COMMERCIAL INSPECTION - 2225 E SHAULIS RD - 04/14/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 20,000
OCCUPANCY FEE
$90.00
$10.00
CUSTOMER #
10030
BILLING DATE
DUE DATE
INVOICE #
CHARGES
04/21/2026
05/26/2026
2026-00000440
City of Waterloo
Less Prepayment
Total Due —�
$100.00
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
10030 cOost
Waterloo Fire Rescue
Inspection Report
Lost Island Waterpark -111111111111111is RD, BLDG 2225 E Shaulis Rd, Waterloo IA
50702
INSPECTION DETAILS
Inspection Date
Lead Inspector
BRAD BALDWIN
Inspection Type
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
16966
Shift Station Unit
NIA N/A N/A
SUMMARY OF INSPECTION
053
Passed codes
NEXT STEPS
027
Failed codes
0 10
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 04/1412026 @ 11:19
$100 annual inspection fee
BRAD BALDWIN - 04/15/2026 @ 16:24
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
05/05!2026
BRAD BALDWIN - 04115/2026 @ 16:24
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 0411512026 @ 16:24
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
Jesse Henry
CHECKLISTS
No signature
Report completed post inspection
Date: BRAD BALDWIN 04/15/2026
GENERATED ON 4/15/26, 4:31 PM 1 OF 10
Means of Egress
Status Code
Fail
Fail
1032.2 - Reliability.
Required exit accesses, exits and exit discharges shall be
continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
1032.2 - Reliability.
Required exit accesses, exits and exit discharges shall be
continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
Emergency Equipment
Status Code
Fail
Fail
Fail
Fail
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Fire Alarm System
Status Code
Fail
Chapter 14 - Inspection, testing, and maintenance
Fire alarm system tested at least annually by licensed
contractor
Description
Location: Gift shop storage room
Comments: Remove all obstructions in path of egress to exit door.
Location: Gift shop
Comments: Remove all obstructions in path of egress to exit door.
Description
Location: Office east
Comments: Repair or replace egress light above exit door.
Location: Gift shop
Comments: Repair or replace exit sign & egress lights combo that
failed to illuminate during test.
Location: Castaway Cafe
Comments: Repair or replace exit signs (2) that failed to illuminate
during test.
Location: Go kart building
Comments: Repair or replace exit signs & egress lights combos (2)
that failed to illuminate during test
Description
Comments: Provide inspection report of fire alarm with any
deficiencies corrected. Contractor must upload report to Compliance
Engine. Due for inspection as of 4128126
GENERATED ON 4/15/26, 4:31 PM 2 OF 10
Additional Codes
Status Code
Fail
Fail
Fail
Fail
2303.2 - Emergency disconnect switches.
An approved emergency disconnect switch shall be provided
at an approved location to stop the transfer of fuel to the fuel
dispensers in the event of a fuel spill or other emergency. The
emergency disconnect switch for exterior fuel dispensers
shall be provided with ready access and shall be located
within 100 feet (30 480 mm) of, but not less than 20 feet (6096
mm) from, the fuel dispensers. For interior fuel -dispensing
operations, the emergency disconnect switch shall be
provided with ready access and be installed at an approved
location. Such devices shall be distinctly labeled as:
"EMERGENCY FUEL SHUTOFF." Signs shall be
provided in approved locations.
2304.3.5 - Emergency procedures.
An approved emergency procedures sign, in addition to the
signs required by Section 2305.6, shall be posted in a
conspicuous location and shall read: IN CASE OF FIRE,
SPILL OR RELEASE 1.USE EMERGENCY PUMP SHUTOFF
2.REPORT THE ACCIDENT! FIRE DEPARTMENT TELEPHONE
NO. FACILITY ADDRESS
2305.5 - Fire extinguishers.
Approved portable fire extinguishers complying with Section
906 with a minimum rating of 2-A:20-B:C shall be provided
and located such that an extinguisher is not more than 75 feet
(22 860 mm) from pumps, dispensers or storage tank fill -pipe
openings.
2305.6 - Warning signs.
Warning signs shall be conspicuously posted within sight of
each dispenser in the fuel -dispensing area and shall state the
following: 1.No smoking. 2.Shut off motor. 3.Discharge your
static electricity before fueling by touching a metal surface
away from the nozzle. 4.To prevent static charge, do not
reenter your vehicle while gasoline is pumping. 5.If a fire
starts, do not remove nozzle —back away immediately. 6.It is
unlawful and dangerous to dispense gasoline into
unapproved containers. 7.No filling of portable containers in
or on a motor vehicle. Place container on ground before
filling.
Description
Location: Go-kart fueling station
Comments: Provide inspector knowledge and location of emergency
disconnect switch and signage of disconnect or have properly
installed.
Location: Go- kart fueling station
Comments: Provide permanent required "Emergency Procedures"
signage in compliance with code near station, laminated paper will
not be accepted.
Location: Go-kart fueling station
Comments: Provide required sized fire extinguisher within 75 feet of
tank/fueling station.
Location: Go-kart fueling station
Comments: Provide permanent required ' Warning" signage in
compliance with code near station, laminated paper will not be
accepted.
GENERATED ON 4/15/26, 4:31 PM 3 OF 10
Fail
Fail
0
5003.5 - Hazard identification signs.
Unless otherwise exempted by the fire code official, visible
hazard identification signs as specified in NFPA 704 for the
specific material contained shall be placed on stationary
containers and above -ground tanks and at entrances to
locations where hazardous materials are stored, dispensed,
used or handled in quantities requiring a permit and at
specific entrances and locations designated by the fire code
official.
507.5.3 - Private fire service mains and water tanks.
Private fire service mains and water tanks shall be
periodically inspected, tested and maintained in accordance
with NFPA 25 at the following intervals: 1.Private fire hydrants
of all types: Inspection annually and after each operation;
flow test and maintenance annually. 2.Fire service main
piping: Inspection of exposed, annually; flow test every 5
years. 3.Fire service main piping strainers: Inspection and
maintenance after each use. Records of inspections, testing
and maintenance shall be maintained.
Location: Go-kart fueling tank
Comments: Replace faded NFPA 704 hazard labeling on fuel tank as
seen in photo attached.
Location: All of property
Comments: Provide annual inspection to all private hydrants, report
of inspection including any deficiencies corrected shall be uploaded
to Compliance Engine
GENERATED ON 4/15/26, 4:31 PM
4 OF 10
Fail
Fail
5704.2.3.2 - Label or placard.
Tanks more than 100 gallons (379 L) in capacity, which are
permanently installed or mounted and used for the storage of
Class I, II or III liquids, shall bear a label and placard
identifying the material therein. Placards shall be in
accordance with NFPA 704. Exceptions: 1.Tanks of 300-gallon
(1136 L) capacity or less located on private property and used
for heating and cooking fuels in single-family dwellings.
2.Tanks located underground.
610.1.1- Installation.
Clothes dryer exhaust duct systems shall be installed in
accordance with the International Mechanical Code or the
International Fuel Gas Code , and the manufacturer's
installation instructions.
Fire Service Features
Sta:.us Code
Fail
506.2 - Key box maintenance.
The operator of the building shall immediately notify the fire
code official and provide the new key where a lock is changed
or rekeyed. The key to such lock shall be secured in the key
box.
Location: Go-kart fueling tank
Comments: Replace faded "Gasoline" identification labeling on tank.
Location: Maintenance shop
Comments: Mechanical contractor shall obtain permit and inspection
to install dryer vent to discharge to the exterior air. Documentation of
dryer vent cleaning shall be kept and provided to inspector annually.
Description
Location: Knox Box
Comments: Keys have been changed, verify with inspector keys were
updated in Knox Boxes.
GENERATED ON 4/15/26, 4:31 PM 5 OF 10
Electrical Safety
status Code
Fail
Fail
Fail
IX�
Fail
Fail
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 min) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Description
Location: Wave pool equipment room
Comments: Provide missing outlet cover near blue filter tanks
Location: South filter room basement
Comments: Replace missing outlet cover on south wall
Location: Calypso pool equipment room
Comments: Replace missing outlet cover on south wall
Location: Figi concession stand
Comments: Replace missing outlet cover behind freezer
Location: Go kart electric room
Comments: Install missing outlet cover next to electric panels.
Location: Go kart electric room
Comments: Remove storage within 36" of electric equipment.
GENERATED ON 4/15/26, 4:31 PM 6 of 10
Fail
603.6 • Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Sales east office
Comments: Remove cord extending through wall to "cash room".
GENERATED ON 4/15/26, 4:31 PM
7 OF 10
Portable Fire Extingusihers
Status Code
Description
Fail 906.2 - General requirements.
', Portable fire extinguishers shall be selected, installed and Location: Tree Top Cafe
maintained in accordance with this section and NFPA 10. Comments: Provide annual service to extinguisher, last recorded
Exceptions: 1.The distance of travel to reach an extinguisher service completed April 2025
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confine that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Location: Molokini pump house
Comments: Provide annual service to all extinguishers, last recorded
service completed April 2025
GENERATED ON 4/15/26, 4:31 PM 8 OF 10
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.i.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
906.7 - Hangers and brackets.
Hand-held portable fire extinguishers, not housed in cabinets,
shall be installed on the hangers or brackets supplied.
Hangers or brackets shall be securely anchored to the
mounting surface in accordance with the manufacturer's
installation instructions.
Location: Go kart building
Comments: Provide annual service to all extinguishers, last recorded
service completed April 2025
Location: Sulu concession stand
Comments: Provide and install fire extinguisher on wall bracket
GENERATED ON 4/15/26, 4:31 PM
9 OF 10