HomeMy WebLinkAboutTARGET SUPER STORE Waterloo Fire Rescue Inspection Report 425 E.3rd Street «<,, o' Target Super Store-1501 E San Marnan DR,BLDG 1501 E San Marnan Dr,Waterloo IA 50702 INSPECTION DETAILS Inspection Date Inspection type Inspection Number �' -= 06/01/2026 Annual Inspection(1Yr) (Q,IU . 22017 Lead Inspector Shift Station Unit BRAD BALDWIN NIA N/A N/A Other Inspectors N/A SUMMARY OF INSPECTION 050 C27 ® 10 Passed codes Failed codes N/A codes NEXT STEPS Please direct questions about your Inspection to: Reinspection Date BRAD BALDWIN 06125/2026 brad.baldwin@waterloo-ia.org,3192914319 GENERAL NOTES BRAD BALDWIN-0610112026 @ 12:24 $610 annual inspection fee BRAD BALDWIN-06/0112026 @ 12:25 •Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224 BRAD BALDWIN-06/0112026 @ 12:25 •Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards corrected BRAD BALDWIN-0610112026 @ 12:25 •If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re- inspection fees start at$100,then$150,and$200 for all subsequent re-inspections. SIGNATURES Contact signature Inspector signature No signature Report completed post inspection Kyle(2025)floor manager Date: BRAD BALDWIN 06104/2026 CHECKLISTS GENERATED ON 6/4/26, 7:06 AM 1 OF 13 Means of Egress S;r.n,s Code Description Fail 1010.1.3-Door opening force Forces to unlatch and open doors. Location:North side emergency exit doors(left door) The force for pushing or pulling open interior swinging Comments:Repair or replace door that failed to open.Replacement egress doors,other than fire doors,shall not exceed 5 of door requires permit and inspection obtained. pounds(22 N).These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door in a closed position.For other swinging doors, as well as sliding and folding doors,the door latch shall release when subjected to a 15-pound(67 N)force.The door shall be set in motion when subjected to a 30-pound(133 N) force.The door shall swing to a full-open position when subjected to a 15-pound(67 N)force.The forces to unlatch doors shall comply with the following:1.Where door hardware operates by push or pull,the operational force to unlatch the door shall not exceed 15 pounds(66.7 N).2.Where door hardware operates by rotation,the operational force to unlatch the door shall not exceed 28 inch-pounds(315 N-cm). The force to open doors shall comply with the following: 1.For interior swinging egress doors that are manually operated,other than doors required to be fire rated,the force for pushing or pulling open the door shall not exceed 5 pounds(22 N).2.For other swinging doors,sliding doors or folding doors,and doors required to be fire rated,the door shall require not more than a 30-pound(133 N)force to be set in motion and shall move to a full-open position when subjected to not more than a 15-pound(67 N)force. GENERATED ON 6/4/26, 7:06 AM 2 OF 13 Additional Codes 5!a?es. Code Descripfioo Fail 102.4-Application of building code. The design and construction of new structures shall comply Location:HVAC permit with the International Building Code,and any alterations, Comments:Contractor(Arris Inc)shall obtain inspection of work additions,changes in use or changes in structures required when completed by this code,which are within the scope of the International Building Code,shall be made in accordance therewith. Fail 102.4-Application of building code. The design and construction of new structures shall comply Location:Electrical permit with the International Building Code,and any alterations, Comments:Contractor(Superior Lighting Inc)shall obtain inspection additions,changes in use or changes in structures required of work when completed by this code,which are within the scope of the International Building Code,shall be made in accordance therewith. Fail 102.4-Application of building code. The design and construction of new structures shall comply Location:Electrical permit(for HVAC) with the International Building Code,and any alterations, Comments:Contractor(Steve's Electric)shall obtain inspection of additions,changes in use or changes in structures required work when completed. by this code,which are within the scope of the International Building Code,shall be made in accordance therewith. Fail 507.5.3-Private fire service mains and water tanks. Private fire service mains and water tanks shall be Location:Private fire hydrants periodically inspected,tested and maintained in accordance Comments:Provide annual hydrants inspection and contractors with NFPA 25 at the following intervals:1.Private fire hydrants report including any deficiencies corrected to Compliance Engine of all types:Inspection annually and after each operation; flow test and maintenance annually.2.Fire service main piping:Inspection of exposed,annually;flow test every 5 years.3.Fire service main piping strainers:Inspection and maintenance after each use.Records of inspections,testing and maintenance shall be maintained. Fail 907.6.6-Monitoring. Fire alarm systems required by this chapter or by the Location:Main fire alarm control panel room International Building Code shall be monitored by an Comments:Smoke monitoring device required installed above main approved supervising station in accordance with NFPA 72. fire alarm panel. Exception:Monitoring by a supervising station is not required for:1.Single-and multiple-station smoke alarms required by Section 907.2.11.2.Smoke detectors in Group 1-3 occupancies.3.Automatic sprinkler systems in one-and two- family dwellings. GENERATED ON 6/4/26, 7:06 AM 3 OF 13 Emergency Equipment S-ards Code Description Fail 1203.2.15-Means of egress illumination. Emergency power shall be provided for means of egress Location:All emergency egress lighting illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:All egress lights shall be tested and repaired if nonfunctional,provide documentation of all lighting working properly to inspector including signed and dated. Fail 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required Location:All exit signs in Section 1013.6.3.The system shall be capable of powering Comments:All exit signs shall be tested and repaired if the required load for a duration of not less than 90 minutes. nonfunctional,provide documentation of all signage working properly to inspector including signed and dated. Fail 1203.4.3-Records. Records of the inspection,testing and maintenance of Location:Emergency backup generator emergency and standby power systems shall include the date Comments:Provide annual inspection and report to be uploaded to of service,name of the servicing technician,a summary of Compliance Engine including any deficiencies corrected.Currently conditions noted and a detailed description of any conditions due by 6125126 requiring correction and what corrective action was taken. Such records shall be maintained. General Housekeeping S[a:us Code Description Fail 315.3.1-Ceiling clearance. Storage shall be maintained 2 feet(610 mm)or more below Location:Deli back storage the ceiling in nonsprinklered areas of buildings or not less Comments:Storage within 18 inches below sprinkler heads shall be than 18 inches(457 mm)below sprinkler head deflectors in lowered or removed not including storage along walls. sprinklered areas of buildings.Exceptions:1.The 2-foot(610 mm)ceiling clearance is not required for storage along walls in nonsprinklered areas of buildings.2.The 18-inch(457 mm) ceiling clearance is not required for storage along walls in areas of buildings equipped with an automatic sprinkler system in accordance with Section 903.3.1.1,903.3.1.2 or 903.3.1.3. Fail 315.3.2-Means of egress. Combustible materials shall not be stored in exits or Location:Bottom of stairway leading to"Hussman House" enclosures for stairways and ramps.Combustible materials in Comments:Remove storage obstructing path to stairway,would the means of egress during construction,demolition, approve floor markings installed where storage shall not be stored. remodeling or alterations shall comply with Section 3312.3. GENERATED ON 6/4/26, 7:06 AM 4 OF 13 Fire Sprinkler System szasu; Code Descripoc: Fail 5.2.1-Annual sprinkler system inspection Sprinklers shall be inspected at least annually by licensed Location:Sprinkler system contractor Comments:Provide annual sprinkler inspection and contractors report including any deficiencies corrected to Compliance Engine Fail 5.2.1.1.5-Missing escutcheons Escutcheons and coverplates for recessed,flush,and Location:Starbucks back storage concealed sprinklers shall be replaced if found missing Comments:Replace missing escutcheon ring. during the inspection. Fail 5.2.1.1.5-Missing escutcheons Escutcheons and coverplates for recessed,flush,and Location:Mechanical room near cash office concealed sprinklers shall be replaced if found missing Comments:Loose sprinkler escutcheon above water heater shall be during the inspection. corrected. r Fail 903.3.3-Obstructed locations. Automatic sprinklers shall be installed with regard to Location:Back stock area obstructions that will delay activation or obstruct the water Comments:Remove water leak umbrella above shelving used for distribution pattern and shall be in accordance with the previous roof water leak obstructing sprinkler coverage.Roof leak applicable automatic sprinkler system standard that is being was reportedly repaired. used.Automatic sprinklers shall be installed in or under covered kiosks,displays,booths,concession stands or equipment that exceeds 4 feet(1219 mm)in width.Not less than a 3-foot(914 mm)clearance shall be maintained between automatic sprinklers and the top of piles of combustible fibers.Exception:Kitchen equipment under exhaust hoods protected with a fire-extinguishing system in accordance with Section 904. GENERATED ON 6/4/26, 7:06 AM 5 OF 13 Fail 903.3.3-Obstructed locations. Automatic sprinklers shall be installed with regard to Location:Back stock area obstructions that will delay activation or obstruct the water Comments:Product on shelving and storage above the maximum distribution pattern and shall be in accordance with the allowed 15 ft shall be lowered. applicable automatic sprinkler system standard that is being used.Automatic sprinklers shall be installed in or under covered kiosks,displays,booths,concession stands or equipment that exceeds 4 feet(1219 mm)in width.Not less than a 3-foot(914 mm)clearance shall be maintained between automatic sprinklers and the top of piles of combustible fibers.Exception:Kitchen equipment under exhaust hoods protected with a fire-extinguishing system in accordance with Section 904. Fire Service Features ;. .. Co- Description Fail 509.2-Equipment access. Approved access shall be provided and maintained for all fire Location:Back stock area-Sprinkler piping protection system equipment to permit immediate safe Comments:Remove storage from within 36"of sprinkler piping operation and maintenance of such equipment.Storage,trash equipment and other materials or objects shall not be placed or kept in such a manner that would prevent such equipment from being readily accessible. 1 1I. i. i -r. , t/1`` AYR GENERATED ON 6/4/26, 7:06 AM 6 OF 13 Electrical Safety s[atus Code Description Fail 603.2.2-Unapproved conditionsOpen electrical terminations. Open junction boxes and open-wiring splices shall be Location:Upper level"Hussman House"-Above"Rack A" prohibited.Approved covers shall be provided for all switch Comments:Wires shall be properly capped with cover installed on and electrical outlet boxes, box • Fail 603.6-Extension cords. Extension cords and flexible cordsshall not be a substitute Location:Cash recycler room for permanent wiring and shall be listed and labeled in accordance with UL 817.Extension cords and flexible Comments:Appliances including motors and/or heating elements cordsshallaccordant not be affixed to structures,extended through shall be plugged directly to a permanent wall outlet.Remove cash recycler from extension cord and power strip and relocate to plug walls,ceilings or floors,or under doors or floor coverings, nor shall such cords be subject to environmental damage or directly to wall outlet physical impact.Extension cords shall be used only with portable appliances.Extension cords marked for indoor use shall not be used outdoors. GENERATED ON 6/4/26, 7:06 AM 7 OF 13 Fire Resistant Construction Maintenance 5[_tus Cafe Description Fail 704.1-Maintaining protection. Where required when the building was originally constructed, Location:Starbucks back storage room materials and systems used to protect joints and voids in the Comments:Carefully remove paint covering fire rating door labels to following locations shall be maintained.The materials and avoid removing label information.Missing or damaged labels systems shall be securely attached to or bonded to the requires door to be re-certified as fire rated or replaced with adjacent construction,without openings visible through the obtaining permit and inspection.Also,door is required to self-shut construction.1.Joints in or between fire-resistance-rated and latch,remove obstructions to door closing and install fire rated walls,floors or floorlceiling assemblies and roof or smoke seals on door frame. roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at the intersection of a horizontal floor assembly and an exterior curtain wall.4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain wall.5.Voids at the intersection of a nonfire-resistance-rated floor assembly and an exterior curtain wall.6.Voids at the intersection of a vertical fire barrier and an exterior curtain wall.7.Voids at the intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.Unprotected joints and voids do not need to be protected where such joints and voids were not required to be protected when the building was originally constructed.Where the system design number is known,the system shall be inspected to the listing criteria and manufacturer&#039;s installation instructions. I�„,� : : ': ,,,,,,_ 4/l s%% 5_,.„ �t,I/yiJrri>u/,, i. ,._,..., , ,..,...... ,,,,,,.: , , , , i,„„. „..,...,,______,„.„,, ,.. rl i i/►.' It, tom` 8 OF 7 GENERATED ON 6/4/26, 7:06 AM Fail 704.1-Maintaining protection. Where required when the building was originally constructed, Location:Cash office hallway entrance materials and systems used to protect joints and voids in the Comments:Carefully remove paint covering fire rating door labels to following locations shall be maintained.The materials and avoid removing label information.Missing or damaged labels systems shall be securely attached to or bonded to the requires door to be re-certified as fire rated or replaced with adjacent construction,without openings visible through the obtaining permit and inspection. construction.1.Joints in or between fire-resistance-rated walls,floors or floorlceiling assemblies and roof or rooflceiling assemblies.2.Joints in smoke barriers.3.Voids at the intersection of a horizontal floor assembly and an exterior curtain wall.4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain wall.5.Voids at the intersection of a nonfire-resistance-rated floor assembly and an exterior curtain wall.6.Voids at the intersection of a vertical fire barrier and an exterior curtain wall.7.Voids at the intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.Unprotected joints and voids do not need to be protected where such joints and voids were not required to be protected when the building was originally constructed.Where the system design number is known,the system shall be inspected to the listing criteria and manufacturer&#039;s installation instructions. 1/4 �S Ni 0 11. • Ya cH 4'4 GENERATED ON 6/4/26, 7:06 AM 9 OF 13 Fail 704.1-Maintaining protection. Where required when the building was originally constructed, Location:Control Room materials and systems used to protect joints and voids in the Comments:Provide missing fire rated smoke seals on door frame following locations shall be maintained.The materials and systems shall be securely attached to or bonded to the adjacent construction,without openings visible through the construction.1.Joints in or between fire-resistance-rated walls,floors or floorlceiling assemblies and roof or roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at the intersection of a horizontal floor assembly and an exterior curtain wall.4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain wall.5.Voids at the intersection of a nonfire-resistance-rated floor assembly and an exterior curtain wall.6.Voids at the intersection of a vertical fire barrier and an exterior curtain wall.7.Voids at the intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.Unprotected joints and voids do not need to be protected where such joints and voids were not required to be protected when the building was originally constructed.Where the system design number is known,the system shall be inspected to the listing criteria and manufacturer&#039;s installation instructions. Fail 704.1-Maintaining protection. Where required when the building was originally constructed, Location:Cash recycler room materials and systems used to protect joints and voids in the Comments:Provide missing fire rated smoke seals on door frame following locations shall be maintained.The materials and systems shall be securely attached to or bonded to the adjacent construction,without openings visible through the construction.1.Joints in or between fire-resistance-rated walls,floors or floor/ceiling assemblies and roof or roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at the intersection of a horizontal floor assembly and an exterior curtain wall.4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain wall.5.Voids at the intersection of a nonfire-resistance-rated floor assembly and an exterior curtain wall.6.Voids at the intersection of a vertical fire barrier and an exterior curtain wall.7.Voids at the intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.Unprotected joints and voids do not need to be protected where such joints and voids were not required to be protected when the building was originally constructed.Where the system design number is known,the system shall be inspected to the listing criteria and manufacturer&#039;s installation instructions. GENERATED ON 6/4/26, 7:06 AM 10 OF 13 Fail 704.1-Maintaining protection. Where required when the building was originally constructed, Location:Electrical equipment room near Cash Recycler materials and systems used to protect joints and voids in the Comments:Provide missing fire rated smoke seals on door frame following locations shall be maintained.The materials and systems shall be securely attached to or bonded to the adjacent construction,without openings visible through the construction.1.Joints in or between fire-resistance-rated walls,floors or floor/ceiling assemblies and roof or rooflceiling assemblies.2.Joints in smoke barriers.3.Voids at the intersection of a horizontal floor assembly and an exterior curtain wall.4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain wall.5.Voids at the intersection of a nonfire-resistance-rated floor assembly and an exterior curtain wall.6.Voids at the intersection of a vertical fire barrier and an exterior curtain wall.7.Voids at the intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.Unprotected joints and voids do not need to be protected where such joints and voids were not required to be protected when the building was originally constructed.Where the system design number is known,the system shall be inspected to the listing criteria and manufacturer&#039;s installation instructions. Fail 705.2.4-Door operation. Swinging fire doors shall close from the full-open position Location:Cash office entrance hallway and latch automatically. Comments:Repair or replace door that failed to self-shut and latch today.Also,install fire rated smoke seals on door frame. GENERATED ON 6/4/26, 7:06 AM 11 OF 13 Portable Fire Extingusihers S:o: s Code Description Fail 906.2-General requirements. Portable fire extinguishers shall be selected,installed and Location:TSC area maintained in accordance with this section and NFPA 10. Comments:Provide properly sized fire extinguisher in area hung on Exceptions:1.The distance of travel to reach an extinguisher wall bracket no more than 5ft from floor to top of extinguisher shall not apply to the spectator seating portions of Group A-5 occupancies.2.Thirty-day inspections shall not be required and maintenance shall be allowed to be once every 3 years for dry-chemical or halogenated agent portable fire extinguishers that are supervised by a listed and approved electronic monitoring device,provided that all of the following conditions are met:2.1.Electronic monitoring shall confirm that extinguishers are properly positioned,properly charged and unobstructed.2.2.Loss of power or circuit continuity to the electronic monitoring device shall initiate a trouble signal.2.3.The extinguishers shall be installed inside of a building or cabinet in a noncorrosive environment. 2.4.Electronic monitoring devices and supervisory circuits shall be tested every 3 years when extinguisher maintenance is performed.2.5.A written log of required hydrostatic test dates for extinguishers shall be maintained by the owner to verify that hydrostatic tests are conducted at the frequency required by NFPA 10.3.In Group 1-3,portable fire extinguishers shall be permitted to be located at staff locations. Fail 906.2-General requirements. Portable fire extinguishers shall be selected,installed and Location:All extinguishers in building maintained in accordance with this section and NFPA 10. Comments:Annual service to all extinguishers due in July 2026 Exceptions:1.The distance of travel to reach an extinguisher shall not apply to the spectator seating portions of Group A-5 occupancies.2.Thirty-day inspections shall not be required and maintenance shall be allowed to be once every 3 years for dry-chemical or halogenated agent portable fire extinguishers that are supervised by a listed and approved electronic monitoring device,provided that all of the following conditions are met:2.1.Electronic monitoring shall confirm that extinguishers are properly positioned,properly charged and unobstructed.2.2.Loss of power or circuit continuity to the electronic monitoring device shall initiate a trouble signal.2.3.The extinguishers shall be installed inside of a building or cabinet in a noncorrosive environment. 2.4.Electronic monitoring devices and supervisory circuits shall be tested every 3 years when extinguisher maintenance is performed.2.5.A written log of required hydrostatic test dates for extinguishers shall be maintained by the owner to verify that hydrostatic tests are conducted at the frequency required by NFPA 10.3.ln Group 1-3,portable fire extinguishers shall be permitted to be located at staff locations. GENERATED ON 6/4/26, 7:06 AM 12 OF 13 `D Statement of Fees FEE Invoice Date Inspection Fee Date Paid Amount Paid NIA $610.00 Invoice Number Check Number Transaction Number N/A N/A NIA GENERATED ON 6/4/26, 7:06 AM 13 OF 13 OF WA TF INVOICE DATE DUE DATE INVOICE# TOTAL DUE 0 06/10/2026 07/15/2026 2026-00000557 $610.00 .. .. O 9S 1tf1��5 Customer#: 4661 Please Make Check Payable and Remit To: City of Waterloo ATTN: City Clerk/Accounts Receivable TARGET STORE T1792 715 Mulberry St PO BOX 111 WATERLOO, IA 50703 MINNEAPOLIS, MN 55440 Amount Enclosed: DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT KEEP THIS PORTION FOR YOUR RECORDS COMMERCIAL FIRE INSPECTION-1501 E. SAN MARNAN DR- I FOR BILLING INQUIRY: (319)291-4323 06/01/2026 Description Total Price INSPECTION 100,000 $600.00 OCCUPANCY FEE $10.00 CUSTOMER# I BILLING DATE' DUE DATE INVOICE# 4661 06/10/2026 07/15/2026 2026-00000557 CHARGES $610.00 Less Prepayment $0.00 Total Due —÷ $610.00 City of Waterloo Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of Administrative Services Offset Program if not paid in full within ninety days.