HomeMy WebLinkAboutCFO DEVELOPMENT, LLC e r0 lYile,/cloiTErt Lz-
73„ / (7e"
Waterloo Fire Rescue w /o J1 /4//
Cg101) Inspection Report Y� 425 E.3rd Street
120 W Wellington-120 W Wellington ST,Waterloo IA 50701-2508
INSPECTION DETAILS Jo� 4-1C0•
r'
Inspection Date Inspection Type Inspection Number
05/08/2026 Rental Inspection LREINSPECTION) 17112-R2
Lead Inspector h: station unit
Randy Girsch NIA NIA N/A
Other Inspectors
NIA 7�
SUMMARY OF INSPECTION �0S — I0L/
D0 017 LAIE. - 5
Passed codes Failed codes gat: _ ' bD
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
Randy Girsch 0610812026
randy.girsch@waterloo-ia.org
GENERAL NOTES
Randy Girsch-0511512026 @ 08:25
On Monday April 6th 2026 at 1223pm I send a text to Walter Peterson in reference to the reinspection of this property was due.I got no response.On
Friday May 1st at 327pm I emailed and advised a reinspection date now set due to the fact that I have not heard back from him.I set the inspection for
Friday May 8th at 2pm.I arrived and waited for quite a while and Mr.Peterson did not show up.A$100 no show fee will be applied to the owner.Due to the
fact that I was unable to see if the corrections were made a$50 fee will be applied.Also Mr.Peterson has been warned time and time again that he needs
to have this rentals registered.lie has refused to register any of them.A$100 fee was be applied to this bill as well for failure to register a rental property.
The total will be$250.I have set the reinspection dated for June 8th 2026 at 0900am.
Randy Girsch-0311012026 @ 15:35
Re-inspection date is as posted on the inspection report given,the rental unit's responsible person/s shall reach out prior to set time of that re-
inspection.If all corrections are made before the scheduled inspection,you can call to set up an earlier re-inspection.Please give the appropriate notices
to occupants of the unit/s.Owner or owner's agent must be present during inspections.Failure to schedule a time on the date given or failure to keep the
inspection will result in a$100 fee.*****Re inspection fees may be assessed for re-inspections.Re-inspection fees start at$50,then$150,and$250 for all
subsequent re inspections.All appropriate keys to gain entry to locked units shall be readily available during re-inspection.
Randy Girsch-0311012026 @ 15:35
As of this date this address has not been registered with the city as a rental property.A citation will be issued if not registered.
SIGNATURES
Contact signature Inspector signature
No signature '
Contact refused-Owner refused to show to inspection '-
/141
Walter Peterson-CFO Development Date: Randy Girsch 0511512026
CHECKLISTS
GENERATED ON 5/15/26, 8:32 AN 1 C= !S
Reinspection
Status Code Description
Fail 603.2 - Abatement of unsafe conditions and electrical
hazards. Location: Living Room
Identified electrical hazards shall be abated. Identified Comments: Light fixture globelcover on ceiling fan needs to be
hazardous electrical conditions in permanent wiring shall be secured
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Fail 603.2 - Abatement of unsafe conditions and electrical
Ohazards. Location: Kitchen
Identified electrical hazards shall be abated. Identified Comments: GfI outlet by sink has improper voltage. Needs to have
hazardous electrical conditions in permanent wiring shall be proper voltage and ability to be reset.
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Fail 603.2 - Abatement of unsafe conditions and electrical
hazards. Location: Bedroom #2
Identified electrical hazards shall be abated. Identified Comments: Outlet tested open ground. Need GFI or two plug outlet.
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Fail 603.2 - Abatement of unsafe conditions and electrical
hazards. Location: Bedroom #3
Identified electrical hazards shall be abated. Identified Comments: Electrical Outlet needs to be secured to the wall along
hazardous electrical conditions in permanent wiring shall be with the outlet plate secure to outlet
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Fail 603.2 - Abatement of unsafe conditions and electrical
hazards. Location: Bedroom #3
Identified electrical hazards shall be abated. Identified Comments: Electrical Outlet tested open ground. Needs to have GFI
hazardous electrical conditions in permanent wiring shall be outlet or just a 2 prong outlet.
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
GENERATED ON 5/15/26, 8:32 AM 2 OF 5
Fail 603.2-Abatement of unsafe conditions and electrical
hazards. Location:Bedroom#4
Identified electrical hazards shall be abated.Identified Comments:Electrical outlet has open ground.Needs to be replaced
hazardous electrical conditions in permanent wiring shall be with GFI outlet or 2 prong outlet.
brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Fail 907.2.11.2-Groups R-2,R-3,R-4 and I-1.
Single-or multiple-station smoke alarms shall be installed Location:Front Door Entry Way
and maintained in Groups R-2,R-3,R-4 and I-1 regardless of Comments:Smoke Detector missing from base
occupant load at all of the following locations:1.On the
ceiling or wall outside of each separate sleeping area in the
immediate vicinity of bedrooms.2.In each room used for
sleeping purposes.3.In each story within a dwelling unit,
including basements but not including crawl spaces and
uninhabitable attics.In dwellings or dwelling units with split
levels and without an intervening door between the adjacent
levels,a smoke alarm installed on the upper level shall suffice
for the adjacent lower level provided that the lower level is
less than one full story below the upper level.
Fail 907.2.11.2-Groups R-2,R-3,R-4 and I-1.
Single-or multiple-station smoke alarms shall be installed Location:Bedroom#1
and maintained in Groups R-2,R-3,R-4 and I-1 regardless of Comments:Needs smoke detector
occupant load at all of the following locations:1.On the
ceiling or wall outside of each separate sleeping area in the
immediate vicinity of bedrooms.2.In each room used for
sleeping purposes.3.In each story within a dwelling unit,
including basements but not including crawl spaces and
uninhabitable attics.In dwellings or dwelling units with split
levels and without an intervening door between the adjacent
levels,a smoke alarm installed on the upper level shall suffice
for the adjacent lower level provided that the lower level is
less than one full story below the upper level.
907.2.11.2-Groups R-2,R-3,R-4 and 1-1.
Single-or multiple-station smoke alarms shall be installed Location:Bedroom#2
and maintained in Groups R-2,R-3,R-4 and 1-1 regardless of Comments:Needs smoke alarm
occupant load at all of the following locations:1.On the
ceiling or wall outside of each separate sleeping area in the
immediate vicinity of bedrooms.2.In each room used for
sleeping purposes.3.In each story within a dwelling unit,
including basements but not including crawl spaces and
uninhabitable attics.In dwellings or dwelling units with split
levels and without an intervening door between the adjacent
levels,a smoke alarm installed on the upper level shall suffice
for the adjacent lower level provided that the lower level is
less than one full story below the upper level.
GENERATED ON 5/15/26, 8:32 AM 3 OF 5
Fail 907.2.11.2-Groups R-2,R-3,R-4 and I-1.
Single-or multiple-station smoke alarms shall be installed Location:Bedroom#3
and maintained in Groups R-2,R-3,R-4 and I-1 regardless of Comments:Needs smoke alarm
occupant load at all of the following locations:1.On the
ceiling or wall outside of each separate sleeping area in the
immediate vicinity of bedrooms.2.In each room used for
sleeping purposes.3.In each story within a dwelling unit,
including basements but not including crawl spaces and
uninhabitable attics.In dwellings or dwelling units with split
levels and without an intervening door between the adjacent
levels,a smoke alarm installed on the upper level shall suffice
for the adjacent lower level provided that the lower level is
less than one full story below the upper level.
Fail 907.2.11.2-Groups R-2,R-3,R-4 and I-1.
Single-or multiple-station smoke alarms shall be installed Location:Bedroom#4
and maintained in Groups R-2,R-3,R-4 and 1-1 regardless of Comments:Needs smoke alarm
occupant load at all of the following locations:1.On the
ceiling or wall outside of each separate sleeping area in the
immediate vicinity of bedrooms.2.In each room used for
sleeping purposes.3.In each story within a dwelling unit,
including basements but not including crawl spaces and
uninhabitable attics.In dwellings or dwelling units with split
levels and without an intervening door between the adjacent
levels,a smoke alarm installed on the upper level shall suffice
for the adjacent lower level provided that the lower level is
less than one full story below the upper level.
Fail R6-Interior Structure
x� Has the interior of the structure and equipment inside been Location:Upstairs staircase
maintained in good repair,structurally sound,and in a Comments:Lower steps handrail needs to have 2 appropriate
sanitary condition?(IPMC 305)
spindles where empty space exists.
Fail R6-Interior Structure
Has the interior of the structure and equipment inside been Location:Upstairs staircase
maintained in good repair,structurally sound,and in a Comments:Upper step needs appropriate hand rail.
sanitary condition?(IPMC 305)
Fail R6-Interior Structure
Has the interior of the structure and equipment inside been Location:Living room
maintained in good repair,structurally sound,and in a Comments:Need to have window replaced where it is broken out
sanitary condition?(IPMC 305)
Fail R6.A.-Interior Structure-Unsafe Conditions
Were any unsafe conditions noted during the interior Location:Living Room
inspection?(IPMC 305.1.1) Comments:Windows need appropriate locks.Also,need to be able to
stay open on there own.
Fail R6.C.-Mechanical Egiupment
Are mechanical appliances properly installed and maintained Location:Kitchen
in good working condition?(IPMC 603.1) Comments:Stove burners need to be functionable.2 work but 2 don't
come on.
Fail R6.E.-Plumbing System and Fixtures
Plumbing fixtures shall be properly installed and maintained Location:Upstairs Bathroom
in working order,and shall be kept free from obstructions. Comments:Toilet needs to be properly secured to floor.
leaks and defects and be capable of performing the function
for which such plumbing fixtures are designed.Plumbing
fixtures shall be maintained in a safe,sanitary and functional
condition.(IPMC 504.1)
GENERATED ON 5/15/26,a:32 AN 4 04.5
in Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $250.00
Invoice Number Check Number Transaction Number
N!A N!A NIA
GENERATED ON 5/15/26, 8:32 AM 5 OF 5
OF W 4 TF INVOICE DATE DUE DATE INVOICE# TOTAL DUE
o 05/19/2026 06/23/2026 2026-00000095 $250.00
/A• O
) O
e.
Customer#: 24952 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
CFO DEVELOPMENT, LLC 715 Mulberry St
1732 PINHURST LANE WATERLOO, IA 50703
WATERLOO, IA 50701
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
RENTAL PROP INSPECTION - 120 W WELLINGTON ST- 05/08/2026 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
NO SHOW INSPECTION FEE $100.00
REINSPECTION FEE 1ST $50.00
FAILURE TO OBTAIN PERMIT $100.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
24952 05/19/2026 06/23/2026 2026-00000095 $250.00
Less Prepayment $0.00
Total Due-* $250.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.