HomeMy WebLinkAbout728 COMMERCIAL STREET C050423 ilt4 "C'
Waterloo Fire Rescue
Inspection Report
t r 425 E.3rd Street
American Legion Post 138 - 728 Commercial ST, BLDG 728 Commercial St, Waterloo
IA 50702
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
04/21/2026 Annual Inspection (1Yr) 16758
Lead Inspector Shift Station Unit
BRAD BALDWIN N/A NIA N/A
Other Inspectors
NIA
SUMMARY OF INSPECTION
� 44 08 ® 25
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN 05/1412026
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 04/23/2026 @ 09:55
$80 annual inspection fee
BRAD BALDWIN -04/23/2026 @ 10:19
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org -Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN -04/23/2026 @ 10:19
• Provide corrections to avoid progressive re-inspection fees beginning at$100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 04123/2026 @ 10:19
• If all corrections are made before the scheduled re-inspection date, you can call to set up an earlier re-inspection. Normal operating hours for
inspections & re-inspections are Monday- Friday, 9:00 a.m. -4:00 p.m. *****Re inspection fees may be assessed for subsequent re-inspections. Re-
inspection fees start at $100, then $150, and $200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Kim Sigler 2026 Date: BRAD BALDWIN 04/23/2026
CHECKLISTS
GENERATED ON 4/23/26, 10:22 AM 1 OF 5
Emergency Equipment
Status Code Description
Fail 1203.2.6-Exit signs.
OEmergency power shall be provided for exit signs as required Location:Near stage at back entrance
in Section 1013.6.3.The system shall be capable of powering Comments:Repair or replace exit sign and egress lights combo that
the required load for a duration of not less than 90 minutes. failed to illuminate during test
Additional Codes
Status Code Description
Fail 5303.5.3-Securing compressed gas containers,cylinders
and tanks. Location:Back bar
Compressed gas containers,cylinders and tanks shall be Comments:Provide chain around compressed cylinder under bar to
secured to prevent falling caused by contact,vibration or avoid tip over hazard
seismic activity.Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers,cylinders and tanks to a fixed object
with one or more restraints.2.Securing containers,cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers,cylinders or tanks.
3.Nesting of compressed gas containers,cylinders and tanks
at container filling or servicing facilities or in sellers'
warehouses not open to the public.Nesting shall be allowed
provided that the nested containers,cylinders or tanks,if
dislodged,do not obstruct the required means of egress.
4.Securing of compressed gas containers,cylinders and
tanks to or within a rack,framework,cabinet or similar
assembly designed for such use.Exception:Compressed gas
containers,cylinders and tanks in the process of
examination,filling,transport or servicing.
a t
4 w
l
GENERATED ON 4/23/26, 10:22 AM 2 OF 5
Electrical Safety
Status Code Description
Fail 603.4-Working space and clearancesclearance.
Ox A working space of not Working space around electrical Location:Near back bar and kitchen entrance
equipment shall be provided in accordance with Section Comments:Remove storage in front of electric panel.
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less,and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts.The minimum required working space
shall be not less than 30 inches(762 mm)in width,36 inches
(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the
electrical service equipment is wider than 30 inches(762
mm),the minimum working space shall be not less than the
width of the equipment.Storage of materials shall not be
located within the designated working space.Exceptions:1.
Where other dimensions are required or allowed by NFPA 70.
2.Access openings into attics or under-floor areas that
provide a minimum clear opening of 22 inches(559 mm)by 30
inches(762 mm).
(7."
$ ,
Fail 603.4-Working space and clearancesclearance.
A working space of not Working space around electrical Location:Mechanical room near back bar
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or Comments:Remove obstructions to electric panels and all storage
less,and Section 110.33 of NFPA 70 for electrical equipment within 36 inches
rated over 1,000 volts.The minimum required working space
shall be not less than 30 inches(762 mm)in width,36 inches
(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the
electrical service equipment is wider than 30 inches(762
mm),the minimum working space shall be not less than the
width of the equipment.Storage of materials shall not be
located within the designated working space.Exceptions:1.
Where other dimensions are required or allowed by NFPA 70.
2.Access openings into attics or under-floor areas that
provide a minimum clear opening of 22 inches(559 mm)by 30
inches(762 mm).
Fail 603.5.3-Installation.
Relocatable power tap cords shall not extend through walls, Location:Behind popcorn machine
ceilings,floors,under doors or floor coverings,or be subject
to environmental or physical damage. Comments:Remove power strip plugged to extension cord,power
strip shall plug directly to wall outlet
GENERATED ON 4/23/26, 10:22 AM
2 0, 5
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Behind popcorn machine
for permanent wiring and shall be listed and labeled in Comments:Remove green extension cord.
accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Fail 603.6-Extension cords.
OExtension cords and flexible cordsshall not be a substitute Location:Front window
for permanent wiring and shall be listed and labeled in Comments:Remove lighted signage from extension cord
accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Fail 603.6-Extension cords.
l^J Extension cords and flexible cordsshall not be a substitute Location:Beer garden window
for permanent wiring and shall be listed and labeled in Comments:Remove'Beer Garden"lighted sign from extension cord
accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
ire'N
V.
A OF S
GENERATED ON 4/23/26, 10:22 AN
Po Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $80.00
Invoice Number Check Number Transaction Number
NIA NIA NIA
GENERATED ON 4/23/26, 10:22 AM 5 OF 5
OF WA rF INVOICE DATE DUE DATE INVOICE# TOTAL DUE
,�x 04/30/2026 06/05/2026 2026-00000445 $80.00
FAN
T .."�` O
4S 7V103•
Customer#: 6422 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
AMERICAN LEGION 715 Mulberry St
728 COMMERCIAL ST WATERLOO, IA 50703
WATERLOO, IA 50703
Amount Enclosed.
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION-728 COMMERCIAL ST- FOR BILLING INQUIRY: (319)291-4323
04/21/2026
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10 00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
6422 04/30/2026 06/05/2026 2026-00000445 $80.00
Less Prepayment $0.00
Total Due —* $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.