Waterloo Fire Rescue
Inspection Report 425 E.3rd Street
Walgreens - 111 W Ridgeway AVE, BLDG 111 W Ridgeway Ave, Waterloo IA 50701
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
04128/2026 Annual Inspection (1Yr) 17171
Lead Inspector1 Station Unit
BRAD BALDWIN NIA NIA NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
046 07 @21
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN 0512712026
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 04/29/2026 @ 06:57
$80 annual inspection fee
BRAD BALDWIN - 04129/2026 @ 07:41
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org -Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 04129/2026 @ 07:41
• Provide corrections to avoid progressive re-inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 04/29/2026 @ 07:41
• If all corrections are made before the scheduled re-inspection date, you can call to set up an earlier re-inspection. Normal operating hours for
inspections & re-inspections are Monday - Friday, 9:00 a.m. -4:00 p.m. *****Re inspection fees may be assessed for subsequent re-inspections. Re-
inspection fees start at $100, then $150, and $200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Toni Franklin Date: BRAD BALDWIN 04/2912026
CHECKLISTS
GENERATED ON 4/29/26, 7:52 AM 1 OF 4
Emergency Equipment
Stctls Code Description
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:Emergency egress lights
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:All egress lights shall be tested and repaired if non
functional,provide documentation of all lighting working properly to
inspector including signed and dated.
Fail 1203.2.6-Exit signs.
Emergency power shall be provided for exit signs as required Location:Exit signs
in Section 1013.6.3.The system shall be capable of powering Comments:All exit signs shall be tested and repaired if non
the required load for a duration of not less than 90 minutes. functional,provide documentation of all signage working properly to
inspector including signed and dated.
Fire Alarm System
Status Code Description
Fail Chapter 14-Inspection,testing,and maintenance
OFire alarm system tested at least annually by licensed Comments:Deficiencies noted in contractor report(Telgian Corp.)
contractor shall be corrected and repair report uploaded to Compliance Engine.
See attachment of deficiencies.
im
Fire Sprinkler System
S::os Code Description
Fail 903.3.3-Obstructed locations.
Automatic sprinklers shall be installed with regard to Location:Above pharmacy pick-up window
obstructions that will delay activation or obstruct the water Comments:Remove dust and debris from sprinkler head.
distribution pattern and shall be in accordance with the
applicable automatic sprinkler system standard that is being
used.Automatic sprinklers shall be installed in or under
covered kiosks,displays,booths,concession stands or
equipment that exceeds 4 feet(1219 mm)in width.Not less
than a 3-foot(914 mm)clearance shall be maintained between
automatic sprinklers and the top of piles of combustible
fibers.Exception:Kitchen equipment under exhaust hoods
protected with a fire-extinguishing system in accordance with
Section 904.
GENERATED ON 4/29/26, 7:52 AN 2 OF 4
Electrical Safety
Status Code Description
Fail 603.2.2-Unapproved conditionsOpen electrical terminations.
Ox Open junction boxes and open-wiring splices shall be Location:Above pharmacy drive thru window(exterior)
prohibited.Approved covers shall be provided for all switch Comments:Provide proper cover to electrical box exposing wires.
and electrical outlet boxes.
S
Portable Fire Extingusihers
Status Code Description
Fail 906.6-Unobstructed and unobscured.
OPortable fire extinguishers shall not be obstructed or Location:Pharmacy
obscured from view.In rooms or areas in which visual Comments:Remove ladder obstructing access to extinguisher
obstruction cannot be completely avoided,means shall be
provided to indicate the locations of extinguishers.
Fail 906.6-Unobstructed and unobscured.
Portable fire extinguishers shall not be obstructed or Location:Storage hallway near exit
obscured from view.In rooms or areas in which visual Comments:Remove storage obstructing ready access to fire
obstruction cannot be completely avoided,means shall be
extinguisher.Maintain proper clearance at all times.
provided to indicate the locations of extinguishers.
GENERATED ON 4/29/26, 7:52 AM 3 OF 4
Po Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $80.00
Invoice Number Check Number Transaction Number
NIA NIA NIA
GENERATED ON 4/29/26, 7:52 AM 4 OF 4
WA r INVOICE DATE DUE DATE INVOICE# TOTAL DUE
O 4''f►
04/30/2026 06/05/2026 2026-00000452 $80.00
/A O
• 1 'III II I I. •
* 0
Customer#: 13307 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
WALGREENS DRUG STORE 715 Mulberry St
111 W RIDGEWAY AV WATERLOO, IA 50703
WATERLOO, IA 50701
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION-111 W. RIDGEWAY AVE- FOR BILLING INQUIRY: (319)291-4323
04/28/2026
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
13307 04/30/2026 06/05/2026 2026-00000452 $80.00
Less Prepayment $0.00
Total Due $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.