COMMERCIAL INSPECTION - 1709 LA PORTE RD - 04/06/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
6140
04/07/2026
05/12/2026
2026-00000410
$80.00
Less Prepayment
Total Due -�
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
(Q140 4So
Waterloo Fire Rescue
Inspection Report
McDonalds - 1709 La Porte RD, BLDG 1709 La Porte Rd, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
04106/2026
Leadlnspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
21589
Shift Station Unit
N/A NIA NIA
SUMMARY OF INSPECTION
0 44
Passed codes
NEXT STEPS
0 8
Failed codes
0 24
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 04/06/2026 @ 11:24
$80 annual inspection fee
BRAD BALDWIN - 04/06/2026 @ 11:31
Fire extinguishers due annually serviced in October 2026
BRAD BALDWIN - 04/06/2026 @ 11:39
Kitchen hood suppression system inspection due 4/20/26
BRAD BALDWIN - 04/07/2026 @ 12:15
• Commercial Fire Inspector - brad.baldwin@waterloo-iaorg - Work: 319-291-4319 (115) - Cell: 319-230-1224
BRAD BALDWIN - 04/07/2026 @ 12:15
Reinspection Date
05/07/2026
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at S100, then S150, and S200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
Heather Lovell 2026
CHECKLISTS
No signature
Report completed post inspection
Date: BRAD BALDWIN 04/07/2026
GENERATED ON 4/7/26, 12:17 PM 1 OF 5
Emergency Equipment
SLdes Code
Fail
Fail
Fail
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Description
Location: Kitchen (west exit)
Comments: Repair or replace exit sign that failed to illuminate during
test.
Location: NE dining exit
Comments: Repair or replace exit sign that failed to illuminate during
test.
Location: Kitchen near ice machine
Comments: Repair or replace exit sign that failed to illuminate during
test.
GENERATED ON 4/7/26, 12:17 PM 2 OF 5
Electrical Safety
Status code
Fail
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Description
Location: Walk-in freezer
Comments: Provide missing cover to avoid exposed wires
Location: Kitchen
Comments: Multiple locations including but not limited to: (1) Above
kitchen west exit, (2) North drive-thru window. (3) Above kitchen
grills: Flexible cords shall not extend through a concealed area
including above drop ceiling. If choose to add new outlets to comply,
a licensed electrical contractor shall obtain permits and inspection.
GENERATED ON 4/7/26, 12:17 PM
3 OF 5
�P�
Additional Codes
Status Code
Fail
603.9.1- Listed and labeled.
Only listed and labeled portable, electric space heaters shall
be used.
Fire Resistant Construction Maintenance
Status Cote
Fail
Fail
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Description
Location: Kitchen "Break area"
Comments: Provide documentation of proper listing and labeling of
commercially approved space heater or remove from budding.
Description
Location: Kitchen hallway near waste oil containers
Comments: Install all missing or loose ceiling tiles
Location: Door to garage
Comments: Repair or replace fire rated door that faled to self -close
and latch. Replacement of door will require permit and inspection
obtained.
GENERATED ON 4/7/26, 12:17 PM 4 OF 5