COMMERCIAL INSPECTION - 626 SYCAMORE ST - 04/16/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
REINSPECTION 2
$150.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
24658
04/21/2026
05/26/2026
2026-00000438
$150.00
Less Prepayment
Total Due —�
City of Waterloo
$0.00
$150.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Pryme Tylne DG 626 Sycamore St, Waterloo IA 50703
INSPECTION DETAILS
Inspection Date
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
425 E. 3rd Street
Inspection Number
20185-R3
Other Inspectors
N/A
Shift
NIA
Station
NIA
Unit
NIA
SUMMARY OF INSPECTION
0 0 0 2
Passed codes Resolved violations
NEXT STEPS
0 7
Failed codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 04/1712026 @ 08:20
Reinspection Date
05/08/2026
$150 re -inspection fee, failure to complete corrections as of 4116/26. Complete corrections to avoid possible fees at following inspections3
BRAD BALDWIN - 03/1912026 @ 15:02
Withholding re -inspection fee today, complete corrections to avoid possible fees at later inspections.
BRAD BALDWIN - 03/1912026 @ 15:02
• $80 annual inspection fee
BRAD BALDWIN - 03/19/2026 @ 15:02
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 03/1912026 @ 15:02
• Provide corrections to avoid progressive re -inspection fees beginning at 5100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 03/19/2026 @ 15:02
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 03/1912026 @ 15:02
$100 re -inspection fee, failure to complete corrections as of 3/19126.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
GENERATED ON 4/17/26, 8:24 AM 1 OF 6
Keaton (2026) Date:
CHECKLISTS
BRAD BALDWIN 0411712026
GENERATED ON 4/17/26, 8:24 AM
2 OF 6
Reinspection
Status_
Fail
1013.1 - Where required.
Exits and exit access doors shall be marked by an approved
exit sign readily visible from any direction of egress travel.
The path of egress travel to exits and within exits shall be
marked by readily visible exit signs to clearly indicate the
direction of egress travel in cases where the exit or the path
of egress travel is not immediately visible to the occupants.
Intervening means of egress doors within exits shall be
marked by exit signs. Exit sign placement shall be such that
any point in an exit access corridor or exit passageway is
within 100 feet (30 480 mm) or the listed viewing distance of
the sign, whichever is less, from the nearest visible exit sign.
Exceptions: 1.Exit signs are not required in rooms or areas
that require only one exit or exit access. 2.Main exterior exit
doors or gates that are obviously and clearly identifiable as
exits need not have exit signs where approved by the fire
code official. 3.Exit signs are not required in occupancies in
Group U and individual sleeping units or dwelling units in
Group R-1, R-2 or R-3. 4.Exit signs are not required in
dayrooms, sleeping rooms or dormitories in occupancies in
Group 1-3. 5.In occupancies in Groups A-4 and A-5, exit signs
are not required on the seating side of vomitories or openings
into seating areas where exit signs are provided in the
concourse that are readily apparent from the vomitories.
Egress lighting is provided to identify each vomitory or
opening within the seating area in an emergency.
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Description
Location: Near bathrooms
Comments: Exit sign shall be turned 90 degrees to direct egress
towards alley exit between bathrooms.
Additional comments: No progress today 4116126
Location: High bay egress lights
Comments: Provide documentation of testing lights including repairs
made if necessary confirming working properly. Document shall
include address, date and signed, email to inspector,
Additional comments: No progress today 4116126
Location: Basement (west of stairs)
Comments: Install cover on box
GENERATED ON 4/17/26, 8:24 AM
3 OF 6
Fail 603.5.2 - Application and usePower supply.
Relocatable power taps and current taps shall be directly
connected to a permanently installed receptacle. Exceptions:
1. Where approved for use in a Group A occupancy or in a
meeting room in a Group B occupancy, not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
Fail 701.5 - Maintaining protection.
Materials, systems and devices used to repair or protect
breaches and openings in fire -resistance -rated construction
and construction installed to resist the passage of smoke
shall be maintained in accordance with Sections 703 through
707.
Location: Bar
Comments: Power strip plugged to another power strip at front of bar
shall be corrected. All power strips shall plug directly to wall outlets
for light duty electric only.
Additional comments: Current power strip behind cooler in bar shall
be properly mounted to wall or supported to avoid hanging by wires
Location: Bathroom hallway
Comments: Obtain permit and inspection to install rated fire door to
neighboring space, currently plywood covering door opening.
Additional comments: No progress today 4116126
GENERATED ON 4/17/26, 8:24 AM
4 OF 6
Fail
Fail
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
rooflceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
901.4.6 - Appearance of equipment.
Any device that has the physical appearance of life safety or
fire protection equipment but that does not perform that life
safety or fire protection function shall be prohibited.
Location: Ceiling
Comments: Obtain permit and inspection and repair hole in ceiling.
Additional comments: No progress today 4116/26
Location: Smoke detectors
Comments: All smoke detectors in building shall be maintained as
working properly. Noted detectors beeping and covers off today
1/27/26.
Additional comments: No progress today 4116126
GENERATED ON 4/17/26, 8:24 AM
5 OF 6
Statement of Fees
FEE
Invoice Date Inspection Fee
NIA $150.00
Invoice Number
NIA
Date Paid Amount Paid
Check Number Transaction Number
NIA NIA
GENERATED ON 4/17/26, 8:24 AM
6 OF 6