accordance with
Section 904.
Location: 4th floor stairwell landing near attic access ladder
Comments: Remove paint on sprinkler head and escutcheon
GENERATED ON 3/26/26, 7:31 AM 8 OF 18
Fire Service Features
Status Code
Fail
Fail
505.1- Address identification.
New and existing buildings shall be provided with approved
address identification. The address identification shall be
legible and placed in a position that is visible from the street
or road fronting the property. Address identification
characters shall contrast with their background. Address
numbers shall be Arabic numbers or alphabetical letters.
Numbers shall not be spelled out. Each character shall be not
less than 4 inches (102 mm) high with a minimum stroke
width of 1/2 inch (12.7 mm). Where required by the fire code
official, address identification shall be provided in additional
approved locations to facilitate emergency response. Where
access is by means of a private road and the building cannot
be viewed from the public way, a monument, pole or other
sign or means shall be used to identify the structure. Address
identification shall be maintained.
509.2 - Equipment access.
Approved access shall be provided and maintained for all fire
protection system equipment to permit immediate safe
operation and maintenance of such equipment. Storage, trash
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
Description
Location: Address numbers
Comments: Install address identification numbers in contrast to the
building visible from the La Porte Rd. See code specifications for
identification numbers requirements
Location: 1st floor laundry room
Comments: Remove all storage (laundry carts) from within 36" of
sprinkler riser piping. Maintain clear path of access at all times.
GENERATED ON 3/26/26, 7:31 AM
9 OF 18
Electrical Safety
ate Cade
Fail
Fail
Fail
603,2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.5.2 - Application and usePower supply.
Relocatable power taps and current taps shall be directly
connected to a permanently installed receptacle. Exceptions:
1. Where approved for use in a Group A occupancy or in a
meeting room in a Group B occupancy, not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
Description
Location: Pool equipment room
Comments: Install cover properly on box on ceiling exposing wires.
Location: IT Room
Comments: Install missing outlet cover.
Location: All power strips
Comments: All power strips shall be plugged directly to a permanent
wall outlet and mounted properly to avoid hanging by wires. Noted
several power strips in violation, including but not limited to, behind
TV furniture in occupant rooms. Provide document to inspector
verifying all power strips have been repaired to comply with
installation requirements.
GENERATED ON 3/26/26, 7:31 AM
10 OF 18
Fail
603.5.2 - Application and usePower supply.
Relocatable power taps and current taps shall be directly
connected to a permanently installed receptacle. Exceptions:
1. Where approved for use in a Group A occupancy or in a
meeting room in a Group B occupancy, not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
Location: 1st floor IT Room
Comments: Remove power strips daisy chained, each power strip
shall plug directly to permanent wall outlet.
GENERATED ON 3/26/26, 7:31 AM 11 OF 18
Fire Resistant Construction Maintenance
Stard,Cod
Fail
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Description
Location: 3rd floor ceiling above elevator
Comments: Obtain permit and inspection for ceiling repair.
GENERATED ON 3/26/26, 7:31 AM
12 OF 18
Fail
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Rooms 419 & 421
Comments: Adjoining rooms door frame missing smoke seal shall be
corrected.
Location: Rooms 418 & 420
Comments: Adjoining rooms door frame missing smoke seal shall be
corrected.
GENERATED ON 3/26/26, 7:31 AM 13 OF 18
Fail
Fail
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Room 131
Comments: Replace partially missing door frame smoke seal
Location: Pool equipment room
Comments: Install missing door frame smoke seals.
GENERATED ON 3/26/26, 7:31 AM
14 OF 18
Fail
Fail
Fail
Fail
705.2 - Inspection and maintenance,
Opening protectives in fire -resistance -rated assemblies shall
be inspected and maintained in accordance with NFPA 80,
Opening protectives in smoke barriers shall be inspected and
maintained in accordance with NFPA 80 and NFPA 105.
Openings in smoke partitions shall be inspected and
maintained in accordance with NFPA 105. Fire doors and
smoke and draft control doors shall not be blocked,
obstructed, or otherwise made inoperable. Fusible links shall
be replaced promptly whenever fused or damaged. Opening
protectives and smoke and draft control doors shall not be
modified.
705.2 - Inspection and maintenance.
Opening protectives in fire -resistance -rated assemblies shall
be inspected and maintained in accordance with NFPA 80.
Opening protectives in smoke barriers shall be inspected and
maintained in accordance with NFPA 80 and NFPA 105.
Openings in smoke partitions shall be inspected and
maintained in accordance with NFPA 105. Fire doors and
smoke and draft control doors shall not be blocked,
obstructed, or otherwise made inoperable. Fusible links shall
be replaced promptly whenever fused or damaged. Opening
protectives and smoke and draft control doors shall not be
modified.
705.2 - Inspection and maintenance.
Opening protectives in fire -resistance -rated assemblies shall
be inspected and maintained in accordance with NFPA 80.
Opening protectives in smoke barriers shall be inspected and
maintained in accordance with NFPA 80 and NFPA 105.
Openings in srnoke partitions shall be inspected and
maintained in accordance with NFPA 105. Fire doors and
smoke and draft control doors shall not be blocked,
obstructed, or otherwise made inoperable. Fusible links shall
be replaced promptly whenever fused or damaged. Opening
protectives and smoke and draft control doors shall not be
modified.
705.2 - Inspection and maintenance.
Opening protectives in fire -resistance -rated assemblies shall
be inspected and maintained in accordance with NFPA 80.
Opening protectives in smoke barriers shall be inspected and
maintained in accordance with NFPA 80 and NFPA 105.
Openings in smoke partitions shall be inspected and
maintained in accordance with NFPA 105. Fire doors and
smoke and draft control doors shall not be blocked,
obstructed, or otherwise made inoperable. Fusible links shall
be replaced promptly whenever fused or damaged. Opening
protectives and smoke and draft control doors shall not be
modified.
Location: Pool equipment room ceiling
Comments: Void surrounding sprinkler escutcheon shall be fire
caulked.
Location: 2nd floor (west end) laundry room
Comments: Door frame to common hallway missing lire rating label.
Frame shall be re -certified and labeled or replaced by obtaining
proper permit and inspection.
Location: Room 205
Comments: Door frame to common hallway missing fire rating label.
Frame shall be re -certified and labeled or replaced by obtaining
proper permit and inspection.
Location: Room 202
Comments: Door frame to common hallway missing fire rating label.
Frame shall be re -certified and labeled or replaced by obtaining
proper permit and inspection.
GENERATED ON 3/26/26, 7:31 AM
15 OF 18
Fail 705.2 - Inspection and maintenance.
Opening protectives in fire -resistance -rated assemblies shall
be inspected and maintained in accordance with NFPA 80.
Opening protectives in smoke barriers shall be inspected and
maintained in accordance with NFPA 80 and NFPA 105.
Openings in smoke partitions shall be inspected and
maintained in accordance with NFPA 105. Fire doors and
smoke and draft control doors shall not be blocked,
obstructed, or otherwise made inoperable. Fusible links shall
be replaced promptly whenever fused or damaged. Opening
protectives and smoke and draft control doors shall not be
modified.
Fail
Fail
Fail
Fail
Fail
Fail
705.2.4 - Door operation.
Swinging fire doors shall dose from the full -open position
and latch automatically.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
705.2.4 • Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Fail 705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Fail 705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Location: 1st floor (east end) electric room
Comments: Door frame to common hallway missing fire rating label.
Frame shall be re -certified and labeled or replaced by obtaining
proper permit and inspection.
Location: Room 128
Comments: Repair or replace door to common hallway that failed to
self shut and latch.
Location: 1st floor men's bathroom door
Comments: Continuing violation: Repair or replace door that failed to
self shut and latch.
Location: Room 228
Comments: Repair or replace door to common hallway that failed to
self shut and latch.
Location: Room 422
Comments: Repair or replace door to common hallway that failed to
self shut and latch.
Location: 4th floor elevator drop doors
Comments: Repair or replace doors that failed to self shut and latch.
Location: Room 408
Comments: Repair or replace door to common hallway that failed to
self shut and latch.
Location: 1st floor Boardroom
Comments: Repair or replace door to common hallway that failed to
self shut and latch.
Location: 1st floor Housekeeping (interior vending door)
Comments: Repair or replace door to common hallway that failed to
self shut and latch.
Location: 4th floor (east end) electric room
Comments: Interior door failed to self shut and latch, repair or
replace.
GENERATED ON 3/26/26, 7:31 AM 16 OF 18
Fail
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Location: 2nd floor (east end) electric room
Comments: Repair or replace door to common hallway that failed to
self shut and latch.
GENERATED ON 3/26/26, 7:31 AM
17 OF 18
Po
FEE
Statement of Fees
Invoice Date Inspection Fee
NIA $235.00
Date Paid Amount Paid