y ) Inspection Report 425 E. 3rd Street
LJ's Neighborhood Bar & Grill - 3550 Kim
Waterloo IA 50701 ball AV E, BLDG 3550 Kimball Ave, �
INSPECTION DETAILS 13 a 4 3
Inspection Date Inspection Type Inspection Number
05106/2026 Annual Inspection (1Yr) 16891
Lead Inspector Shift Station Unit
BRAD BALDWIN N/A N/A NIA
Other Inspectors
N/A
SUMMARY OF INSPECTION
044 � 5 ® 25
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319 05/29/2026
GENERAL NOTES
BRAD BALDWIN - 05/06/2026 @ 11:42
• $80 annual inspection fee
BRAD BALDWIN -05106/2026 @ 11:42
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org -Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 05/06/2026 @ 11:42
• Provide corrections to avoid progressive re-inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 0510612026 @ 11:42
• If all corrections are made before the scheduled re-inspection date, you can call to set up an earlier re-inspection. Normal operating hours for
inspections & re-inspections are Monday- Friday, 9:00 a.m. -4:00 p.m. *****Re inspection fees may be assessed for subsequent re-inspections. Re-
inspection fees start at $100, then $150, and $200 for all subsequent re-inspections.
BRAD BALDWIN - 05/0712026 @ 07:48
New outdoor seating shall comply with all egress exiting requirements. Work currently in progress
SIGNATURES
Contact signature Inspector signature
No signature :E11
Report completed post inspection
Kelsey Delp 2025 Date: BRAD BALDWIN 05107/2026
CHECKLISTS
GENERATED ON 5/7/26, 7:49 AM 1 OF 4
Additional Codes
Status Code Description
Fail 1010.2.4-Locks and latches.
Locks and latches shall be permitted to prevent operation of Location:NE glass exit door near bar and outdoor patio seating
doors where any of the following exist:1.Places of detention Comments:Permanent approved signage shall be installed to door
or restraint.2.In Group I-1,Condition 2 and Group 1-2 stating,"THIS DOOR SHALL REMAIN UNLOCKED DURING
occupancies where the clinical needs of persons receiving BUSINESS HOURS".
care require containment or where persons receiving care
pose a security threat,provided that all clinical staff can
readily unlock doors at all times,and all such locks are keyed
to keys carried by all clinical staff at all times or all clinical
staff have the codes or other means necessary to operate the
locks at all times.2.3.In buildings in occupancy Group A
having an occupant load of 300 or less,Groups B,F,M and S,
and in places of religious worship,the main door or doors are
permitted to be equipped with key-operated locking devices
from the egress side provided:2.1.3.1.The locking device is
readily distinguishable as locked.2.2.3.2.A readily visible
durable sign is posted on the egress side on or adjacent to
the door stating:"THIS DOOR TO REMAIN UNLOCKED WHEN
THIS SPACE IS OCCUPIED."The sign shall be in letters 1 inch
(25 mm)high on a contrasting background.2.3.3.3.The use
of the key-operated locking device is revocable by the fire
code official for due cause.3.4.Where egress doors are used
in pairs,approved automatic flush bolts shall be permitted to
be used,provided that the door leaf having the automatic
flush bolts does not have a doorknob or surface-mounted
hardware.4.5.Doors from individual dwelling or sleeping
units of Group R occupancies having an occupant load of 10
or less are permitted to be equipped with a night latch,dead
bolt or security chain,provided such devices are openable
from the inside without the use of a key or tool.5.6.Fire
doors after the minimum elevated temperature has disabled
the unlatching mechanism in accordance with listed fire door
test procedures.6.7.Doors serving roofs not intended to be
occupied shall be permitted to be locked,preventing entry to
the building from the roof.8.Other than egress courts,where
occupants must egress from an exterior space through the
building for means of egress,exit access doors shall be
permitted to be equipped with an approved locking device
where installed and operated in accordance with all of the
following:8.1.The maximum occupant load shall be posted
where required by Section 1004.9.Such sign shall be
permanently affixed inside the building and shall be posted in
a conspicuous space near all the exit access doorways.8.2.A
weatherproof telephone or two-way communication system
installed in accordance with Sections 1009.8.1 and 1009.8.2
shall be located adjacent to not less than one required exit
access door on the exterior side.8.3.The egress door locking
device is readily distinguishable as locked and shall be a key-
operated locking device.8.4.A clear window or glazed door
opening,not less than 5 square feet(0.46 m2)in area,shall
be provided at each exit access door to determine if there are
occupants using the outdoor area.8.5.A readily visible
durable sign shall be posted on the interior side on or
adjacent to each locked required exit access door serving the
exterior area stating:"THIS DOOR TO REMAIN UNLOCKED
WHEN THE OUTDOOR AREA IS OCCUPIED."The letters on
the sign shall be not less than 1 inch(25.4 mm)high on a
contrasting background.8.6.The occupant load of the
occupied exterior area shall not exceed 300 occupants in
accordance with Section 1004.9.Locking devices are
permitted on doors to balconies,decks or other exterior
spaces serving individual dwelling or sleeping units.
10.Locking devices are permitted on doors to balconies,
decks or other exterior spaces of 250 square feet(23.23
m2)or less,serving a private office space.
GENERATED ON 5/7/26, 7:49 AM 2 OF 4
Emergency Equipment
Status Code Description
Fail 1203.2.15-Means of egress illumination.
OEmergency power shall be provided for means of egress Location:Near bar-above"Blue Moon"sign
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Repair or replace egress light that failed to illuminate
during test
General Housekeeping
Status Code Description
Fail 304.3.1-Spontaneous ignition.
Ox Materials susceptible to spontaneous ignition,such as oily Location:Kitchen
rags,shall be stored in a listed disposal container.Contents Comments:Provide listed container to dispose of oily rags,see
of such containers shall be removed and disposed of daily. attachement
Commercial Cooking Hood Suppression System
Status Code Description
Fail 606.3.3.2-Grease accumulation.
Ox If during the inspection it is found that hoods,grease-removal Location:Kitchen hood filters
devices,fans,ducts or other appurtenances have an Comments:Clean hood filters and all excess of grease on and
accumulation of grease,such components shall be cleaned in surrounding cooking equipment.
accordance with ANSIIIKECA C10.
Fire Resistant Construction Maintenance
Status Code Description
Fail 704.1-Maintaining protection.
Where required when the building was originally constructed, Location:South dining area
materials and systems used to protect joints and voids in the Comments:Replace all missing ceiling tiles.
following locations shall be maintained.The materials and
systems shall be securely attached to or bonded to the
adjacent construction,without openings visible through the
construction.1.Joints in or between fire-resistance-rated
walls,floors or floorlceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall.4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall.5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall.6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall.7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly.Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed.Where the system design number is known,the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
GENERATED ON 5/7/26, 7:49 AM 3 OF 4
ro Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $80.00
Invoice Number Check Number Transaction Number
NIA NIA NIA
GENERATED ON 5/7/26, 7:49 AM 4 OF 4
OF W A T� INVOICE DATE DUE DATE INVOICE# TOTAL DUE
�/�0 05/18/2026 06/23/2026 2026-00000473 $80.00
.,iaa••.. Ian 0
• •
O
4S 1tt10N�
Customer#: 13263 Please Make Check Payable and Remit To:
City of Waterloo
ATTN:: City Clerk/Accounts Receivable
L J'S NEIGHBORHOOD GRILL& BAR 715 Mulberry St
3550 KIMBALL AV WATERLOO, IA 50703
WATERLOO, IA 50702
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION - 3550 KIMBALL AVE- FOR BILLING INQUIRY: (319)291-4323
05/06/2026
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
13263 05/18/2026 06/23/2026 2026-00000473 $80.00
Less Prepayment $0.00
Total Due-+ $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.