ffg Inspection Report 425 E.3rd Street
4,E HE', Waigreens - 3910 University AVE, BLDG 3910 University Ave, Waterloo IA 50701
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
04/28/2026 Annual Inspection (1Yr) 17941
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA NIA
Other Inspectors
N/A
SUMMARY OF INSPECTION
045 Cog 21
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN
05/27/2026
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 04/29/2026 @ 08:12
• $80 annual inspection fee
BRAD BALDWIN - 04/29/2026 @ 08:12
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org -Work: 319-291-4319 (#5) -Cell: 319-230-1224
BRAD BALDWIN - 04/29/2026 @ 08:12
• Provide corrections to avoid progressive re-inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN -04/29/2026 @ 08:12
• If all corrections are made before the scheduled re-inspection date, you can call to set up an earlier re-inspection. Normal operating hours for
inspections & re-inspections are Monday - Friday, 9:00 a.m. -4:00 p.m. *****Re inspection fees may be assessed for subsequent re-inspections. Re-
inspection fees start at$100, then $150, and $200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Carey Bass 2025 Date: BRAD BALDWIN 04/29/2026
CHECKLISTS
GENERATED ON 4/29/26, 12:43 PM
1 OF 6
Means of Egress
Starus Code Description
Fail 1010.1.3-Door opening force Forces to unlatch and open
doors. Location:Back storage area(west exit)
The force for pushing or pulling open interior swinging Comments:Repair or replace egress exit door that failed to open with
egress doors,other than fire doors,shall not exceed 5 less than 15lbs of force.Replacement of door requires building
pounds(22 N).These forces do not apply to the force permit and inspection obtained.
required to retract latch bolts or disengage other devices that
hold the door in a closed position.For other swinging doors,
as well as sliding and folding doors,the door latch shall
release when subjected to a 15-pound(67 N)force.The door
shall be set in motion when subjected to a 30-pound(133 N)
force.The door shall swing to a full-open position when
subjected to a 15-pound(67 N)force.The forces to unlatch
doors shall comply with the following:1.Where door
hardware operates by push or pull,the operational force to
unlatch the door shall not exceed 15 pounds(66.7 N).2.Where
door hardware operates by rotation,the operational force to
unlatch the door shall not exceed 28 inch-pounds(315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated,other than doors required to be fire rated,the force
for pushing or pulling open the door shall not exceed 5
pounds(22 N).2.For other swinging doors,sliding doors or
folding doors,and doors required to be fire rated,the door
shall require not more than a 30-pound(133 N)force to be set
in motion and shall move to a full-open position when
subjected to not more than a 15-pound(67 N)force.
Fail 1010.1.3-Door opening force Forces to unlatch and open
doors. Location:North exit near bathrooms
The force for pushing or pulling open interior swinging Comments:Repair or replace egress exit door that failed to open with
egress doors,other than fire doors,shall not exceed 5 less than 15lbs of force.Replacement of door requires building
pounds(22 N).These forces do not apply to the force permit and inspection obtained.
required to retract latch bolts or disengage other devices that
hold the door in a closed position.For other swinging doors,
as well as sliding and folding doors,the door latch shall
release when subjected to a 15-pound(67 N)force.The door
shall be set in motion when subjected to a 30-pound(133 N)
force.The door shall swing to a full-open position when
subjected to a 15-pound(67 N)force.The forces to unlatch
doors shall comply with the following:1.Where door
hardware operates by push or pull,the operational force to
unlatch the door shall not exceed 15 pounds(66.7 N).2.Where
door hardware operates by rotation,the operational force to
unlatch the door shall not exceed 28 inch-pounds(315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated,other than doors required to be fire rated,the force
for pushing or pulling open the door shall not exceed 5
pounds(22 N).2.For other swinging doors,sliding doors or
folding doors,and doors required to be fire rated,the door
shall require not more than a 30-pound(133 N)force to be set
in motion and shall move to a full-open position when
subjected to not more than a 15-pound(67 N)force.
GENERATED ON 4/29/26, 12:43 PM 2 OF 6
Emergency Equipment
Status Code Description
Fail 1203.2.15-Means of egress illumination.
0 Emergency power shall be provided for means of egress Location:Emergency egress lighting
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:All egress lights shall be tested and repaired if
nonfunctional,provide documentation of all lighting working properly
to inspector including signed and dated.
Fail 1203.2.6-Exit signs.
Ux Emergency power shall be provided for exit signs as required Location:All exit signage
in Section 1013.6.3.The system shall be capable of powering Comments:All exit signs shall be tested and repaired if
the required load for a duration of not less than 90 minutes. nonfunctional,provide documentation of all signage working
properly to inspector including signed and dated.
Fire Alarm System
Status Code Description
Fail Chapter 14-Inspection,testing,and maintenance
0 Fire alarm system tested at least annually by licensed Location:Fire alarm
contractor Comments:Deficiencies noted in contractor report(Telgian Corp.)
shall be corrected and repair report uploaded to Compliance Engine.
See attachment of deficiencies.
Fire Sprinkler System
Status Code Description
Fail 903.3.3-Obstructed locations.
0 Automatic sprinklers shall be installed with regard to Location:Above register check out
obstructions that will delay activation or obstruct the water Comments:Clean dust and debris from sprinkler heads(2)above
distribution pattern and shall be in accordance with the register.
applicable automatic sprinkler system standard that is being
used.Automatic sprinklers shall be installed in or under
covered kiosks,displays,booths,concession stands or
equipment that exceeds 4 feet(1219 mm)in width.Not less
than a 3-foot(914 mm)clearance shall be maintained between
automatic sprinklers and the top of piles of combustible
fibers.Exception:Kitchen equipment under exhaust hoods
protected with a fire-extinguishing system in accordance with
Section 904.
GENERATED ON 4/29/26, 12:43 PM 3 OF 6
Electrical Safety
Code Description
Fail 603.2-Abatement of unsafe conditions and electrical
hazards. Location:West side of building(exterior)
Identified electrical hazards shall be abated.Identified Comments:Licensed electrician shall make necessary repairs to
hazardous electrical conditions in permanent wiring shall be damaged piping.
brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
f
j j..
.Y:
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Pharmacy
for permanent wiring and shall be listed and labeled in Comments:Remove extension cord plugged to dehumidifier.
accordance with UL 817.Extension cords and flexible Appliance shall plug directly to permanent wall outlet.Adding new
cordsshall not be affixed to structures,extended through outlet requires licensed electrician obtaining permit and inspection.
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
GENERATED ON 4/29/26, 12:43 PM 4 OF 6
Additional Codes
staws Code Description
Fail 912.2.2-Existing buildings.
On existing buildings,wherever the fire department Location:Front exterior of building(South)
connection is not visible to approaching fire apparatus,the Comments:Permanent"FDC"sign including arrow pointing towards
fire department connection shall be indicated by an approved west side of building shall be installed in an approved location.
sign mounted on the street front or on the side of the Laminated paper will not be accepted.See attachment for example of
building.Such sign shall have the letters"FDC"not less than
signage.
6 inches(152 mm)high and words in letters not less than 2
inches(51 mm)high or an arrow to indicate the location.
Such signs shall be subject to the approval of the fire code
official.
FDC
GENERATED ON 4/29/26, 12:43 PM 5 OF 6
Po Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
N/A $80.00
Invoice Number Check Number Transaction Number
N/A NIA NIA
GENERATED ON 4/29/26, 12:43 PM 6 OF 6
OF W q T� INVOICE DATE DUE DATE INVOICE ft TOTAL DUE
4)1, 04/30/2026 06/05/2026 2026-00000454 $80.00
• ...I."I '1 III'III*� •
a ,"IF 0
4' "tvil
Customer#: 21006 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
WALGREENS DRUG STORE#3590 715 Mulberry St
3910 UNIVERSITY AV WATERLOO, IA 50703
WATERLOO, IA 50701
Amount Enclosed.
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION-3910 UNIVERSITY AVE- FOR BILLING INQUIRY: (319)291-4323
04/28/2026-
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE' DUE DATE INVOICE# CHARGES
21006 04/30/2026 06/05/2026 2026-00000454 $80.00
Less Prepayment $0.00
Total Due—> $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.