HomeMy WebLinkAbout1955 LOCKE AVENUE-MAJESTIC MOON �p1Eq(� Waterloo Fire Rescue
t a Inspection Report
4 425 E.3rd Street
qAE'.G Majestic Moon - 1955 Locke AVE, BLDG 1955 Locke Ave, Waterloo IA 50702
INSPECTION DETAILSqg:(31
Inspection Date Inspection Type Inspection Number
0510512026 Annual Inspection (1Yr) 17041
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
041 ® 13 Q26
Passed codes Failed codes N/A codes
NEXT STEPS
directquestions aboutyour Inspection to: Reinspection Date
Please p p
BRAD BALDWIN 0610312026
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 05/06/2026 @ 08:09
• $80 annual inspection fee
BRAD BALDWIN - 05106/2026 @ 08:09
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org -Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN -05106/2026 @ 08:10
• Provide corrections to avoid progressive re-inspection fees beginning at$100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 05106/2026 @ 08:10
• If all corrections are made before the scheduled re-inspection date, you can call to set up an earlier re-inspection. Normal operating hours for
inspections & re-inspections are Monday - Friday, 9:00 a.m. -4:00 p.m. *****Re inspection fees may be assessed for subsequent re-inspections. Re-
inspection fees start at $100, then $150, and $200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Lorraine Price Date: BRAD BALDWIN 05/06/2026
CHECKLISTS
1 OF 6
GENERATED ON 5/6/26, 8:40 AM
Means of Egress
Status Code Description
Fail 1010.2.5-Bolt locks.
Manually operated flush bolts or surface bolts are not Location:Lower level-hallway door near mechanical room
permitted.Exceptions:l.On doors not required for egress in Comments:Remove slide-bolt lock on door part of egress exit path.
individual dwelling units or sleeping units.2.Where a pair of
doors serves a storage or equipment room,manually
operated edge-or surface-mounted bolts are permitted on the
inactive leaf.3.Where a pair of doors serves an occupant load
of less than 50 persons in a Group B,F or S occupancy,
manually operated edge-or surface-mounted bolts are
permitted on the inactive leaf.The inactive leaf shall not
contain doorknobs,panic bars or similar operating hardware.
4.Where a pair of doors serves a Group B,F or S occupancy,
manually operated edge-or surface-mounted bolts are
permitted on the inactive leaf provided that such inactive leaf
is not needed to meet egress capacity requirements and the
building is equipped throughout with an automatic sprinkler
system in accordance with Section 903.3.1.1.The inactive leaf
shall not contain doorknobs,panic bars or similar operating
hardware.5.Where a pair of doors serves patient care rooms
in Group 1-2 occupancies,self-latching edge-or surface-
mounted bolts are permitted on the inactive leaf provided that
the inactive leaf is not needed to meet egress capacity
requirements and the inactive leaf shall not contain
doorknobs,panic bars or similar operating hardware.
GENERATED ON 5/6/26, 8:40 AM 2 OF 6
Additional Codes
S:anus Code
Description
Fail 102.4-Application of building code.
The design and construction of new structures shall comply Location:Lower level mechanical room
with the International Building Code,and any alterations, Comments:Licensed plumbing contractor shall obtain permit and
additions,changes in use or changes in structures required inspection of water heater installed without permit in January 2026
by this code,which are within the scope of the International
Building Code,shall be made in accordance therewith.
Fail 5303.5.3-Securing compressed gas containers,cylinders
and tanks. Location:Upper bar
Compressed gas containers,cylinders and tanks shall be Comments:Secure compressed gas cylinders with chain to avoid tip
secured to prevent falling caused by contact,vibration or over.
seismic activity.Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers,cylinders and tanks to a fixed object
with one or more restraints.2.Securing containers,cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers,cylinders or tanks.
3.Nesting of compressed gas containers,cylinders and tanks
at container filling or servicing facilities or in sellers'
warehouses not open to the public.Nesting shall be allowed
provided that the nested containers,cylinders or tanks,if
dislodged,do not obstruct the required means of egress.
4.Securing of compressed gas containers,cylinders and
tanks to or within a rack,framework,cabinet or similar
assembly designed for such use.Exception:Compressed gas
containers,cylinders and tanks in the process of
examination,filling,transport or servicing.
Fail 603.1-General.
Electrical equipment,wiring and systems required by this Location:Lower bar"back room"
code or the International Building Code shall be installed, Comments:Remove chest freezer plugged to extension cord,
used and maintained in accordance with NFPA 70 and appliance shall plug directly to permanent wall outlet.If choose to
Sections 603.2 through 603.10. add new outlet,licensed electrical contractor shall obtain permits and
inspections.
Fail 603.1-General.
Electrical equipment,wiring and systems required by this Location:Lower bar"back room"
code or the International Building Code shall be installed, Comments:Remove ice machine plugged to power strip,appliance
used and maintained in accordance with NFPA 70 and shall plug directly to permanent wall outlet.If choose to add new
Sections 603.2 through 603.10. outlet,licensed electrical contractor shall obtain permits and
inspections.
Fail 603.1-General.
Electrical equipment,wiring and systems required by this Location:Lower level mechanical room
code or the International Building Code shall be installed, Comments:Remove freezer from plugged to extension cord and
used and maintained in accordance with NFPA 70 and power strip.Appliance shall plug directly to permanent wall outlet.If
Sections 603.2 through 603.10. choose to add new outlet,licensed electrical contractor shall obtain
permits and inspections.
GENERATED ON 5/6/26, 8:40 AM 3 OF 6
Emergency Equipment
Status Code Description
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:Lower exit facing Locke St
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Repair or replace egress lights on exit sign that failed to
illuminate during test
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:Lower Ballroom
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Repair or replace egress lights near mechanical room
that failed to illuminate during test
Electrical Safety
Status Code Description
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Lower bar
for permanent wiring and shall be listed and labeled in Comments:Remove extension cord to LED lights above bar.Would
accordance with UL 817.Extension cords and flexible approve to replace with properly supported
cordsshall not be affixed to structures,extended through PP p P p Y power strip with manual
reset switch for low wattage electronics only.Power strip shall plug
walls,ceilings or floors,or under doors or floor coverings, directly to wall outlet.
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Upper bar
for permanent wiring and shall be listed and labeled in Comments:Remove orange extension cord plugged to compressor
accordance with UL 817.Extension cords and flexible below bar.Compressor shall plug directly to permanent wall outlet.
cordsshall not be affixed to structures,extended through Adding new outlet requires licensed electrical contactor obtaining
walls,ceilings or floors,or under doors or floor coverings, permit and inspection
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Commercial Cooking Hood Suppression System
S:atos Code Description
Fail 606.3.3-Cleaning.
Hoods,grease-removal devices,fans,ducts and other Location:Kitchen exhaust hood
appurtenances shall be cleaned at intervals as required by Comments:Exhaust system cleaning 202 days past due as of 516126.
Sections 606.3.3.1 through 606.3.3.3. Provide cleaning and report to be uploaded to Compliance Engine
with any deficiencies corrected.
Fail 606.3.3.1-Inspection.
Hoods,grease-removal devices,fans,ducts and other Location:Kitchen exhaust suppression system
appurtenances shall be inspected at intervals specified in Comments:Provide suppression system inspection report with any
Table 606.3.3.1 or as approved by the fire code official. deficiencies corrected,Contractor must upload report to Compliance
Inspections shall be completed by qualified individuals. Engine.Currently 202 days past due as of 516126
GENERATED ON 5/8/26, 8:40 Mr 4 OF fi
Portable Fire Extingusihers
Staves Code Description
Fail 906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and Comments: Provide annual service to all extinguishers, last recorded
maintained in accordance with this section and NFPA 10. service April 2025
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
5 OF 6
GENERATED ON 5/6/26, 8:40 AM
po Statement of Fees
FEE
Invoice Date Date Paid Amount Paid
NIA $80.00
Invoice Number Check Number Transaction Number
NIA NIA NIA
GENERATED ON 5/6/26, 8:40 AM 6 OF 6
® W A pks INVOICE DATE DUE DATE INVOICE# TOTAL DUE
��O 05/18/2026 06/23/2026 2026-00000475 $80.00
Customer#: 22980 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
MAJESTIC MOON 715 Mulberry St
1955 LOCKE WATERLOO, IA 50703
WATERLOO, IA 50702
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION - 1955 LOCKE AVE - 05/05/2026 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE _ DUE DATE INVOICE# CHARGES
22980 05/18/2026 06/23/2026 2026-00000475 _ $80.00
Less Prepayment $0.00
Total Due-+ $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.