HomeMy WebLinkAbout515 BROADWAY ST-KWIK STOP 4 Waterloo Fire Rescue
0 15 Inspection Report 425 E.3rd Street
« Kwik Stop 4-515 Broadway ST,BLDG 515 Broadway St,Waterloo IA 50703
INSPECTION DETAILS c70 95 3 4100—
Inspection Date Inspection Type Inspection Number
05108/2026 Annual Inspection(1Yr) ( REINSPECTION ) 16651-R2
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA N/A N/A
Other Inspectors
N/A
SUMMARY OF INSPECTION
0 0 6
Passed codes Failed codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN 06/0312026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-0411712026 @ 13:06
Withholding re-inspection fee due to some progress made 4117/26,complete corrections to avoid possible fees at following inspections
BRAD BALDWIN-0411712026 @ 13:06
$80 annual inspection fee
BRAD BALDWIN-0411712026 @ 13:06
Corrected during 3126/26 inspection:Removed 2 beverage fridges plugged to power strips and plugged directly to wall outlet.
BRAD BALDWIN-04/1712026 @ 13:06
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-0411712026(t 13:06
•Provide corrections to avoid progressive re-inspection fees beginning at S100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-0411712026 @ 13:06
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
BRAD BALDWIN-0511112026 @ 07:08
$100 re-inspection fee,failure to complete corrections on 518/26.Complete corrections to avoid possible fees at following inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
1 OF 6
GENERATED ON 5/11/26, 7:10 AM
Mohammad Sarwar Date:
___I!E :::1 <Z5l
CHECKLISTS
BRAD BALDWIN 05111/2026
l
GENERATED ON 5/11/26, 7:10 AN
2 OF 6
Reinspection
Status Code Description
Fail 1018.4-Aisle accessways in Group M.
OAn aisle accessway shall be provided on not less than one Location:Aisles
side of each element within the merchandise pad.The Comments:Aisles not maintained clear today,remove obstructions
minimum clear width for an aisle accessway not required to and maintain proper clearances at all times.
be accessible shall be 30 inches(762 mm).The required clear
width of the aisle accessway shall be measured perpendicular
to the elements and merchandise within the merchandise
pad.The 30-inch(762 mm)minimum clear width shall be
maintained to provide a path to an adjacent aisle or aisle
accessway.The common path of egress travel shall not
exceed 30 feet(9144 mm)from any point in the merchandise
pad.Exception:For areas serving not more than 50
occupants,the common path of egress travel shall not
exceed 75 feet(22 860 mm).
Fail 102.4-Application of building code.
0 The design and construction of new structures shall comply Location:Air Conditioner
with the International Building Code,and any alterations, Comments:Licensed mechanical contractor shall obtain permit and
additions,changes in use or changes in structures required inspection for sir conditioner replaced without permit.
by this code,which are within the scope of the International
Building Code,shall be made in accordance therewith.
Fail 102.4-Application of building code.
UThe design and construction of new structures shall comply Location:Furnace
with the International Building Code,and any alterations, Comments:Licensed mechanical contractor shall obtain permit and
additions,changes in use or changes in structures required inspection for furnace replaced without permit.
by this code,which are within the scope of the International
Building Code,shall be made in accordance therewith.
Fail 1032.2-Reliability.
Required exit accesses,exits and exit discharges shall be Location:Back exit
continuously maintained free from obstructions or Comments:Remove all storage(including boxes)in path to exit,
impediments to full instant use in the case of fire or other maintain clear path of egress at all times
emergency where the building area served by the means of
egress is occupied.An exit or exit passageway shall not be Additional comments:Obstructions against door on exterior of
used for any purpose that interferes with a means of egress. building also noted today 518126.Remove immediately.
y � �a
„tom
iii 411P- 1
s I
GENERATED ON 5/11/26, 7:10 AM 3 OF 6
Fail 603.4-Working space and clearancesclearance.
A working space of not Working space around electrical Location:Electric panel near back exit
equipment shall be provided in accordance with Section Comments:Remove storage within 36 inches,maintain proper
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or clearances at all times.
less,and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts.The minimum required working space
shall be not less than 30 inches(762 mm)in width,36 inches
(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the
electrical service equipment is wider than 30 inches(762
mm),the minimum working space shall be not less than the
width of the equipment.Storage of materials shall not be
located within the designated working space.Exceptions:1.
Where other dimensions are required or allowed by NFPA 70.
2.Access openings into attics or under-floor areas that
provide a minimum clear opening of 22 inches(559 mm)by 30
inches(762 mm).
■ •
a
r.i i !I ..
, .
@' 4)
, ,,
., ,
! , ,,,,,„4,
,.. „„ ,,..,.
N.,..„.
'14 T1 ://fli
.
GENERATED ON 5/11/26, 7:10 AM 4 OF 6
Fail 603.5.3-Installation.
ORelocatable power tap cords shall not extend through walls, Location:Back storage area
ceilings,floors,under doors or floor coverings,or be subject Comments:Properly mount power strip to avoid hanging by wires.
to environmental or physical damage.
ima t
- �' 1
r,i
.....„ .
, ,„.......
...
,, J •
y 0
i 1,,,,, .
GENERATED ON 5/11/26, 7:10 AM 5 OF 6
o Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $100.00
Invoice Number Check Number Transaction Number
NIA NIA NIA
GENERATED ON 5/11/26, 7:10 AN 6 OF 6
OF WA PF INVOICE DATE DUE DATE INVOICE# TOTAL DUE
e 05/18/2026 06/23/2026 2026-00000472 $100.00
u / O
O
Customer#: 20953 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
KWIK STOP#4 715 Mulberry St
515 BROADWAY ST WATERLOO, IA 50703
WATERLOO, IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION - 515 BROADWAY ST- FOR BILLING INQUIRY: (319)291-4323
05/08/2026
Description Total Price
REINSPECTION 1 $100.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
20953 05/18/2026 06/23/2026 2026-00000472 $100.00
Less Prepayment $0.00
Total Due $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.