COMMERCIAL INSPECTION - 205 W 4TH ST - 03/24/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 100,000
$600.00
CUSTOMER #
24080
BILLING DATE
04/07/2026
DUE DATE
05/12/2026
INVOICE #
2026-00000424
CHARGES
$600.00
Less Prepayment
Total Due —
City of Waterloo
$0.00
$600.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
2.46t6 yuto
Waterloo Fire Rescue
Inspection Report
Best Western - W 4th ST, BLDG 205 W 4th St, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
03/24/2026
Lead lnspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
16355
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
049
Passed codes
NEXT STEPS
31
Failed codes
18
N/A codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 03/25/2026 @ 07:44
$600 annual inspection fee
BRAD BALDWIN - 03/25/2026 @ 07:47
Fire alarm inspection and report including deficiencies corrected due 5/14/26.
BRAD BALDWIN - 03125/2026 @ 07:52
Fire extinguishers due annually serviced in July 2026
BRAD BALDWIN - 03/25/2026 @ 12:10
Reinspection Date
04/3012026
Corrected during 3/24126 inspection: (1) Removed space heater from 1st floor Assistant General Manager's office. (2) Removed stand up lamps plugged to
extension cords in unoccupied rooms walked today.
BRAD BALDWIN - 03/30/2026 @ 07:27
Sprinkler heads and escutcheon plates shall be free of debris and paint at all times, multiple escutcheons noted with paint that shall b removed. (1) 204
bathroom, (2) 4th floor outside elevators, (3) room 806, (4) Near room 913, (5) Near sales office 1st floor
BRAD BALDWIN - 03131/2026 @ 11:15
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 03131/2026 @ 11:15
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
GENERATED ON 3/31/26, 11:17 AM 1 OF 17
Report completed post inspection
Kari Smith gen Mgr 2022 Date:
CHECKLISTS
Emergency Equipment
Status Code
Fail
Fail
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
1�6
Description
Location: Egress lighting
Comments: Provide documentation of testing all emergency egress
lighting in the building including repairs made to maintain working
properly, documentation shall include address, signature and date of
responsible person.
Location: Exit signs
Comments: Provide documentation of testing all exit signs in the
building including repairs made to maintain working properly,
documentation shall include address, signature and date of
responsible person.
GENERATED ON 3/31/26, 11:17 AM 2 OF 17
Additional Codes
Status Code
Description
Fail
Fail
Fail
5303.5.3 - Securing compressed gas containers, cylinders
and tanks.
Compressed gas containers, cylinders and tanks shall be
secured to prevent falling caused by contact, vibration or
seismic activity. Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers, cylinders and tanks to a fixed object
with one or more restraints. 2.Securing containers, cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers, cylinders or tanks.
3. Nesting of compressed gas containers, cylinders and tanks
at container filling or servicing facilities or in sellers'
warehouses not open to the public. Nesting shall be allowed
provided that the nested containers, cylinders or tanks, if
dislodged, do not obstruct the required means of egress.
4.Securing of compressed gas containers, cylinders and
tanks to or within a rack, framework, cabinet or similar
assembly designed for such use. Exception: Compressed gas
containers, cylinders and tanks in the process of
examination, filling, transport or servicing.
610.1.2 - Maintenance.
The lint trap, mechanical and heating components, and the
exhaust duct system of a clothes dryer shall be maintained in
accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that
prevents the exhaust of air and products of combustion.
907.10 - Smoke alarm maintenance.
Smoke alarms shall be tested and maintained in accordance
with the manufacturer's instructions. Smoke alarms shall be
replaced when they fail to respond to operability tests, or
when they exceed 10 years from the date of manufacture,
unless an earlier replacement is specified in the
manufacturer's published instructions.
Location: Basement boiler room
Comments: Secure compressed gas cylinders with chain to avoid tip
over.
Location: House and guest laundry dryers
Comments: Provide documentation of cleaning of dryer vents from
appliances to the exterior of the building with address, signature and
date. Email documentation to fire inspector.
Location: Smoke & carbon monoxide detection
Comments: Provide document of testing all detection devices and are
working properly. Document shall include date, location and person
completing testing.
GENERATED ON 3/31/26, 11:17 AM 3 OF 17
i
Fail
907.6 - Installation and monitoring.
A fire alarm system shall be installed and monitored in
accordance with Sections 907.6.1 through 907.6.6.3 and NFPA
72.
Location: 9th floor near room 913
Comments: Alarm device loose to bracket shall be corrected.
GENERATED ON 3/31/26, 11:17 AM 4 OF 17
Electrical Safety
status Code
Description
Fail
Fail
Fail
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.5 - Relocatable power taps and current taps.Multiplug
adapters.
Multiplug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Back office behind check -in counter
Comments: Provide missing cover to box behind fridge
Location: 2nd floor "Maintenance room"
Comments: Provide missing covers to open box near bathroom and
on ceiling near exit door.
Location: 4th floor electric room
Comments: Remove multi plug adapter, may replace with properly
mounted power strip with manual reset for low wattage electronics
only.
Location: Occupant rooms
Comments: Remove all extension cords noted in several rooms
plugged to stand up lamps. Provide document stating all rooms have
been checked and extension cords removed.
GENERATED ON 3/31/26, 11:17 AM
5 OF 17
Fail
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: East stair tower (10th floor) near elevator equipment room
Comments: Licensed electrical contractor shall be obtained to repair
wiring to exterior lighted sign that does not comply with electrical
code. Proper permits and inspections shall be obtained for repair.
Location: Main lobby TV near check -in counter
Comments: Remove extension cord plugged to TV, may replace with
properly mounted power strip with manual reset for low wattage
electronics only.
GENERATED ON 3/31/26, 11:17 AM 6 OF 17
Fire Resistant Construction Maintenance
Sts w s C00,3
Fail
Fail
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floorlceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Description
Location: 6th floor west stair tower
Comments: Door frame to stair tower missing fire rating label. Frame
shall be re -certified or replaced by obtaining permit and inspection.
Replace missing door frame smoke seals. Door label shall be
maintained as to not alter or remove label information.
Location: Room 1004
Comments: Adjoining rooms door frame missing smoke seals.
GENERATED ON 3/31/26, 11:17 AM 7 OF 17
Fail
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: 5th floor west stair tower
Comments: Door frame to stair tower missing fire rating label. Frame
shall be re -certified or replaced by obtaining permit and inspection.
Door label shall be maintained as to not alter or remove label
information.
GENERATED ON 3/31/26, 11:17 AM
8 OF 17
Fail
Fail
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floorlceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: 8th floor east stair tower
Comments: Door frame to stair tower missing fire rating label. Frame
shall be re -certified or replaced by obtaining permit and inspection.
Door label shall be maintained as to not alter or remove label
information.
Location: 7th floor west stair tower
Comments: Door frame to stair tower missing fire rating label. Frame
shall be re -certified or replaced by obtaining permit and inspection.
Door label shall be maintained as to not alter or remove label
information.
GENERATED ON 3/31/26, 11:17 AM 9 OF 17
•- Ittit • • •"'"'
t.
1,-. •
- . ^
Fail
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Room 806
Comments: Install missing smoke seal on door frame.
GENERATED ON 3/31/26, 11:17 AM 10 OF 17
r
Fail
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
rooflceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: 10th floor ceiling near elevators
Comments: Replace missing ceiling tiles (1) on each side of hallway.
GENERATED ON 3/31/26, 11:17 AM
11 OF 17
Fail
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: 3rd floor west stair tower
Comments: Door frame to stair tower missing fire rating label. Frame
shall be re -certified or replaced by obtaining permit and inspection.
Door label shall be maintained as to not alter or remove label
information.
GENERATED ON 3/31/26, 11:17 AM
12 OF 17
Fail
Fail
704.1- Maintaining protection.
Where required when the budding was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floorlceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: 8 floor west stair tower
Comments: Door frame to stair tower missing fire rating label. Frame
shall be re -certified or replaced by obtaining permit and inspection.
Door label shall be maintained as to not alter or remove label
information.
Location: 10th floor west stair tower
Comments: Door fire rating label painted over, carefully remove paint
too avoid altering or removing label information. Door frame to stair
tower missing fire rating label. Frame shall be re -certified or replaced
by obtaining permit and inspection.
GENERATED ON 3/31/26, 11:17 AM 13 OF 17
Fail
Fail
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floorlceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: 3rd floor east stair tower
Comments: Door frame to stair tower missing fire rating label. Frame
shall be re -certified or replaced by obtaining permit and inspection.
Door label shall be maintained as to not alter or remove label
information.
Location: 9th floor west stair tower
Comments: Door frame to stair tower missing fire rating label. Frame
shall be re -certified or replaced by obtaining permi'.: and inspection.
Door label shall be maintained as to not alter or remove lab&
information.
GENERATED ON 3/31/26, 11:17 AM 14 OF 17
i
Fail
Fail
Fail
Fail
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Location: 4th floor west stair tower
Comments: Door frame to stair tower missing fire rating label. Frame
shall be re -certified or replaced by obtaining permit and inspection.
Door label shall be maintained as to not alter or remove label
information.
Location: Basement record storage room
Comments: Repair or replace door that failed to seI -shut and latch.
Replacing door requires obtaining permit and inspection.
Location: Basement "Governors" room
Comments: Remove door hold open device from door.
Location: 8th floor west stair tower
Comments: Repair or replace door to stair tower that failed to self -
shut and latch.
GENERATED ON 3/31/26, 11:17 AM
15 OF 17
1..91111MPIG91111.21.21•M
Fail
Fail
0
Fail
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
705.2.6 - Testing.
Horizontal and vertical sliding and rolling fire doors shall be
inspected and tested annually to confirm proper operation
and full closure. Records of inspections and testing shall be
maintained.
Location: Basement "Mayors" room
Comments: Remove door hold open device from door.
Location: Basement "Riverside" room
Comments: Remove door hold open device from door.
Location: All fire drop doors
Comments: Provide documentation of inspections of all fire drop
doors in building including any deficiencies corrected.
GENERATED ON 3/31/26, 11:17 AM 16 OF 17