Inspection
�6 Ins p Report 425 E.3rd Street
iTiOo Main Administration Office - 2600 E Shaulis Rd, BLDG Main Administration Office,
Waterloo IA 50701
INSPECTION DETAILS
inspection Date Inspection Type Inspection Number
04/21/2026 Annual Inspection (1Yr) 17272
Lead Inspector S!, + Station Unit
BRAD BALDWIN NIA NIA NIA
Other Inspectors
BROCK WELIVER
SUMMARY OF INSPECTION
� 46 a7 Q23
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN
05/29/2026
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 04130/2026 @ 15:47
All buildings inspected are on this report except Whale Bone, Maintenance Shop, Volkanu, Thirsty Voyager and Totora Market which have individual
reports due to the fire safety systems installed in them
BRAD BALDWIN - 04130/2026 @ 15:47
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org -Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 04/30/2026 @ 15:47
• Provide corrections to avoid progressive re-inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 04130/2026 @ 15:48
• If all corrections are made before the scheduled re-inspection date, you can call to set up an earlier re-inspection. Normal operating hours for
inspections & re-inspections are Monday - Friday, 9:00 a.m. -4:00 p.m. *****Re inspection fees may be assessed for subsequent re-inspections. Re-
inspection fees start at $100, then $150, and $200 for all subsequent re-inspections.
BRAD BALDWIN - 05101/2026 @ 07:24
$610 annual inspection fee for entire property.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Eric Bertch Date: BRAD BALDWIN 05/0112026
CHECKLISTS
GENERATED ON 5/1/26, 7:54 AM 1 OF 4
Additional Codes
S:a'us Code Description
Fail 102.4-Application of building code.
The design and construction of new structures shall comply Location:New roller coaster building
with the International Building Code,and any alterations, Comments:Obtain all required inspections regarding permit for roller
additions,changes in use or changes in structures required coaster building.No passed final inspection on record as of 511126.
by this code,which are within the scope of the International
Building Code,shall be made in accordance therewith.
Fail 610.1.2-Maintenance.
The lint trap,mechanical and heating components,and the Location:Main office clothes dryer
exhaust duct system of a clothes dryer shall be maintained in Comments:Provide documentation of cleaning of dryer vent from
accordance with the manufacturer's operating appliance to the exterior of the building with signature and date.
instructions to prevent the accumulation of lint or debris that Email documentation to fire inspector.
prevents the exhaust of air and products of combustion.
Emergency Equipment
Code Description
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:Emergency egress lighting in all buildings except Whale
illumination in accordance with Sections 1008.3 and 1104.5.1. Bone,Maintenance Warehouse,Totara,Volkanu and Thirsty Voyager
Comments:All emergency egress lighting shall be tested and
repaired if nonfunctional,provide documentation of all lighting
working properly to inspector including signed and dated.
Fail 1203.2.6-Exit signs.
Emergency power shall be provided for exit signs as required Location:Exit signage in all buildings except Whale Bone,
in Section 1013.6.3.The system shall be capable of powering Maintenance Warehouse,Totara,Volkanu and Thirsty Voyager
the required load for a duration of not less than 90 minutes. Comments:All exit signage shall be tested and repaired or replaced if
nonfunctional.Provide documentation of all exit signs working
properly including signature and date of responsible person.
Electrical Safety
Code Description
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Gift shop
for permanent wiring and shall be listed and labeled in Comments:Remove green extension cord below thermostat.
accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
GENERATED ON 5/1/26, 7:54 AM 2 OF 4
Portable Fire Extingusihers
Status CodF Desc ipt,0.)
Fail 906.2-General requirements.
OPortable fire extinguishers shall be selected,installed and Location:All ride staff kiosks
maintained in accordance with this section and NFPA 10. Comments:Provide extinguishers annually serviced in required
Exceptions:1.The distance of travel to reach an extinguisher locations.
shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.In Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.
Fail 906.2-General requirements.
OPortable fire extinguishers shall be selected,installed and Location:Nopuko Ride-main electric room
maintained in accordance with this section and NFPA 10. Comments:Provide annually serviced fire extinguisher in required
Exceptions:1.The distance of travel to reach an extinguisher location
shall not apply to the spectator seating portions of Group A-5
occupancies,2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.In Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.
GENERATED ON 5/1/26, 7:54 AM 3 OF 4
law
E'® Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $610.00
Invoice Number Check Number Transaction Number
NIA NIA NIA
GENERATED ON 5/1/26, 7:54 AM 4 OF 4
W A r INVOICE DATE DUE DATE INVOICE# TOTAL DUE
O t�
i " 11'� 05/18/2026 06/23/2026 2026-00000474 $610.00
uAim O
6
Customer#: 24708 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
LOST ISLAND THEME PARK 715 Mulberry St
2600 E SHAULIS RD WATERLOO, IA 50703
WATERLOO, IA 50701
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION - 2600 E SHAULIS RD- FOR BILLING INQUIRY: (319)291-4323
04/21/2026
Description Total Price
INSPECTION 100,000 $600.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
24708 05/18/2026 06/23/2026 2026-00000474 $610.00
Less Prepayment $0.00
Total Due-- $610.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.