COMMERCIAL INSPECTION - 1039 PEOPLES SQ - 04/01/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
24941
04/07/2026
05/12/2026
2026-00000420
$80.00
Less Prepayment
Total Due —
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
2�19�11 $ 80
Waterloo Fire Rescue
Inspection Report
Tropical Smoothie Cafe -1039 peoples SQ, BLDG 1035 - 1039 Peoples Sq - STE
1039, Waterloo IA 50701 larai
INSPECTION DETAILS
Inspection Date
04/01/2026
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
21491
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
031 03 039
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 04/02/2026 @ 08:05
$80 annual inspection fee
BRAD BALDWIN - 04/02/2026 @ 08:10
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 04/02/2026 @ 08:10
Reinspection Date
0510112026
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
Troy Greenwood
CHECKLISTS
No signature
Report completed post inspection
Date: BRAD BALDWIN 04/02/2026
GENERATED ON 4/2/26, 8:16 AM 1 OF 4
Electrical Safety
Status Code
Fail
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Description
Location: Electric panels near back exit
Comments: Remove all storage blocking access to electric panels,
maintain 36 inches of clearance in front of panels at all times.
Location: Kitchen - Air purifyer
Comments: Remove extension cord plugged to appliance.
GENERATED ON 4/2/26, 8:16 AM 2 OF 4
Portable Fire Extingusihers
Status Code
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Location: All extinguishers
Comments: Provide annual service to extinguishers, last recorded
service completed June 2023