COMMERCIAL INSPECTION - 1008 LA PORTE RD - 04/14/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
13811
04/21/2026
05/26/2026
2026-00000439
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
1 3,8 I \ .$40,0
Waterloo Fire Rescue
Inspection Report
Prime Mart #3 - 1008 La Porte RD, BLDG 1008 La Porte Rd, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
1111111111111
Lead Inspector
BRAD BALDWIN
Inspection Type
Other Inspectors
N/A
425 E. 3rd Street
Inspection Number
16505
Sii Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
034 09
Passed codes Failed codes
NEXT STEPS
36
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 0411512026 @ 07:46
$80 annual inspection fee
BRAD BALDWIN - 04/1512026 @ 15:40
• Comrnercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
05/0612026
BRAD BALDWIN - 04/15/2026 @ 15:40
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 0411512026 @ 15:41
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and 9200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Aftab Chatha Date: BRAD BALDWIN 04/15/2026
CHECKLISTS
GENERATED ON 4/15/26, 3:47 PM
1 OF 6
Additional Codes
Status Code
Fail 102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
Fail
Fail
2305.2.1 - Inspections.
Flammable and combustible liquid fuel -dispensing and
containment equipment shall be periodically inspected where
required by the fire code official to verify that the equipment
is in proper working order and not subject to leakage.
Records of inspections shall be maintained.
2305.2.1 - Inspections.
Flammable and combustible liquid fuel -dispensing and
containment equipment shall be periodically inspected where
required by the fire code official to verify that the equipment
is in proper working order and not subject to leakage.
Records of inspections shall be raintained.
Fail 603.1.1 - Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
Description
Location: Water heater
Comments: Licensed plumbing contractor shall obtain permit and
inspection for water heater installed without permit.
Location: Gas pump # 4
Comments: Visual signs of leakage at top of flexible hose, necessary
repairs shall be completed.
Location: Gas pump #6
Comments: Visual signs of leakage at top of flexible hose, necessary
repairs shall be completed.
Location: LED lighting
Comments: Provide documentation of listing of lights in clear display
cases at counter. Lighting shall be properly listed and comply with
listing.
GENERATED ON 4/15/26, 3:47 PM 2 OF 6
General Housekeeping
Status Codi:
Fail
315.3.1- Ceiling clearance.
Storage shall be maintained 2 feet (610 mm) or more below
the ceiling in nonsprinklered areas of buildings or not less
than 18 inches (457 mm) below sprinkler head deflectors in
sprinklered areas of buildings. Exceptions: 1.The 2-foot (610
mm) ceiling clearance is not required for storage along walls
in nonsprinklered areas of buildings. 2.The 18-inch (457 mm)
ceiling clearance is not required for storage along walls in
areas of buildings equipped with an automatic sprinkler
system in accordance with Section 903.3.1.1, 903.3.1.2 or
903.3.1.3.
Fire Service Features
Status Code
Fail
505.1 - Address identification.
New and existing buildings shall be provided with approved
address identification. The address identification shall be
legible and placed in a position that is visible from the street
or road fronting the property. Address identification
characters shall contrast with their background. Address
numbers shall be Arabic numbers or alphabetical letters.
Numbers shall not be spelled out. Each character shall be not
less than 4 inches (102 mm) high with a minimum stroke
width of 1/2 inch (12.7 mm). Where required by the fire code
official, address identification shall be provided in additional
approved locations to facilitate emergency response. Where
access is by means of a private road and the building cannot
be viewed from the public way, a monument, pole or other
sign or means shall be used to identify the structure. Address
identification shall be maintained.
Description
Location: Above "Monster beverage fridge"
Comments: Remove storage above fridge, no storag,t allowed within
24 inches of ceiling.
Description
Location: Front of building
Comments: Install address identification numbers (mL nimum 4" in
height) on the building in contrast with the building facing La Porte
Rd.
GENERATED ON 4/15/26, 3:47 PM
3 OF 6
Electrical Safety
Status Cede
Fail
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not Tess than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Description
Location: Back storage room
Comments: REPEAT VIOLATION: Remove storage within 36" of
electric panels. Maintain proper clearance from electrical equipment
at all times. Continuing to obstruct equipment will require marking
tape on floor where storage shall not be stored within.
GENERATED ON 4/15/26, 3:47 PM
4 OF 6
Portable Fire Extingusihers
Sta u= Cod
Fail
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Location: Near front exit
Comments: Service tag fails to note date of service, provide date of
service.
Location: Near large beverage coolers
Comments: Provide annual service to extinguisher, currently missing
tag noting last recorded service
GENERATED ON 4/15/26, 3:47 PM