HomeMy WebLinkAboutCHERYL L. HILL owlellay
�Psew,.00 Waterloo Fire Rescue
• 01 Inspection Report 425 E. 3rd Street
ikFR`°` BLDG 516 Stratford - 516 Stratford AVE, Waterloo IA 50701-5832
INSPECTION DETAILS a3pq r
Inspection Date Inspection Type Inspection Number
05/13/2026 Rental Inspection ( REINSPECTION ) r _ 15981-R6
Lead Inspector Shift Station Unit
Randy Girsch NIA NIA N/A
Other Inspectors
NIA
SUMMARY OF INSPECTION
0 0 0 20 0% 36
Passed codes Resolved violations Failed codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
Randy Girsch
randy.girsch@waterloo-ia.org 0611512026
GENERAL NOTES
Randy Girsch - 04115/2026 @ 10:44
Property Safety Inspector— brad.baldwin@waterloo-ia.org —Work: 319-291-4319 (#5) - Cell: 319-464-5605
Randy Girsch - 04115/2026 @ 10:44
-Re-inspection date is as posted on the inspection report given, the rental unit's responsible person/s shall reach out prior to set time of that re-
inspection. If all corrections are made before the scheduled inspection, you can call to set up an earlier re-inspection. Appropriate notices shall be given
to occupants of the unit's. Owner or owner's agent must be present during inspections. Failure to schedule a time on the date given or failure to keep the
inspection will result in a $100 fee. *****Re inspection fees may be assessed for re-inspections. Re-inspection fees start at $50, then $150, and $250 for all
subsequent re-inspections. All appropriate keys to gain entry to locked units shall be readily available during re-inspection.
Randy Girsch - 04115/2026 @ 10:44
Exterior surfaces repairs and corrections that do not cause an unsafe condition to the building or occupants of the building will be allowed to be made in
spring time when weather permits such work to be made.
Raidy Girsch - 04115/2026 @ 10:44
4/17 - $100 No show fee for scheduled inspection, $50 re-inspection fee for corrections incomplete.
Randy Girsch - 04/1512026 @ 10:44
Tree west of house split at base with potential to break off towards house noted.
GENERATED ON 5/15/26, 3:00 PM 1 OF 11
Yr .
t
•
=
Randy Girsch-0411512026 @ 10:44
$100.00 No show fee for scheduled inspection,$100.00 re-inspection fee for corrections incomplete.
Randy Girsch-0411512026 @ 10:44
03-16-2026-Randy Girsch$100 No Show fee for scheduled inspection,$250 re-inspection fee for corrections incomplete.Re-inspection will be set for
Monday April 13th @ 9:00 am.
Randy Girsch-05115/2026 @ 14:57
05-13-2026 Randy Girsch-On this date I conducted a reinspection of the property located at 516 Stratford Ave.Owner Cheryl Hill and renter were present.
After the inspection I noticed there were still 36 corrections that needed to be made.Due to all the corrections not being done and the fact that the owner
has know about the corrections needed for a year and 4 months a fee of$250 will be charged for the reinspection fee.I have scheduled the next
reinspection for Monday June 15th 2026 at 9am.At this time I would expect that all the violations would be corrected along with the roof.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection A1`
Cheryl Hill Date: Randy Girsch 05/15/2026
GENERATED ON 5/15/26, 3:00 PM 7 OF 1:.
CHECKLISTS
GENERATED ON 5/15/26, 3:00 PM 3 OF 11
Reinspection
Status Code Description
Fail 603.2-Abatement of unsafe conditions and electrical
hazards. Location:2nd floor toilet room
Identified electrical hazards shall be abated.Identified Comments:Electrical box on wall open without cover and loose wires
hazardous electrical conditions in permanent wiring shall be uncapped or connected.605.1 Installation.Electrical equipment,
brought to the attention of the responsible code official. wiring and appliances shall be properly installed and maintained in a
Electrical wiring,devices,appliances and other equipment safe and approved manner.
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Fail 603.2-Abatement of unsafe conditions and electrical
hazards. Location:Laundry washer outlet
Identified electrical hazards shall be abated.Identified Comments:Outlet shows sign of damage,shall be replaced.604.3
hazardous electrical conditions in permanent wiring shall be Electrical system hazards.Where it is found that the electrical system
brought to the attention of the responsible code official. in a structure constitutes a hazard to the occupants or the structure
Electrical wiring,devices,appliances and other equipment by reason of inadequate service,improper fusing,insufficient
that is modified or damaged and constitutes Conditions that receptacle and lighting outlets,improper wiring or installation,
constitute an electrical shock or fire hazard shall be abated deterioration or damage,or for similar reasons,the code official shall
not be used. require the defects to be corrected to eliminate the hazard.
Fail 603.2-Abatement of unsafe conditions and electrical
hazards. Location:Main floor bathroom light/electrical wiring
Identified electrical hazards shall be abated.Identified Comments:Wiring for light fixture shall be installed to code.Permit
hazardous electrical conditions in permanent wiring shall be and inspection shall be obtained
brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Fail 603.2-Abatement of unsafe conditions and electrical
hazards. Location:2nd floor bedroom#1(clockwise)
Identified electrical hazards shall be abated.Identified Comments:Broken light switch cover shall be replaced.
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Fail 907.2.11.2-Groups R-2,R-3,R-4 and I-1.
Single-or multiple-station smoke alarms shall be installed Location:2nd floor bedrooms
and maintained in Groups R-2,R-3,R-4 and I-1 regardless of Comments:Smoke detectors required installed properly in
occupant load at all of the following locations:i.On the accordance to manufactures guidelines in bedrooms and in good
ceiling or wall outside of each separate sleeping area in the
working condition.
immediate vicinity of bedrooms.2.In each room used for
sleeping purposes.3.In each story within a dwelling unit,
including basements but not including crawl spaces and
uninhabitable attics.In dwellings or dwelling units with split
levels and without an intervening door between the adjacent
levels,a smoke alarm installed on the upper level shall suffice
for the adjacent lower level provided that the lower level is
less than one full story below the upper level.
GENERATED ON 5/15/26, 3:00 PM 4 OF 11
Fail 907.2.11.2-Groups R-2,R-3,R-4 and 1-1.
Single-or multiple-station smoke alarms shall be installed Location:Main floor bedroom smoke detector
and maintained in Groups R-2,R-3,R-4 and I-1 regardless of Comments:Missing detector shall be corrected.Smoke detectors
occupant load at all of the following locations:1.On the required installed ro erl
ceiling or wall outside of each separate sleeping area in the q p Yin accordance to manufactures guidelines
in bedrooms and in good working condition.
immediate vicinity of bedrooms.2.In each room used for
sleeping purposes.3.In each story within a dwelling unit,
including basements but not including crawl spaces and
uninhabitable attics.In dwellings or dwelling units with split
levels and without an intervening door between the adjacent
levels,a smoke alarm installed on the upper level shall suffice
for the adjacent lower level provided that the lower level is
less than one full story below the upper level.
Fail 915.2.1-Dwelling units.
Carbon monoxide detection shall be installed in dwelling Location:Outside 2nd floor bedrooms
units outside of each separate sleeping area in the immediate Comments:Carbon monoxide detector shall be properly installed in
vicinity of the bedrooms.Where a fuel-burning appliance is near proximity to bedrooms.
located within a bedroom or its attached bathroom,carbon
monoxide detection shall be installed within the bedroom.
Fail R5-Exterior Structure
Is the exterior of the structure maintained in good repair, Location:2nd floor bedroom window
structurally sound and sanitary state?(IPMC 304) Comments:Cracked window shall be corrected.304.13.1 Glazing.
Glazing materials shall be maintained free from cracks and holes.
Fail R5-Exterior Structure
Is the exterior of the structure maintained in good repair, Location:West side stairs
structurally sound and sanitary state?(IPMC 304) Comments:Stairs missing guardraillhandrail shall be corrected.Prior
to installation requires building permit and inspection to follow.307.1
General.Every exterior and interior flight of stairs having more than
four risers shall have a handrail on one side of the stair and every
open portion of a stair,landing,balcony,porch,deck,ramp or other
walking surface that is more than 30 inches(762 mm)above the floor
or grade below shall have guards.
Fail R5-Exterior Structure
Is the exterior of the structure maintained in good repair, Location:Roof
structurally sound and sanitary state?(IPMC 304) Comments:Metal roof overlay installation incomplete,contractor is
waiting for parts on order.Building inspection shall be obtained when
work completed.
Fail R5-Exterior Structure
Is the exterior of the structure maintained in good repair, Location:SW corner foundation wall
structurally sound and sanitary state?(IPMC 304) Comments:Openings in foundation wall shall be corrected by means
of tuck-pointing.304.5 Foundation walls.Foundation walls shall be
maintained plumb and free from open cracks and breaks and shall be
kept in such condition so as to prevent the entry of rodents and other
pests.
Fail R5-Exterior Structure
V Is the exterior of the structure maintained in good repair, Location:North deck guardrail
structurally sound and sanitary state?(IPMC 304) Comments:Missing spindles in guardrail shall be corrected.304.12
Handrails and guards.Every handrail and guard shall be firmly
fastened and capable of supporting normally imposed loads and
shall be maintained in good condition
GENERATED ON 5/15/26, 3:00 PM 5 OF 11
Fail R5-Exterior Structure
Is the exterior of the structure maintained in good repair, Location:South corners of building
structurally sound and sanitary state?(IPMC 304) Comments:Openings to exterior elements allowing weather shall be
corrected 304.6 Exterior walls.Exterior walls shall be free from holes,
breaks,and loose or rotting materials;and maintained weatherproof
and properly surface coated where required to prevent deterioration
Fail R5-Exterior Structure
L:J Is the exterior of the structure maintained in good repair, Location:East side window coverings
structurally sound and sanitary state?(IPMC 304) Comments:Untreated window coverings shall maintain weather-tight,
exterior of door shall maintain protected from elements.(IPMC)-
304.2 Protective treatment.Exterior surfaces,including but not
limited to,doors,door and window frames,cornices,porches,trim,
balconies,decks and fences,shall be maintained in good condition.
Exterior wood surfaces,other than decay-resistant woods,shall be
protected from the elements and decay by painting or other
protective covering or treatment.Peeling,flaking and chipped paint
shall be eliminated and surfaces repainted.Siding and masonry
joints,as well as those between the building envelope and the
perimeter of windows,doors and skylights,shall be maintained
weather resistant and water tight.
Fail R5-Exterior Structure
OIs the exterior of the structure maintained in good repair, Location:North deck guardrail.
structurally sound and sanitary state?(IPMC 304) Comments:Deck guardrail(east side)has become loose from
framing and unable to support imposed loads.304.12 Handrails and
guards.Every handrail and guard shall be firmly fastened and
capable of supporting normally imposed loads and shall be
maintained in good condition
Fail R5-Exterior Structure
Is the exterior of the structure maintained in good repair, Location:Chimney
structurally sound and sanitary state?(IPMC 304) Comments:Chimney lacks maintenance,shall be inspected by
professional contractor for necessary repairs.
4 Al •
w
.\
Nr.
' , \ . ,
\III
• ,
s4 ,t \
GENERATED ON 5/15/26, 3:00 PM 'i
Fail R5-Exterior Structure
Is the exterior of the structure maintained in good repair, Location:East side basement window coverings
structurally sound and sanitary state?(IPMC 304) Comments:Plywood window coverings untreated shall be treated to
protect from weather elements or glass in good condition installed.•{
\
• 1
Fail R5-Exterior Structure
Is the exterior of the structure maintained in good repair, Location:North side deck guardrail
structurally sound and sanitary state?(IPMC 304) Comments:Guardrail on east side of deck unable to withstand
imposed force,loose from framing shall be corrected.
Fail R6-Interior Structure
Has the interior of the structure and equipment inside been Location:Kitchen vanity cabinets
maintained in good repair,structurally sound,and in a Comments:Holes in,damaged,defective vanity cabinets shall be
sanitary condition?(IPMC 305) repaired or replaced.
Fail R6-Interior Structure
Has the interior of the structure and equipment inside been Location:Wall surface near 2nd floor closet(top of stairs)
maintained in good repair,structurally sound,and in a Comments:Wall covering missing around doorway shall be
sanitary condition?(IPMC 305) corrected.
Fail R6-Interior Structure
Has the interior of the structure and equipment inside been Location:2nd floor bedroom ceiling surfaces
maintained in good repair,structurally sound,and in a Comments:Peeling paint and all loose surfaces shall be
sanitary condition?(IPMC 305) removed/repaired.305.3 Interior surfaces.Interior surfaces,including
windows and doors,shall be maintained in good,clean and sanitary
condition.Peeling,chipping,flaking or abraded paint shall be
repaired,removed or covered.Cracked or loose plaster,decayed
wood and other defective surface conditions shall be corrected.
Fail R6-Interior Structure
Has the interior of the structure and equipment inside been Location:2nd floor toilet room
maintained in good repair,structurally sound,and in a Comments:Door missing to toilet room and openings in walls fail to
sanitary condition?(IPMC 305) provide privacy required.[P]503.1 Privacy.Toilet rooms and
bathrooms shall provide privacy and shall not constitute the only
passageway to a hall or other space,or to the exterior.A door and
interior locking device shall be provided for all common or shared
bathrooms and toilet rooms in a multiple dwelling.
GENERATED ON 5/15/26, 3:00 PM 7 OF 11
Fail R6•Interior Structure
Has the interior of the structure and equipment inside been Location:Stairway to 2nd floor handrail.
maintained in good repair,structurally sound,and in a Comments:Handrail loose shall be fastened tightly.304.12 Handrails
sanitary condition?(IPMC 305) and guards.Every handrail and guard shall be firmly fastened and
capable of supporting normally imposed loads and shall be
maintained in good condition
Fail R6-Interior Structure
Ox Has the interior of the structure and equipment inside been Location:2nd floor flooring
maintained in good repair,structurally sound,and in a Comments:Carpet tack strips are present without carpet attached.
sanitary condition?QPMC 305) Tack strips shall either be removed or carpet installed.305.4 Stairs
and walking surfaces.Every stair,ramp,landing,balcony,porch,
deck or other walking surface shall be maintained in sound condition
and good repair.
Fail R6-Interior Structure
Ox Has the interior of the structure and equipment inside been Location:Stairway to basement handrail
maintained in good repair,structurally sound,and in a Comments:Missing guardrail&handrail shall be corrected.Building
sanitary condition?(IPMC 305) - permit and inspections shall be obtained.307.1 General.Every
exterior and interior flight of stairs having more than four risers shall
have a handrail on one side of the stair and every open portion of a
stair,landing,balcony,porch,deck,ramp or other walking surface
that is more than 30 inches(762 mm)above the floor or grade below
shall have guards.
Fall R6-Interior Structure
Has the interior of the structure and equipment inside been Location:Main floor bathroom door
maintained in good repair,structurally sound,and in a Comments:Door hinges loose to jamb and door fails to latch,shall
sanitary condition?QPMC 305) be corrected.
Fail R6.C.-Mechanical Egiupment
Are mechanical appliances properly installed and maintained Location:Main floor HVAC registers
in good working condition?(IPMC 603.1) Comments:Appropriate register covers shall be installed/607.1
General.Duct systems shall be maintained free of obstructions and
shall be capable of performing the required function.
Fail R6.E.•Plumbing System and Fixtures
Plumbing fixtures shall be properly installed and maintained Location:Main floor vanity faucet
in working order,and shall be kept free from obstructions, Comments:Faucet spout loose and handles installed backwards.
leaks and defects and be capable of performing the function
for which such plumbing fixtures are designed.Plumbing
fixtures shall be maintained in a safe,sanitary and functional
condition.QPMC 504.1)
Fail R6.E.-Plumbing System and Fixtures
Plumbing fixtures shall be properly installed and maintained Location:Kitchen sink drain piping.
in working order,and shall be kept free from obstructions, Comments:Improper drainage("s trap"not allowed)installation shall
leaks and defects and be capable of performing the function be corrected.Installation of wasteNent piping shall be done by
for which such plumbing fixtures are designed.Plumbing licensed plumber with permit and inspections obtained.[Pj 504.3
fixtures shall be maintained in a safe,sanitary and functional Plumbing system hazards.Where h is found that a plumbing system
condition.(IPMC 504.1) in a structure constitutes a hazard to the occupants or the structure
by reason of inadequate service,inadequate venting,cross
connection,backsiphonage,improper installation,deterioration or
damage or for similar reasons,the code official shall require the
defects to be corrected to eliminate the hazard.
GENERATED ON 5/15/On, 3:00 PM 0 OF 11
Fail R6.E. - Plumbing System and Fixtures
Plumbing fixtures shall be properly installed and maintained Location: 2nd floor toilet
in working order, and shall be kept free from obstructions, Comments: Tenant has stated toilet is not functional due to defective
leaks and defects and be capable of performing the function parts. Repairs shall be made to rectify if necessary. [P] 504.1 General.
for which such plumbing fixtures are designed. Plumbing Plumbing fixtures shall be properly installed and maintained in
fixtures shall be maintained in a safe, sanitary and functional working order, and shall be kept free from obstructions, leaks and
condition. (IPMC 504.1) defects and be capable of performing the function for which such
plumbing fixtures are designed. Plumbing fixtures shall be
maintained in a safe, sanitary and functional condition.
Fail R6.E. - Plumbing System and Fixtures
Plumbing fixtures shall be properly installed and maintained Location: Basement laundry drainage
in working order, and shall be kept free from obstructions, Comments: Laundry drainage shall be properly connected to building
leaks and defects and be capable of performing the function sewer system or laundry washer removed from basement.
for which such plumbing fixtures are designed. Plumbing Connection to sewer system shall be installed by licensed plumber
fixtures shall be maintained in a safe, sanitary and functional with permit and inspections obtained. [P] 504.3 Plumbing system
condition. (IPMC 504.1) hazards. Where it is found that a plumbing system in a structure
constitutes a hazard to the occupants or the structure by reason of
inadequate service, inadequate venting, cross connection,
backsiphonage, improper installation, deterioration or damage or for
similar reasons, the code official shall require the defects to be
corrected to eliminate the hazard.
Fail R6.E. - Plumbing System and Fixtures
Plumbing fixtures shall be properly installed and maintained Location: Main floor shower walls
in working order, and shall be kept free from obstructions, Comments: OSB plywood water soaked and shows signs of mold like
leaks and defects and be capable of performing the function substance shall be removed and replaced. Per IRC Code - "Shower
for which such plumbing fixtures are designed. Plumbing walls shall be a nonabsorbent surface and extend not less than 6ft
fixtures shall be maintained in a safe, sanitary and functional above the floor"
condition. (IPMC 504.1)
Fail R6.E. - Plumbing System and Fixtures
Plumbing fixtures shall be properly installed and maintained Location: 2nd floor bathroom sink drainage
in working order, and shall be kept free from obstructions, Comments: drainage Improper "s trap" piping not
leaks and defects and be capable of performing the function g ( Installation
p g
approved by code) installation shall be corrected. of
for which such plumbing fixtures are designed. Plumbing wastelvent piping shall be done by licensed plumber with permit and
fixtures shall be maintained in a safe, sanitary and functional inspections obtained. [P] 504.3 Plumbing system hazards. Where it is
condition. (IPMC 504.1) found that a plumbing system in a structure constitutes a hazard to
the occupants or the structure by reason of inadequate service,
inadequate venting, cross connection, backsiphonage, improper
installation, deterioration or damage or for similar reasons, the code
official shall require the defects to be corrected to eliminate the
hazard.
Fail R6.E. - Plumbing System and Fixtures
Plumbing fixtures shall be properly installed and maintained Location: Main floor bathroom sink drainage
in working order, and shall be kept free from obstructions, Comments: Improper drainage ("s trap" not allowed) installation shall
leaks and defects and be capable of performing the function be corrected. Installation of wastelvent piping shall be done by
for which such plumbing fixtures are designed. Plumbing licensed plumber with permit and inspections obtained. [P] 504.3
fixtures shall be maintained in a safe, sanitary and functional Plumbing system hazards. Where it is found that a plumbing system
condition. (IPMC 504.1) in a structure constitutes a hazard to the occupants or the structure
by reason of inadequate service, inadequate venting, cross
connection, backsiphonage, improper installation, deterioration or
damage or for similar reasons, the code official shall require the
defects to be corrected to eliminate the hazard.
GENERATED ON 5/15/26, 3:00 PM 9 OF 11
Fail R6.E.-Plumbing System and Fixtures
Plumbing fixtures shall be properly installed and maintained Location:Water heater
in working order,and shall be kept free from obstructions, Comments:Pressure relief valve missing drain tubing.Installation
leaks and defects and be capable of performing the function shall be up to plumbing code.
for which such plumbing fixtures are designed.Plumbing
fixtures shall be maintained in a safe,sanitary and functional
condition.(IPMC 504.1)
Fail R6.E.-Plumbing System and Fixtures
Plumbing fixtures shall be properly installed and maintained Location:Main floor sink drain
in working order,and shall be kept free from obstructions, Comments:Pop up assembly sealed shut with silicone,not as
leaks and defects and be capable of performing the function manufactured.Corrections shall be made to be installed as
for which such plumbing fixtures are designed.Plumbing manufactured.
fixtures shall be maintained in a safe,sanitary and functional
condition.(IPMC 504.1)
GENERATED ON 5/15/26, 3:00 PM 10 OF 11
la Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $250.00
Invoice Number Check Number Transaction Number
NIA NIA NIA
GENERATED ON 5/15/26, 3:00 PM 11 OF 11
OF W q7.4 INVOICE DATE DUE DATE INVOICE# TOTAL DUE
05/19/2026 06/23/2026 2026-00000096 $250.00
u fiy IA O
> O
Customer#: 24911 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
CHERYL L HILL 715 Mulberry St
215 LAWRENCE AVE WATERLOO, IA 50703
EVANSDALE, IA 50707
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
RENTAL PROP INSPECTION - 516 STRATFORD AVE - 05/13/2026 FOR BILLING INQUIRY: (319)291-4323
[ascription Total Price
REINSPECTION FEE 3RD $250.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
24911 05/19/2026 06/23/2026 2026-00000096 $250.00
Less Prepayment $0.00
Total Due $250.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
W A T INVOICE DATE DUE DATE INVOICE# TOTAL DUE
A #1:0� 03/16/2026 04/20/2026 2026-00000080 $350.00
• •iisci •
r.
44.
7vil‘
Customer#: 24911 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
CHERYL L HILL 715 Mulberry St
215 LAWRENCE AVE WATERLOO, IA 50703
EVANSDALE, IA 50707
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
RENTAL INSPECTION - 516 STRATFORD AVE- 03/16/2026 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
NO SHOW INSPECTION FEE $100.00
REINSPECTION FEE 3RD $250.00
CUSTOMER# BILLING DATE DUE DATE _ INVOICE# CHARGES
24911 03/16/2026 04/20/2026 2026-00000080 $350.00
Less Prepayment $0.00
Total Due—> $350.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
W A p INVOICE DATE DUE DATE INVOICE# TOTAL DUE
O
s 4 //0 02/18/2026 03/25/2026 2026-00000073 $200.00
,oa0.. /Am O
4. 7 e►O`�
Customer#: 24911 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
CHERYL L HILL 715 Mulberry St
215 LAWRENCE AVE WATERLOO, IA 50703
EVANSDALE, IA 50707
Amount Enclosed.
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
RENTAL FIRE INSPECTION- 516 STRATFORD AVE- 02/16/2026 FOR BILLING INQUIRY: (319)291-4323
02/16/2026-No Show Fee $100.00
02/16/2026 - Incomplete corrections for re-inspection
Description Total Price
NO SHOW INSPECTION FEE $100.00
REINSPECTION FEE 1ST $100.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
24911 02/18/2026 03/25/2026 2026-00000073 $200.00
Less Prepayment $0.00
Total Due —* S200.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
F W A T INVOICE DATE DUE DATE INVOICE # TOTAL DUE
Oj ( 06/20/2025 07/20/2025 2025-00000150 $150.00
o
*...,..... v o
Customer #: 23409 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
CHERYL L HILL 715 Mulberry St
215 LAWRENCE AVE WATERLOO, IA 50703
EVANSDALE, IA 50707
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
RENTAL INSPECTION - 516 STRATFORD - 4-17-25 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
REINSPECTION FEE 2ND $150.00
CUSTOMER# BILLING DATE DUE DATE INVOICE # CHARGES
23409 06/20/2025 07/20/2025 2025-00000150 $150.00
Less Prepayment $0.00
Total Due --> $150.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.