HomeMy WebLinkAbout2845 CROSSROADS BLVD.-PANCHEROS MEXICAN GRILL r
Waterloo Fire Rescue
A Inspection Report 425 E.3rd Street
<70 Pancheros Mexican Grill-2845 Crossroads BLVD,BLDG 2845 Crossroads Blvd, 00 --
Waterloo IA 50702
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
05/1412026 Annual Inspection(1Yr) L REINSPECTION] 7530-R2
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA N/A
Other Inspectors
NIA
SUMMARY OF INSPECTION
0 0 0 1 0 4
Passed codes Resolved violations Failed codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN 06111/2026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-04/16/2026 @ 13:01
Withholding re-inspection today 4/16/26,complete corrections to avoid further inspection fees
BRAD BALDWIN-0411612026 @ 13:01
•$80 annual inspection fee
BRAD BALDWIN-04/16/2026 @ 13:01
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-04/16/2026 @ 13:01
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*"*"*Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
BRAD BALDWIN-05/14/2026 @ 12:31
$100 re-inspection fee,failure to complete corrections.All repairs shall be completed to avoid possible fees at following inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completedeelpost stinspection
Josh Whiteman(2026) Date: BRAD BALDWIN 05114/2026
CHECKLISTS
1 OF 4
GENERATED ON 5/14/26, 12:32 PM
Reinspection
Status Code Description
Fail 1203.2.6-Exit signs.
Ox Emergency power shall be provided for exit signs as required Location:Back(North)exit
in Section 1013.6.3.The system shall be capable of powering
Comments:Repair or replace exit sign and egress lights combo that
the required load for a duration of not less than 90 minutes.
failed to illuminate during test.
Fail 304.3.1-Spontaneous ignition.
Materials susceptible to spontaneous ignition,such as oily Location:Kitchen
rags,shall be stored in a listed disposal container.Contents
Comments:Provide listed container to dispose of oily rags,see
of such containers shall be removed and disposed of daily.
attachment.
Additional comments:Metal trash can provided does not meet
requirements of:Listed grease rag dispensing container with self
closing lid.
Fail 606.3.3.1-Inspection.
rx-) Hoods,grease-removal devices,fans,ducts and other Location:Hood suppression system
appurtenances shall be inspected at intervals specified in
Table 606.3.3.1 or as approved by the fire code official. Comments:Provide suppression system inspection report with any
Inspections shall be com leted bydeficiencies corrected.Contractor must upload report to Compliance
p qualified individuals. Engine.Currently 545 days past due.Missing suppression nozzle
covers shall be replaced
GENERATED ON 5/14/26, 12:32 PM
2 OF 4
Fail 704.1-Maintaining protection.
Where required when the building was originally constructed, Location:Above walk-in fridge
materials and systems used to protect joints and voids in the Comments:Replace several missing ceiling tiles above walk-in
following locations shall be maintained.The materials and
systems shall be securely attached to or bonded to the
adjacent construction,without openings visible through the
construction.1.Joints in or between fire-resistance-rated
walls,floors or floor/ceiling assemblies and roof or
rooflceiling assemblies.2.Joints in smoke barriers.3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall.4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall.5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall.6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall.7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly.Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed.Where the system design number is known,the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
3 OF 4
GENERATED ON 5/14/26, 12:32 PM
El Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
N/A $100.00
Invoice Number Check Number Transaction Number
N/A N/A NIA
GENERATED ON 5/14/26, 12:32 PM 4 OF 4
O F W, rF INVOICE DATE DUE DATE INVOICE# TOTAL DUE
05/18/2026 06/23/2026 2026-00000480 $100.00
� O
S 7v1/‘
Customer#: 20755 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
PANCHERO'S MEXICAN GRILL 715 Mulberry St
2475 CORAL COURT WATERLOO, IA 50703
CORALVILLE, IA 52241
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION -2845 CROSSROADS BLVD - FOR BILLING INQUIRY: (319)291-4323
05/14/2026
Description Total Price
REINSPECTION 1 $100.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES _
20755 05/18/2026 06/23/2026 2026-00000480 $100.00
Less Prepayment $0.00
Total Due $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.