COMMERCIAL INSPECTION - 305 W 4TH ST - 03/31/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #,
CHARGES
11328
04/07/2026
05/12/2026
2026-00000421
$80.00
Less Prepayment
Total Due —
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
11328 �So
Waterloo Fire Rescue
Inspection Report
Red Apple Chinese Restaurant - 305 W 4th ST, BLDG 305 W 4th St, Waterloo IA
50701
INSPECTION DETAILS
Inspection Date
03131/2026
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
1229
Shift Station Unit
N/A NIA NIA
SUMMARY OF INSPECTION
036 021 ®24
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 04/0112026 @ 07:52
580 annual inspection fee
BRAD BALDWIN - 04/01/2026 @ 15:48
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (45) - Cell: 319-230-1224
BRAD BALDWIN - 04/0112026 @ 15:48
Reinspection Date
05/01/2026
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at 5100, then 6150, and 5200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
Yen Zheng (2026)
CHECKLISTS
No signature
Report completed post inspection
Date: BRAD BALDWIN 04/01/2026
GENERATED ON 4/1/26, 3:49 PM 1 OF 10
Additional Codes
St tuft
Code Description
Fail
1016.2 - Egress through intervening spaces.
Egress through intervening spaces shall comply with this
section. 1. Exit access through an enclosed elevator lobby is
permitted. Where access to two or more exits or exit access
doorways is required in Section 1006.2.1, access Accessto
not less than one of the required exits shall be provided
without travel through the enclosed elevator lobbies required
by Section 3006 of the International Building Code. Where the
path of exit access travel passes through an enclosed
elevator lobby the level of protection required for the
enclosed elevator lobby is not required to be extended to the
exit unless direct access to an exit is required by other
sections of this code. 2.Egress from a room or space shall
not pass through adjoining or intervening rooms or areas,
except where such adjoining rooms or areas and the area
served are accessory to one or the other, are not a Group H
occupancy and provide a discernible path of egress travel to
an exit. Exception: Means of egress are not prohibited
through adjoining or intervening rooms or spaces in a Group
H, S or F occupancy where the adjoining or intervening
rooms or spaces are the same or a lesser hazard occupancy
group. 3.An exit access shall not pass through a room that
can be locked to prevent egress. 4. Means of egress from
dwelling units or sleeping areas shall not lead through other
sleeping areas, toilet rooms or bathrooms. 5.Egress shall not
pass through kitchens, storage rooms, closets or spaces
used for similar purposes. Exceptions: 1. Means of egress are
not prohibited through a kitchen area serving adjoining
rooms constituting part of the same dwelling unit or sleeping
unit. 2. Means of egress are not prohibited through
stockrooms in Group M occupancies where all of the
following are met: 2.1.The stock is of the same hazard
classification as that found in the main retail area. 2.2.Not
more than 50 percent of the exit access is through the
stockroom. 2.3.The stockroom is not subject to locking from
the egress side. 2.4.There is a demarcated, minimum 44-inch-
wide (1118 mm) aisle defined by full- or partial -height fixed
walls or similar construction that will maintain the required
width and lead directly from the retail area to the exit without
obstructions.
Location: Door near bathroom to kitchen
Comments: Remove exit sign above doorway leading to kitchen,
properly cap electrical wires and contain in box.
GENERATED ON 4/1/26, 3:49 PM 2 OF 10
Fail
102.3 - Change of use or occupancy.
A change of occupancy shall not be made unless the use or
occupancy is made to comply with the requirements of this
code and the International Existing Building Code .
Exception: Where approved by the fire code official, a change
of occupancy shall be permitted without complying with the
requirements of this code and the International Existing
Building Code , provided that the new or proposed use or
occupancy is less hazardous, based on life and fire risk, than
the existing use or occupancy.
Emergency Equipment
Status Code
Fail
1^J
Fail
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
General Housekeeping
Status Code
Fail
304.3.1- Spontaneous ignition.
Materials susceptible to spontaneous ignition, such as oily
rags, shall be stored in a listed disposal container. Contents
of such containers shall be removed and disposed of daily.
Location: Near bathroom hallway
Comments: Remove bed from building immediately, sleeping not an
approved use in commercial space.
Description
Location: Front exit
Comments: Repair or replace egress lights on exit sign above front
exit that failed to illuminate during test.
Location: Back exit near basement stairs
Comments: Repair or replace exit sign and egress lights combo that
failed to illuminate during test.
Description
Location: Kitchen
Comments: Provide listed container with self -closing lid to dispose of
oily rags. See attachment
GENERATED ON 4/1/26, 3:49 PM
3 OF 10
Fire Service Features
Status Code Description
Fail 509.2 - Equipment access.
0 Approved access shall be provided and maintained for all fire Location: Basement gas meter
protection system equipment to permit immediate safe Comments: Remove obstructions in path to gas meter, maintain clear
operation and maintenance of such equipment. Storage, trash path at all times.
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
Fail
509.2 - Equipment access.
Approved access shall be provided and maintained for all fire
protection system equipment to permit immediate safe
operation and maintenance of such equipment. Storage, trash
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
Location: Kitchen - Class K fire extinguisher
Comments: Remove all obstructions to accessing fire extinguisher,
maintain proper clearances at all times.
GENERATED ON 4/1/26, 3:49 PM
4 OF 10
Electrical Safety
Status cod
Fail
Fail
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Description
Location: Kitchen- Outlet on walk-in fridge
Comments: Remove damaged multi -plug adapter from building.
Location: Basernent near compressors
Comments: Provide cover to floor joist junction box exposing wire
connections
GENERATED ON 4/1/26, 3:49 PM
5 OF 10
41611Ntaeai 1
Fail
Fail
®
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Location: Basement near compressors
Comments: Cover shall be installed properly to avoid exposing wire
connections.
Location: Basement near compressors
Comments: Provide missing cover to avoid exposed wire connection.
GENERATED ON 4/1/26, 3:49 PM
6 OF 10
Fail
Fail
Fail
Fail
Fail
603.5.2 - Application and usePower supply.
Relocatable power taps and current taps shall be directly
connected to a permanently installed receptacle. Exceptions:
1. Where approved for use in a Group A occupancy or in a
meeting room in a Group B occupancy, not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
603.5.3 - Installation.
Relocatable power tap cords shall not extend through walls,
ceilings, floors, under doors or floor coverings, or be subject
to environmental or physical damage.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Ordering counter & cabinet
Comments: All power strips shall plug directly to a permanent wall
outlet. Noted multiple power strips plugged to other power strips
near computer and throughout cabinet.
Location: Computer cabinet near bathroom hallway
Comments: Yellow corded power strip in cabinet shall be removed
from running through wall to adjacent room. Power strips with
manual resets shall be properly mounted for low wattage electrical
usage only.
Location: Basement chest freezer
Comments: Remove yellow extension cord plugged to freezer,
appliance shall be relocated to plug directly to a permanent wall
outlet. Adding a new outlet would require a licensed electrical
contractor obtaining permit and inspection.
Location: Kitchen "cold table"
Comments: Remove table from plugged to extension cord, appliance
shall plug directly to permanent wall outlet.
Location: Room near bathroom hallway
Comments: Remove extension cord plugged to ye'rlow power strip for
light fixture.
GENERATED ON 4/1/26, 3:49 PM 7 OF 10
Commercial Cooking Hood Suppression System
Status Code
Description
Fail
Fail
Fail
606.3.3 - Cleaning.
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be cleaned at intervals as required by
Sections 606.3.3.1 through 606.3.3.3.
606.3.3.1- Inspection.
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be inspected at intervals specified in
Table 606.3.3.1 or as approved by the fire code official.
Inspections shall be completed by qualified individuals.
606.3.3.2 - Grease accumulation.
If during the inspection it is found that hoods, grease -removal
devices, fans, ducts or other appurtenances have an
accumulation of grease, such components shall be cleaned in
accordance with ANSIIIKECA C10.
Location: Kitchen exhaust hood
Comments: Exhaust system cleaning 43 days past due as of 411I26.
Provide cleaning and report to be uploaded to Compliance Engine
with any deficiencies corrected. Deficiency notice attached from AKA
services shall be corrected with report uploaded to Compliance
Engine.
m
Location: Kitchen hood suppression system
Comments: Provide suppression system inspection report with any
deficiencies corrected. Contractor must upload report to Compliance
Engine. Currently 381 days past due, current tags on system do not
note last service date.
Location: Kitchen exhaust hood
Comments: Clean grease filters. currently dripping grease.
GENERATED ON 4/1/26, 3:49 PM 8 OF 10
Portable Fire Extingusihers
Status Code
Fail
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
906.7 - Hangers and brackets.
Hand-held portable fire extinguishers, not housed in cabinets,
shall be installed on the hangers or brackets supplied.
Hangers or brackets shall be securely anchored to the
mounting surface in accordance with the manufacturer's
installation instructions.
Description
Location: All fire extinguishers
Comments: Provide annual service to extinguishers, last recorded
service completed in February 2024.
Location: Kitchen - near fryers
Comments: Fire extinguisher shall be properly mounted on wall
bracket, currently sitting on floor. Remove bag covering extinguisher.