COMMERCIAL INSPECTION - 1309 LAFAYETTE ST - 04/14/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
23198
04/21/2026
05/26/2026
2026-00000441
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
C
Waterloo Fire Rescue
Inspection Report
Prime Mart 7 - 1309 Lafayette ST, BLDG 1309 Lafayette St, Waterloo IA 50703
INSPECTION DETAILS
Inspection Date
1111111110
Lead Inspector
BRAD BALDWIN
Inspection Type
Other inspectors
N/A
425 E. 3rd Street
Inspection Nurser
16759
Shift Station Unit
NIA NIA N/A
SUMMARY OF INSPECTION
0 32
Passed codes
NEXT STEPS
0 11 ®36
Failed codes NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 0411512026 @ 08:26
$80 Annual inspection fee
BRAD BALDWIN - 04/1612026 @ 07:22
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
05/0712026
BRAD BALDWIN - 04/16/2026 @ 07:23
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 04/1612026 @ 07:23
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Usman Chatha 2026 Date: BRAD BALDWIN 0411612026
CHECKLISTS
GENERATED ON 4/16/26, 7:25 AM 1 OF 9
Additional Codes
Status Code
Fail
Fail
Fail
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
603.1.1 - Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
603.9.1- Listed and labeled.
Only listed and labeled portable, electric space heaters shall
be used.
Description
Location: Electric permit
Comments: Contractor (B & C Electric of Iowa) shall obtain
inspection of work completed. Permit obtained for "12 outlets" in
December 2025.
Location: LED lighting (front exterior windows & above coolers)
Comments: Provide documentation of listing of lights. Lighting shall
be properly listed and comply with listing.
Location: Liquor storage
Comments: Provide documentation of proper listing and labeling of
commercially approved heater or remove from building.
GENERATED ON 4/16/26, 7:25 AM 2 OF 9
Electrical Safety
States Code
Fail
Fail
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Description
Location: Near Lotto machine/register counter
Comments: Conduit drop shall be properly supported, currently not
anchored or supported to anything. Also, outlet cover is loose and
shall be properly installed to avoid exposing wires in box.
Location: Front of building near ice machine
Comments: Exterior rated cover shall be installed and repairs made
to avoid exposed wiring to exterior elements.
GENERATED ON 4/16/26, 7:25 AM
3 OF 9
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Location: Near front exit - behind Coke fridge
Comments: Replace broken outlet cover
GENERATED ON 4/16/26, 7:25 AM 4 OF 9
Fail
Fail
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
Tess, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
603.5.2 - Application and usePower supply.
Relocatable power taps and current taps shall be directly
connected to a permanently installed receptacle. Exceptions:
1. Where approved for use in a Group A occupancy or in a
meeting room in a Group B occupancy, not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
Location: Back storage room
Comments: Remove storage within 36 inches of electric panels.
Maintain proper clearances and ready access to panels at all times.
Location: Register counter
Comments: Remove power strip plugged to another power strip near
register, must plug directly to wall outlet.
GENERATED ON 4/16/26, 7:25 AM
5 OF 9
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Behind counter
Comments: Remove green extension cord
GENERATED ON 4/16/26, 7:25 AM
6 OF 9
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Above Monster bev fridge at front wall of building.
Comments: Remove black cord extending above drop ceiling.
GENERATED ON 4/16/26, 7:25 AM 7 OF 9
Portable Fire Extingusihers
Status Code
Fail
906.7 - Hangers and brackets.
Hand-held portable fire extinguishers, not housed in cabinets,
shall be installed on the hangers or brackets supplied.
Hangers or brackets shall be securely anchored to the
mounting surface in accordance with the manufacturer's
installation instructions.
Description
Location: Liquor storage
Comments: Install fire extinguisher on wall bracket in required
location, currently sitting on floor.
GENERATED ON 4/16/26, 7:25 AM 8 OF 9