COMMERCIAL INSPECTION - 3115 KIMBALL AVE - 03/16/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER # BILLING DATE
DUE DATE
INVOICE #
CHARGES
3919
03/27/2026
05/01/2026
City of Waterloo
2026-00000399
Less Prepayment
Total Due -›
$80.00
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
1
3c1tc
Waterloo Fire Rescue
Inspection Report
Kentucky Fried Chicken - 3115 Kimball AVE, BLDG 3115 Kimball Ave, Waterloo IA
50702
INSPECTION DETAILS
Inspection Date
03/16/2026
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
Shift Station
NIA NIA
425 E. 3rd Street
Inspection Number
21221
Unit
N/A
SUMMARY OF INSPECTION
0 41
Passed codes
NEXT STEPS
Q 11
Failed codes
25
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 03/17/2026 @ 11:26
• $80 annual inspection fee
BRAD BALDWIN - 03/17/2026 @ 11:28
Fire extinguishers due annually serviced in November 2026
BRAD BALDWIN - 03/17/2026 @ 11:45
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 03/1712026 @ 11:45
Reinspection Date
04/16/2026
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. """Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Patrick Sumerall (2026) Date:
CHECKLISTS
BRAD BALDWIN 03/17/2026
GENERATED ON 3/17/26, 11T 47 AM 1 OF 7
Emergency Equipment
Status Code
Fail
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
General Housekeeping
statics Code
Fail
304.3.1- Spontaneous ignition.
Materials susceptible to spontaneous ignition, such as oily
rags, shall be stored in a listed disposal container. Contents
of such containers shall be removed and disposed of daily.
Additional Codes
Status Code
Fail
Fail
603.1.1- Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
606.3.1 - Ventilation system.
The ventilation system in connection with hoods shall be
operated at the required rate of air movement, and grease
filters listed and labeled in accordance with UL 1046 shall be
in place where equipment under a kitchen grease hood is
used.
Description
Location: Kitchen near walk-in fridge
Comments: Repair or replace exit sign and lights combo that failed to
illuminate during test.
Description
Location: Kitchen
Comments: Provide listed container for disposal of oily rags
Description
Location: Fountain machine at drive-thru window
Comments: Remove white multi -plug cord plugged to fountain
machine. Appliance shall plug directly to wall outlet. If adding new
outlet, licensed electrical contractor shall obtain permit and
inspection.
Location: Kitchen hood exhaust
Comments: Replace or repair broken hood filters.
GENERATED ON 3/17/26, 11:47 AM
2 OF 7
Electrical Safety
Status Cede Des
Fail 603.2.2 - Unapproved conditionsOpen electrical terminations.
OOpen junction boxes and open -wiring splices shall be Location: Walk-in fridge
prohibited. Approved covers shall be provided for all switch Comments: Provide missing moisture proof cover to light fixture
and electrical outlet boxes.
Fail
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Location: Near back kitchen door
Comments: Remove obstructions (boxes) impeding 36" clear access.
space in front of electric panels.
GENERATED ON 3/17/26, 11:47 AM
3 OF 7
Fail
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Location: Office
Comments: Remove obstructions impeding 36" clear access space in
front of electric panels. Maintain clearance from storage at all times.
GENERATED ON 3/17/26, 11:47 AM
4 OF 7
Fail
Fail
603.5 - Relocatable power taps and current taps.Multiplug
adapters.
Multiplug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Office
Comments: Remove multi -plug cord. May replace with properly
mounted power strip with manual reset for light duty electric only.
Location: Kitchen (above fountain drink rack & condiment rack)
Comments: Remove orange extension cord from above drop ceiling.
GENERATED ON 3/17/26, 11.:47 AM
5 OF 7
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Commercial Cooking Hood Suppression System
Status Code
Fail
606.3.3.2 - Grease accumulation.
If during the inspection it is found that hoods, grease -removal
devices, fans, ducts or other appurtenances have an
accumulation of grease, such components shall be cleaned in
accordance with ANSIIIKECA C10.
Location: Kitchen near condiment station
Comments: Remove white flexible cord from above drop ceiling.
Dcscru tion
Location: Cooking equipment under hood
Comments: Clean and remove all excess grease behind and on fryer
cabinet.