HomeMy WebLinkAbout1005 BLACK HAWK ROAD-BLACK HAWK TENNIS CLUB Waterloo Fire Rescue
sPIN Inspection Report 425 E.3rd Street
4240 Black Hawk Tennis Club - 1005 Black Hawk RD, BLDG 1005 Black Hawk Rd,
Waterloo IA 50701 -4 100—
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
05/04/2026 Annual Inspection (1Yr) 16944
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
035 0'' 13 ® 31
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN 05126/2026
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 05/05/2026 @ 09:43
• $100 annual inspection fee
BRAD BALDWIN - 05/05/2026 @ 09:43
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org -Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 05/05/2026 @ 09:43
• Provide corrections to avoid progressive re-inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 05/05/2026 @ 09:43
• If all corrections are made before the scheduled re-inspection date, you can call to set up an earlier re-inspection. Normal operating hours for
inspections & re-inspections are Monday - Friday, 9:00 a.m. -4:00 p.m. *****Re inspection fees may be assessed for subsequent re-inspections. Re-
inspection fees start at $100, then $150, and $200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Chris Sagers Date: BRAD BALDWIN 05105/2026
CHECKLISTS
GENERATED ON 5/5/26, 11:11 AM 1 OF /
•
Means of Egress
Status Code Description
Fail 1010.1.3-Door opening force Forces to unlatch and open
Odoors. Location:Court 4(east end)
The force for pushing or pulling open interior swinging Comments:Repair or replace exit door that failed to open easily,
egress doors,other than fire doors,shall not exceed 5 replacing door requires permit and inspection obtained.
pounds(22 N).These forces do not apply to the force
required to retract latch bolts or disengage other devices that
hold the door in a closed position.For other swinging doors,
as well as sliding and folding doors,the door latch shall
release when subjected to a 15-pound(67 N)force.The door
shall be set in motion when subjected to a 30-pound(133 N)
force.The door shall swing to a full-open position when
subjected to a 15-pound(67 N)force.The forces to unlatch
doors shall comply with the following:1.Where door
hardware operates by push or pull,the operational force to
unlatch the door shall not exceed 15 pounds(66.7 N).2.Where
door hardware operates by rotation,the operational force to
unlatch the door shall not exceed 28 inch-pounds(315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated,other than doors required to be fire rated,the force
for pushing or pulling open the door shall not exceed 5
pounds(22 N).2.For other swinging doors,sliding doors or
folding doors,and doors required to be fire rated,the door
shall require not more than a 30-pound(133 N)force to be set
in motion and shall move to a full-open position when
subjected to not more than a 15-pound(67 N)force.
Fail 1010.1.3-Door opening force Forces to unlatch and open
Odoors. Location:Court 2(east end)
The force for pushing or pulling open interior swinging Comments:Repair or replace exit door that failed to open at all,
egress doors,other than fire doors,shall not exceed 5 replacing door requires permit and inspection obtained.
pounds(22 N).These forces do not apply to the force
required to retract latch bolts or disengage other devices that
hold the door in a closed position.For other swinging doors,
as well as sliding and folding doors,the door latch shall
release when subjected to a 15-pound(67 N)force.The door
shall be set in motion when subjected to a 30-pound(133 N)
force.The door shall swing to a full-open position when
subjected to a 15-pound(67 N)force.The forces to unlatch
doors shall comply with the following:1.Where door
hardware operates by push or pull,the operational force to
unlatch the door shall not exceed 15 pounds(66.7 N).2.Where
door hardware operates by rotation,the operational force to
unlatch the door shall not exceed 28 inch-pounds(315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated,other than doors required to be fire rated,the force
for pushing or pulling open the door shall not exceed 5
pounds(22 N).2.For other swinging doors,sliding doors or
folding doors,and doors required to be fire rated,the door
shall require not more than a 30-pound(133 N)force to be set
in motion and shall move to a full-open position when
subjected to not more than a 15-pound(67 N)force.
Fail 1032.2-Reliability.
ORequired exit accesses,exits and exit discharges shall be Location:Court 5
continuously maintained free from obstructions or Comments:Remove extension ladder laying in exit path in front of
impediments to full instant use in the case of fire or other door
emergency where the building area served by the means of
egress is occupied.An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
GENERATED ON 5/5/26, 11:11 AN 2 OF 7
Additional Codes
Status Code Description
Fail 1010.2.4-Locks and latches.
Locks and latches shall be permitted to prevent operation of Location:Main exit doors
doors where any of the following exist:1.Places of detention Comments:Permanent approved signage shall be installed to doors
or restraint.2.In Group I-1,Condition 2 and Group 1-2
(2)stating,"THIS DOOR SHALL REMAIN UNLOCKED DURING
occupancies where the clinical needs of persons receiving BUSINESS HOURS"
care require containment or where persons receiving care
pose a security threat,provided that all clinical staff can
readily unlock doors at all times,and all such locks are keyed
to keys carried by all clinical staff at all times or all clinical
staff have the codes or other means necessary to operate the
locks at all times.2.3.In buildings in occupancy Group A
having an occupant load of 300 or less,Groups B,F,M and S,
and in places of religious worship,the main door or doors are
permitted to be equipped with key-operated locking devices
from the egress side provided:2.1.3.1.The locking device is
readily distinguishable as locked.2.2.3.2.A readily visible
durable sign is posted on the egress side on or adjacent to
the door stating:"THIS DOOR TO REMAIN UNLOCKED WHEN
THIS SPACE IS OCCUPIED."The sign shall be in letters 1 inch
(25 mm)high on a contrasting background.2.3.3.3.The use
of the key-operated locking device is revocable by the fire
code official for due cause.3.4.Where egress doors are used
in pairs,approved automatic flush bolts shall be permitted to
be used,provided that the door leaf having the automatic
flush bolts does not have a doorknob or surface-mounted
hardware.4.5.Doors from individual dwelling or sleeping
units of Group R occupancies having an occupant load of 10
or less are permitted to be equipped with a night latch,dead
bolt or security chain,provided such devices are openable
from the inside without the use of a key or tool.5.6.Fire
doors after the minimum elevated temperature has disabled
the unlatching mechanism in accordance with listed fire door
test procedures.6.7.Doors serving roofs not intended to be
occupied shall be permitted to be locked,preventing entry to
the building from the roof.8.Other than egress courts,where
occupants must egress from an exterior space through the
building for means of egress,exit access doors shall be
permitted to be equipped with an approved locking device
where installed and operated in accordance with all of the
following:8.1.The maximum occupant load shall be posted
where required by Section 1004.9.Such sign shall be
permanently affixed inside the building and shall be posted in
a conspicuous space near all the exit access doorways.8.2.A
weatherproof telephone or two-way communication system
installed in accordance with Sections 1009.8.1 and 1009.8.2
shall be located adjacent to not less than one required exit
access door on the exterior side.8.3.The egress door locking
device is readily distinguishable as locked and shall be a key-
operated locking device.8.4.A clear window or glazed door
opening,not less than 5 square feet(0.46 m2)in area,shall
be provided at each exit access door to determine if there are
occupants using the outdoor area.8.5.A readily visible
durable sign shall be posted on the interior side on or
adjacent to each locked required exit access door serving the
exterior area stating:"THIS DOOR TO REMAIN UNLOCKED
WHEN THE OUTDOOR AREA IS OCCUPIED."The letters on
the sign shall be not less than 1 inch(25.4 mm)high on a
contrasting background.8.6.The occupant load of the
occupied exterior area shall not exceed 300 occupants in
accordance with Section 1004.9.Locking devices are
permitted on doors to balconies,decks or other exterior
spaces serving individual dwelling or sleeping units.
10.Locking devices are permitted on doors to balconies,
decks or other exterior spaces of 250 square feet(23.23
m2)or less,serving a private office space.
GENERATED ON 5/5/26, 11:11 AN 3 OF
Fail 610.1.2 - Maintenance.
The lint trap, mechanical and heating components, and the Location: Clothes dryer vent
exhaust duct system of a clothes dryer shall be maintained in Comments: Provide documentation of cleaning of dryer vent from
accordance with the manufacturer's operating appliance to the outside of the building with signature and date.
instructions to prevent the accumulation of lint or debris that Email documentation to fire inspector.
prevents the exhaust of air and products of combustion.
Emergency Equipment
Status Code Description
Fail 1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress Location: Court 2 (east end)
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments: Egress light on exit sign damaged (hanging by wires)
shall be repaired or replaced
GENERATED ON 5/5/26, 11:11 AM 4 OF 7
Electrical Safety
Status Code Description
Fail 603.2-Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated.Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Fail 603.2.2-Unapproved conditionsOpen electrical terminations.
OOpen junction boxes and open-wiring splices shall be Location:Court 4(west end)
prohibited.Approved covers shall be provided for all switch Comments:Provide missing cover to box at wall/ceiling intersection
and electrical outlet boxes.
Fail 603.2.2-Unapproved conditionsOpen electrical terminations.
0 Open junction boxes and open-wiring splices shall be Location:Outdoor tennis building
prohibited.Approved covers shall be provided for all switch Comments:Light fixture near women's bathroom shall be repaired to
and electrical outlet boxes. avoid hanging by wires and open to exterior elements
4 R> IV
ilk
r tp, �, myN
�K
9 E
em
$'12116 v r
Fail 603.2.2-Unapproved conditionsOpen electrical terminations.
OOpen junction boxes and open-wiring splices shall be Location:Men's locker room entrance near Court 1
prohibited.Approved covers shall be provided for all switch Comments:Open wire connection above door missing cover shall be
and electrical outlet boxes. corrected.If is exit sign or egress light,repair to proper working
order
GENERATED ON 5/5/26, 11:11 AM 5 OF 7
Portable Fire Extingusihers
Status Code Description
Fail 906.2-General requirements.
Portable fire extinguishers shall be selected,installed and Comments:Annual service to all extinguishers due June 2026
maintained in accordance with this section and NFPA 10.
Exceptions:1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.In Group 13,portable fire
extinguishers shall be permitted to be located at staff
locations.
Fail 906.2-General requirements.
Portable fire extinguishers shall be selected,installed and Location:Outdoor tennis building and volleyball shack
maintained in accordance with this section and NFPA 10. Comments:Was not given access to inspect on 514126.Provide
Exceptions:1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5 inspector access to inspect on scheduled re-inspection or call to set
up separate time.
occupancies.2.Thirty-0ay inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.In Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.
Fail 906.7-Hangers and brackets.
Hand-held portable fire extinguishers,not housed in cabinets, Location:Court 2(west)
shall be installed on the hangers or brackets supplied. Comments:Extinguisher currently sitting on ground,bracket missing
Hangers or brackets shall be securely anchored to the from wall.Discussed moving extinguisher AND signage closer to
mounting surface in accordance with the manufacturer's post to protect from being bumped off the wall
installation instructions.
GENERATED ON 5/5/26, 11:11 NI 6 of 7
Po Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $100.00
Invoice Number Check Number Transaction Number
NIA NIA NIA
7 OF 7
GENERATED ON 5/5/26, 11:11 AM
OF WA rF INVOICE DATE DUE DATE INVOICE# TOTAL DUE
I. // 0 05/18/2026 06/23/2026 2026-00000461 $100.00
u .,aiv�••. !A o
4w •
O
SS1 d 11‘
Customer#: 4653 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
BLACK HAWK TENNIS CLUB 715 Mulberry St
PO BOX 26 WATERLOO, IA 50703
WATERLOO, IA 50704
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION - 1005 BLACK HAWK RD - FOR BILLING INQUIRY: (319)291-4323
05/04/2026
Description Total Price
INSPECTION 2,000 HH $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
4653 05/18/2026 06/23/2026 2026-00000461 $100.00
Less Prepayment $0.00
Total Due -* $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
OF W A . INVOICE DATE DUE DATE INVOICE# TOTAL DUE
to 05/20/2025 06/25/2025 2025-00000353 $100.00
•
. O
Customer#: 4653 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
BLACK HAWK TENNIS CLUB 715 Mulberry St
PO BOX 26 WATERLOO, IA 50703
WATERLOO, IA 50704
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION - 1005 BLACK HAWK RD- 5-5-25 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 20,000 $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
4653 05/20/2025 06/25/2025 2025-00000353 $100.00
Less Prepayment $0.00
Total Due—* $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.