HomeMy WebLinkAbout1315 E SAN MARNAN DRCustomer #: 4712
OLIVE GARDEN
1315 E SAN MARNAN DR
WATERLOO, IA 50702
INVOICE DATE
DUE DATE
INVOICE #
TOTAL DUE
04/07/2026
05/12/2026
2026-00000426
$80.00
Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
715 Mulberry St
WATERLOO, IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION - 1315 E SAN MARNAN DR -
03/30/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
4712
BILLING DATE
04/07/2026
DUE DATE
05/12/2026
INVOICE #
2026-00000426
CHARGES
$80.00
City of Waterloo
Less Prepayment
Total Due —>
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Olive Garden - 1315 E San Marnan DR, BLDG 1315 E San Marnan Dr, Waterloo IA
50702
INSPECTION DETAILS
Inspection Dale
03/3012026
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
16722
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
0 51
Passed codes
NEXT STEPS
0 8
Failed codes
16
N/A codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 03/31/2026 @ 08:14
$80 annual inspection fee
Reinspection Date
04/21/2026
BRAD BALDWIN - 03/31/2026 @ 08:18
Kitchen hood suppression system due for inspection on 5/19/26. Suppression system pull station currently missing tag noting last completed inspection.
BRAD BALDWIN - 03131/2026 @ 08:30
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 03/31/2026 @ 08:30
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 03/31/2026 @ 08:30
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Christina Brainard 2026
CHECKLISTS
Date: BRAD BALDWIN 03/31/2026
GENERATED ON 3/31/26, 8:32 AM 1 OF 6
Additional Codes
Slaws Code
Fail
Fail
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
903.5 - Testing and maintenance.
Sprinkler systems shall be tested and maintained in
accordance with Section 901.
Fire Alarm System
Status Code
Fail
2015 IFC - Fire alarm testing and maintenance
Is the fire alarm system powered, operational and displaying
normal operation (no troubles, supervisory, or alarms)?
General Housekeeping
status Cols
Fail
304.3.1- Spontaneous ignition.
Materials susceptible to spontaneous ignition, such as oily
rags, shall be stored in a listed disposal container. Contents
of such containers shall be removed and disposed of daily.
Description
Location: Water heater
Comments: Licensed plumbing contractor shall obtain permit and
inspection for water heater installed 6/29125 without permit
Location: 5 year sprinkler inspection
Comments: Inspection due 5119/26. Annual inspection due 4115/26.
Inspections and reports including deficiencies corrected shall be
uploaded to Compliance Engine.
Description
Location: Fire alarm
Comments: See attached report: deficiency noted by Johnson
Controls Security shall be repaired and report uploaded to
Compliance Engine
Description
Location: Kitchen
Comments: Provide listed container to dispose of c oly rags with self -
closing lid. See attachment
GENERATED ON 3/31/26, 8:32 AM 2 OF 6
I
Fire Sprinkler System
Status Code
Fail
®
5.2.1.1.5 - Missing escutcheons
Escutcheons and coverplates for recessed, flush, and
concealed sprinklers shall be replaced if found missing
during the inspection.
Description
Location: Kitchen near coffee makers
Comments: Escutcheon loose to ceiling shall be corrected.
GENERATED ON 3/31/26, 8:32 AM
30F 6
V
Fail
903.3.3 - Obstructed locations.
Automatic sprinklers shall be installed with regard to
obstructions that will delay activation or obstruct the water
distribution pattern and shall be in accordance with the
applicable automatic sprinkler system standard that is being
used. Automatic sprinklers shall be installed in or under
covered kiosks, displays, booths, concession stands or
equipment that exceeds 4 feet (1219 mm) in width. Not Tess
than a 3-foot (914 mm) clearance shall be maintained between
automatic sprinklers and the top of piles of combustible
fibers. Exception: Kitchen equipment under exhaust hoods
protected with a fire -extinguishing system in accordance with
Section 904.
Location: Kitchen "To Go" area
Comments: Remove dust & debris from sprinkler head.
GENERATED ON 3/31/26, 8:32 AM
4 OF 6
Electrical Safety
Status Core
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Commercial Cooking Hood Suppression System
States Coda
Fail
606.3.3.2 - Grease accumulation.
If during the inspection it is found that hoods, grease -removal
devices, fans, ducts or other appurtenances have an
accumulation of grease, such components shall be cleaned in
accordance with ANSI/IKECA C10.
Description
Location: Bar
Comments: Provide missing outlets cover
Description
Location: Kitchen
Comments: Excess grease noted in fryer cabinets and on hood
suppression system piping above 6 burner range shall be cleaned.
GENERATED ON 3/31/26, 8:32 AM
5 OF 6
Statement of Fees
FEE
Invoice Date Inspection Fee
NIA $80,00
Invoice Number
NIA
Date Paid Amount Paid
Check Number Transaction Number
NIA NIA
GENERATED ON 3/31/26, 8:32 AM
6 OF 6
I