COMMERCIAL INSPECTION - 1600 OLYMPIC DR - 04/15/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 20,000
OCCUPANCY FEE
$90.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
3311
04/21/2026
05/26/2026
2026-00000435
Less Prepayment
Total Due
City of Waterloo
CHARGES
$100.00
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
.1160 -41Now
Waterloo Fire Rescue
Inspection Report
Sunnyside Country Club , BLDG 1600 Olympic Dr, Waterloo IA
50701
INSPECTION DETAILS
Inspection Date
Lead Inspector
BRAD BALDWIN
Inspection Type
0111111111.1111111111110
Other Inspectors
N/A
425 E. 3rd Street
Inspection Number
16426
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
054 026 ®11
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 04/1612026 @ 07:26
$100 annual inspection fee
BRAD BALDWIN - 04/1612026 @ 07:29
Reinspection Date
05/0712026
Annual sprinkler system inspection due 517126. Complete inspection with report uploaded by contractor to Compliance Engine including any deficiencies
corrected.
BRAD BALDWIN - 04/1712026 @ 14:54
All extinguishers shall be annually serviced, different dates of last recorded service noted throughout property.
BRAD BALDWIN - 04/1712026 @ 14:56
Did not access pool equipment building during 4/15126 inspection.
BRAD BALDWIN - 04/1712026 @ 15:14
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 04117/2026 @ 15:14
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 04/17/2026 @ 15:14
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 am. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
GENERATED ON 4/17/26, 3:16 PM 1 OF 15
Report completed post inspection
Colin Kitson Date:
CHECKLISTS
1E
GENERATED ON 4/17/26, 3:16 PM
2 OF 15
Means of Egress
Status Code
Fail
Fail
1032.2 - Reliability.
Required exit accesses, exits and exit discharges shall be
continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
1032.2 - Reliability.
Required exit accesses, exits and exit discharges shall be
continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
Description
Location: Basement - Golf simulator area
Comments: Simulator obstructing egress path to marked exit: Per
City building Official Greg Ahlhelm, 2nd exit leading to interior
hallway not required, approved to remove exit sign and properly cap
electric wires in box with cover. Exit sign shall be installed above
employee "Service Hallway" directing path of egress to hallway.
Location: Basement exit path leading to golf simulator area
Comments: As seen in photo attached: Remove store;ge and
obstructions to clear path of egress to exit.
GENERATED ON 4/17/26, 3:16 PM
3 OF 15
Additional Codes
Status Code
Fail
2303.2 - Emergency disconnect switches.
An approved emergency disconnect switch shall be provided
at an approved location to stop the transfer of fuel to the fuel
dispensers in the event of a fuel spill or other emergency. The
emergency disconnect switch for exterior fuel dispensers
shall be provided with ready access and shall be located
within 100 feet (30 480 mm) of, but not less than 20 feet (6096
mm) from, the fuel dispensers. For interior fuel -dispensing
operations, the emergency disconnect switch shall be
provided with ready access and be installed at an approved
location. Such devices shall be distinctly labeled as:
"EMERGENCY FUEL SHUTOFF." Signs shall be
provided in approved locations.
Fail 2304.3.5 - Emergency procedures.
An approved emergency procedures sign, in addition to the
signs required by Section 2305.6, shall be posted in a
conspicuous location and shall read: IN CASE OF FIRE,
SPILL OR RELEASE 1.USE EMERGENCY PUMP SHUTOFF
2.REPORT THE ACCIDENT! FIRE DEPARTMENT TELEPHONE
NO. FACILITY ADDRESS
Fail
2305.6 - Warning signs.
Warning signs shall be conspicuously posted within sight of
each dispenser in the fuel -dispensing area and shall state the
following: 1.No smoking. 2.Shut off motor. 3.Discharge your
static electricity before fueling by touching a metal surface
away from the nozzle. 4.To prevent static charge, do not
reenter your vehicle while gasoline is pumping. 5.If a fire
starts, do not remove nozzle —back away immediately. 6.It is
unlawful and dangerous to dispense gasoline into
unapproved containers. 7.No filling of portable containers in
or on a motor vehicle. Place container on ground before
filling.
Description
Location: Maintenance garage
Comments: Provide permanent signage near interior emergency shut
off switches and also on the exterior of building in approved location.
Laminated paper will not be accepted.
Location: Maintenance garage fueling tanks
Comments: Provide permanent required Emergency Procedures
signage in compliance with code near station, laminated paper will
not be accepted.
Location: Maintenance garage fueling tanks
Comments: Provide permanent required "Warning" signage in
compliance with code near station, laminated paper will not be
accepted.
GENERATED ON 4/17/26, 3:16 PM
4 OF 15
Fail
Fail
509.2 - Equipment access.
Approved access shall be provided and maintained for all fire
protection system equipment to permit immediate safe
operation and maintenance of such equipment. Storage, trash
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
509.2 - Equipment access.
Approved access shall be provided and maintained for all fire
protection system equipment to permit immediate safe
operation and maintenance of such equipment. Storage, trash
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
Location: Basement utility room
Comments: Remove obstructions to ready access to sprinkler riser
room and electrical room. Maintain clear path at all times.
Location: Pro Shop - Maintenance area
Comments: Remove storage within 36" of sprinkler equipment,
maintain clearance at all times.
GENERATED ON 4/17/26, 3:16 PM
5 OF 15
Fail 5704.2.3.2 - Label or placard.
Tanks more than 100 gallons (379 L) in capacity, which are
permanently installed or mounted and used for the storage of
Class I, II or III liquids, shall bear a label and placard
identifying the material therein. Placards shall be in
accordance with NFPA 704. Exceptions: 1.Tanks of 300-gallon
(1136 L) capacity or less located on private property and used
for heating and cooking fuels in single-family dwellings.
2.Tanks located underground.
Fail
Fail
603.1- General.
Electrical equipment, wiring and systems required by this
code or the International Building Code shall be installed,
used and maintained in accordance with NFPA 70 and
Sections 603.2 through 603.10.
603.1- General.
Electrical equipment, wiring and systems required by this
code or the International Building Code shall be installed,
used and maintained in accordance with NFPA 70 and
Sections 603.2 through 603.10.
Location: Maintenance garage fueling station
Comments: Replace faded "Gasoline" identification labeling on tank
Location: Basement - Main bar
Comments: Remove roller grill machine plugged to power strip. Heat
producing appliances shall plug directly to a wall outlet
Location: Maintenance garage - Employee area
Comments: Remove microwave and coffee maker from plugged to
extension cord and multi -plug adapter. Each appliance shall plug
directly to wall outlet
GENERATED ON 4:17/26, 3:16 PM
6 OF 15
Fail
Fail
901.6 - Inspection, testing and maintenance.
Fire detection and alarm systems, emergency alarm systems,
gas detection systems, fire -extinguishing systems,
mechanical smoke exhaust systems and smoke and heat
vents protection and life safety systems shall be maintained
in an operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection and life
safety systems and equipment shall be inspected, tested and
maintained or removed in accordance with Section 901.8 .
906.3 - Size and distribution.
The size and distribution of portable fire extinguishers shall
be in accordance with Sections 906.3.1 through 906.3.4.
Location: Basement - Sprinkler Riser Room (near mean electric
panels)
Comments: Licensed sprinkler contractor shall make necessary
repair on sprinkler leak.
Location: Basement - Main bar area
Comments: Maximum distance of travel of 75 feet access to
extinguisher exceeded. Properly install extinguisher of required size
on wall bracket between 4in - 5ft from the floor on war l bracket.
Extinguisher shall be installed in a location that is accessible within
75 ft of the next nearest extinguisher.
GENERATED ON 4/17/26, 3:16 PM
7 OF 15
Electrical Safety
Status Code Description
Fail 603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified Comments: Replace damaged outlet.
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Location: Kitchen near electric panels labeled "L8"
Location: Colin's office
Comments: Install missing outlet covers (2)
GENERATED ON 4/17/26, 3:16 PM 8 OF 15
Fail
Fail
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Location: Basement - Main bar
Comments: NW corner TV - Install missing outlet cover and remove
multi -plug adapter. May replace adapter with properly mounted power
strip with manual reset for low wattage electrical equipment only.
Location: Basement - Gym Room
Comments: Provide cover to box exposing wires on north wall.
Location: Basement - Ladies locker room
Comments: Install missing outlet cover behind sitting chair near
lockers
GENERATED ON 4/17/26, 3:16 PM
9 OF 15
Fail 603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Fail 603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum dear opening of 22 inches (559 mm) by 30
inches (762 mm).
Location: Panel "L1" near business office
Comments: Remove storage within 36" of electric panel, maintain
ready access to utilities at all times.
Location: Pro Shop - Mechanical room
Comments: Remove storage within 36" of electrical panel and
maintain clear path of access at all times.
GENERATED ON 4/17/26, 3:16 PM
10 OF 15
Fail
Fail
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Commercial Cooking Hood Suppression System
sta:us Coco
Fail
606.3.3 - Cleaning.
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be cleaned at intervals as required by
Sections 606.3.3.1 through 606.3.3.3.
Location: Boiler room - Below fire alarm panel
Comments: Remove yellow extension cord.
Location: Basement - Golf simulator
Comments: Remove blue multi -use extension cord.
Location: Maintenance garage - Office
Comments: Remove extension cord plugged to printer.
Description
Location: Kitchen hood exhaust
Comments: Exhaust system cleaning past due. Provide cleaning and
report to be uploaded to Compliance Engine with any deficiencies
corrected.
GENERATED ON 4/17/26, 3:16 PM
11 OF 15
Fire Resistant Construction Maintenance
Status Cede
Fail 704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Description
Location: Basement - Main bar
Comments: Replace missing ceiling tile west of bar above doorway
GENERATED ON 4/17/26, 3:16 PM 12 OF 15
Portable Fire Extingusihers
Slates COCI,
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Location: Basement - Golf simulator area bar
Comments: Class K fire extinguisher due for annual service by May
2026
GENERATED ON 4/17/26, 3:16 PM
13 OF 15
Fail
O
906.6 - Unobstructed and unobscured.
Portable fire extinguishers shall not be obstructed or
obscured from view. In rooms or areas in which visual
obstruction cannot be completely avoided, means shall be
provided to indicate the locations of extinguishers.
Location: Pro Shop
Comments: Extinguisher shall be relocated to conspicuous, easily
accessed location or a "Fire Extinguisher" sign installed above
current location (See attachment)
GENERATED ON 4/17/26, 3:16 PM 14 OF 15
Statement of Fees
FEE
Invoice Date Inspection Fee
NIA $100.00
Invoice Number
N/A
Date Paid Amount Paid
Check Number Transaction Number
NIA NIA
GENERATED ON 4/17/26, 3:16 PM 15 OF 15