HomeMy WebLinkAbout2332 FALLS AVENUE-METRO 66 Waterloo Fire Rescue
Inspection Report 425 E.3rd Street
Metro 66 - 2332 Falls AVE, BLDG 2332 Falls Ave, Waterloo IA 50701
� av
INSPECTION DETAILS C)V f?3
Inspection Date Inspection Type j Inspection Number
0510412026 Annual Inspection (1Yr) 16950
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
G 35 03 Q37
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN 05126/2026
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 05/05/2026 @ 09:17
• $80 annual inspection fee
BRAD BALDWIN - 05/05/2026 @ 09:17
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org -Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN -05/05/2026 @ 09:18
• Provide corrections to avoid progressive re-inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 05/05/2026 @ 09:18
• If all corrections are made before the scheduled re-inspection date, you can call to set up an earlier re-inspection. Normal operating hours for
inspections & re-inspections are Monday - Friday, 9:00 a.m. -4:00 p.m. *****Re inspection fees may be assessed for subsequent re-inspections. Re-
inspection fees start at $100, then $150, and $200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
No signature 1
Report completed post inspection I
Sam Annis Date: BRAD BALDWIN 05/05/2026
CHECKLISTS
GENERATED ON 5/5/26, 9:27 AM 1 OF 4
Additional Codes
Status Code Description
Fail 1010.2.4-Locks and latches.
Locks and latches shall be permitted to prevent operation of Location:Front exit doors
doors where any of the following exist:1.Places of detention Comments:Permanent approved signage shall be installed to doors
or restraint.2.In Group I-1,Condition 2 and Group 1-2 stating,"THIS DOOR SHALL REMAIN UNLOCKED DURING
occupancies where the clinical needs of persons receiving BUSINESS HOURS"
care require containment or where persons receiving care
pose a security threat,provided that all clinical staff can
readily unlock doors at all times,and all such locks are keyed
to keys carried by all clinical staff at all times or all clinical
staff have the codes or other means necessary to operate the
locks at all times.2.3.In buildings in occupancy Group A
having an occupant load of 300 or less,Groups B,F,M and S,
and in places of religious worship,the main door or doors are
permitted to be equipped with key-operated locking devices
from the egress side provided:2.1.3.1.The locking device is
readily distinguishable as locked.2.2.3.2.A readily visible
durable sign is posted on the egress side on or adjacent to
the door stating:"THIS DOOR TO REMAIN UNLOCKED WHEN
THIS SPACE IS OCCUPIED."The sign shall be in letters 1 inch
(25 mm)high on a contrasting background.2.3.3.3.The use
of the key-operated locking device is revocable by the fire
code official for due cause.3.4.Where egress doors are used
in pairs,approved automatic flush bolts shall be permitted to
be used,provided that the door leaf having the automatic
flush bolts does not have a doorknob or surface-mounted
hardware.4.5.Doors from individual dwelling or sleeping
units of Group R occupancies having an occupant load of 10
or less are permitted to be equipped with a night latch,dead
bolt or security chain,provided such devices are openable
from the inside without the use of a key or tool.5.6.Fire
doors after the minimum elevated temperature has disabled
the unlatching mechanism in accordance with listed fire door
test procedures.6.7.Doors serving roofs not intended to be
occupied shall be permitted to be locked,preventing entry to
the building from the roof.8.Other than egress courts,where
occupants must egress from an exterior space through the
building for means of egress,exit access doors shall be
permitted to be equipped with an approved locking device
where installed and operated in accordance with all of the
following:8.1.The maximum occupant load shall be posted
where required by Section 1004.9.Such sign shall be
permanently affixed inside the building and shall be posted in
a conspicuous space near all the exit access doorways.8.2.A
weatherproof telephone or two-way communication system
installed in accordance with Sections 1009.8.1 and 1009.8.2
shall be located adjacent to not less than one required exit
access door on the exterior side.8.3.The egress door locking
device is readily distinguishable as locked and shall be a key-
operated locking device.8.4.A clear window or glazed door
opening,not less than 5 square feet(0.46 m2)in area,shall
be provided at each exit access door to determine if there are
occupants using the outdoor area.8.5.A readily visible
durable sign shall be posted on the interior side on or
adjacent to each locked required exit access door serving the
exterior area stating:"THIS DOOR TO REMAIN UNLOCKED
WHEN THE OUTDOOR AREA IS OCCUPIED."The letters on
the sign shall be not less than 1 inch(25.4 mm)high on a
contrasting background.8.6.The occupant load of the
occupied exterior area shall not exceed 300 occupants in
accordance with Section 1004.9.Locking devices are
permitted on doors to balconies,decks or other exterior
spaces serving individual dwelling or sleeping units.
10.Locking devices are permitted on doors to balconies,
decks or other exterior spaces of 250 square feet(23.23
m2)or less,serving a private office space.
GENERATED ON 5/5/26, 9:27 AM 2 OF 4
Fail 603.1-General.
Electrical equipment,wiring and systems required by this Location:Blue Bunny ice cream freezer
code or the International Building Code shall be installed, Comments:Remove freezer from plugged to power strip.Appliance
used and maintained in accordance with NFPA 70 and shall plug directly to permanent wall outlet.
Sections 603.2 through 603.10.
Portable Fire Extingusihers
Staves Code Description
Fail 906.2-General requirements.
Portable fire extinguishers shall be selected,installed and Comments:Provide annual service to all extinguishers,currently due
maintained in accordance with this section and NFPA 10. in May 2026.
Exceptions:1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.In Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.
GENERATED ON 5/5/26, 9:27 AM 3 OF 4
Fo Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $80.00
Invoice Number Check Number Transaction Number
NIA NIA NIA
GENERATED ON 5/5/26, 9:27 AM 4 OF 4
OF W A rF INVOICE DATE DUE DATE INVOICE# TOTAL DUE
,�N ( 05/18/2026 06/23/2026 2026-00000476 $80.00
U 4 O
O
3;1(14es-
S 7v11‘
Customer#: 20423 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
METRO MART#4 715 Mulberry St
2332 FALLS AV WATERLOO, IA 50703
WATERLOO, IA 50701
Amount Enclosed.
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION- 2332 FALLS AVE- 05/04/2026 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
20423 05/18/2026 06/23/2026 2026-00000476 $80.00
Less Prepayment $0.00
Total Due-* $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.