HomeMy WebLinkAboutTARGET SUPER STORE Waterloo Fire Rescue
Inspection Report
425 E.3rd Street
«<,, o' Target Super Store-1501 E San Marnan DR,BLDG 1501 E San Marnan Dr,Waterloo
IA 50702
INSPECTION DETAILS
Inspection Date Inspection type Inspection Number
�' -=
06/01/2026 Annual Inspection(1Yr) (Q,IU . 22017
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA N/A N/A
Other Inspectors
N/A
SUMMARY OF INSPECTION
050 C27 ® 10
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN
06125/2026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-0610112026 @ 12:24
$610 annual inspection fee
BRAD BALDWIN-06/0112026 @ 12:25
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-06/0112026 @ 12:25
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-0610112026 @ 12:25
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Kyle(2025)floor manager Date: BRAD BALDWIN 06104/2026
CHECKLISTS
GENERATED ON 6/4/26, 7:06 AM 1 OF 13
Means of Egress
S;r.n,s Code Description
Fail 1010.1.3-Door opening force Forces to unlatch and open
doors. Location:North side emergency exit doors(left door)
The force for pushing or pulling open interior swinging Comments:Repair or replace door that failed to open.Replacement
egress doors,other than fire doors,shall not exceed 5 of door requires permit and inspection obtained.
pounds(22 N).These forces do not apply to the force
required to retract latch bolts or disengage other devices that
hold the door in a closed position.For other swinging doors,
as well as sliding and folding doors,the door latch shall
release when subjected to a 15-pound(67 N)force.The door
shall be set in motion when subjected to a 30-pound(133 N)
force.The door shall swing to a full-open position when
subjected to a 15-pound(67 N)force.The forces to unlatch
doors shall comply with the following:1.Where door
hardware operates by push or pull,the operational force to
unlatch the door shall not exceed 15 pounds(66.7 N).2.Where
door hardware operates by rotation,the operational force to
unlatch the door shall not exceed 28 inch-pounds(315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated,other than doors required to be fire rated,the force
for pushing or pulling open the door shall not exceed 5
pounds(22 N).2.For other swinging doors,sliding doors or
folding doors,and doors required to be fire rated,the door
shall require not more than a 30-pound(133 N)force to be set
in motion and shall move to a full-open position when
subjected to not more than a 15-pound(67 N)force.
GENERATED ON 6/4/26, 7:06 AM 2 OF 13
Additional Codes
5!a?es. Code Descripfioo
Fail 102.4-Application of building code.
The design and construction of new structures shall comply Location:HVAC permit
with the International Building Code,and any alterations, Comments:Contractor(Arris Inc)shall obtain inspection of work
additions,changes in use or changes in structures required when completed
by this code,which are within the scope of the International
Building Code,shall be made in accordance therewith.
Fail 102.4-Application of building code.
The design and construction of new structures shall comply Location:Electrical permit
with the International Building Code,and any alterations, Comments:Contractor(Superior Lighting Inc)shall obtain inspection
additions,changes in use or changes in structures required of work when completed
by this code,which are within the scope of the International
Building Code,shall be made in accordance therewith.
Fail 102.4-Application of building code.
The design and construction of new structures shall comply Location:Electrical permit(for HVAC)
with the International Building Code,and any alterations, Comments:Contractor(Steve's Electric)shall obtain inspection of
additions,changes in use or changes in structures required work when completed.
by this code,which are within the scope of the International
Building Code,shall be made in accordance therewith.
Fail 507.5.3-Private fire service mains and water tanks.
Private fire service mains and water tanks shall be Location:Private fire hydrants
periodically inspected,tested and maintained in accordance Comments:Provide annual hydrants inspection and contractors
with NFPA 25 at the following intervals:1.Private fire hydrants report including any deficiencies corrected to Compliance Engine
of all types:Inspection annually and after each operation;
flow test and maintenance annually.2.Fire service main
piping:Inspection of exposed,annually;flow test every 5
years.3.Fire service main piping strainers:Inspection and
maintenance after each use.Records of inspections,testing
and maintenance shall be maintained.
Fail 907.6.6-Monitoring.
Fire alarm systems required by this chapter or by the Location:Main fire alarm control panel room
International Building Code shall be monitored by an Comments:Smoke monitoring device required installed above main
approved supervising station in accordance with NFPA 72. fire alarm panel.
Exception:Monitoring by a supervising station is not required
for:1.Single-and multiple-station smoke alarms required by
Section 907.2.11.2.Smoke detectors in Group 1-3
occupancies.3.Automatic sprinkler systems in one-and two-
family dwellings.
GENERATED ON 6/4/26, 7:06 AM 3 OF 13
Emergency Equipment
S-ards Code Description
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:All emergency egress lighting
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:All egress lights shall be tested and repaired if
nonfunctional,provide documentation of all lighting working properly
to inspector including signed and dated.
Fail 1203.2.6-Exit signs.
Emergency power shall be provided for exit signs as required Location:All exit signs
in Section 1013.6.3.The system shall be capable of powering Comments:All exit signs shall be tested and repaired if
the required load for a duration of not less than 90 minutes. nonfunctional,provide documentation of all signage working
properly to inspector including signed and dated.
Fail 1203.4.3-Records.
Records of the inspection,testing and maintenance of Location:Emergency backup generator
emergency and standby power systems shall include the date
Comments:Provide annual inspection and report to be uploaded to
of service,name of the servicing technician,a summary of
Compliance Engine including any deficiencies corrected.Currently
conditions noted and a detailed description of any conditions due by 6125126
requiring correction and what corrective action was taken.
Such records shall be maintained.
General Housekeeping
S[a:us Code Description
Fail 315.3.1-Ceiling clearance.
Storage shall be maintained 2 feet(610 mm)or more below Location:Deli back storage
the ceiling in nonsprinklered areas of buildings or not less Comments:Storage within 18 inches below sprinkler heads shall be
than 18 inches(457 mm)below sprinkler head deflectors in lowered or removed not including storage along walls.
sprinklered areas of buildings.Exceptions:1.The 2-foot(610
mm)ceiling clearance is not required for storage along walls
in nonsprinklered areas of buildings.2.The 18-inch(457 mm)
ceiling clearance is not required for storage along walls in
areas of buildings equipped with an automatic sprinkler
system in accordance with Section 903.3.1.1,903.3.1.2 or
903.3.1.3.
Fail 315.3.2-Means of egress.
Combustible materials shall not be stored in exits or Location:Bottom of stairway leading to"Hussman House"
enclosures for stairways and ramps.Combustible materials in Comments:Remove storage obstructing path to stairway,would
the means of egress during construction,demolition, approve floor markings installed where storage shall not be stored.
remodeling or alterations shall comply with Section 3312.3.
GENERATED ON 6/4/26, 7:06 AM 4 OF 13
Fire Sprinkler System
szasu; Code Descripoc:
Fail 5.2.1-Annual sprinkler system inspection
Sprinklers shall be inspected at least annually by licensed Location:Sprinkler system
contractor
Comments:Provide annual sprinkler inspection and contractors
report including any deficiencies corrected to Compliance Engine
Fail 5.2.1.1.5-Missing escutcheons
Escutcheons and coverplates for recessed,flush,and Location:Starbucks back storage
concealed sprinklers shall be replaced if found missing Comments:Replace missing escutcheon ring.
during the inspection.
Fail 5.2.1.1.5-Missing escutcheons
Escutcheons and coverplates for recessed,flush,and Location:Mechanical room near cash office
concealed sprinklers shall be replaced if found missing Comments:Loose sprinkler escutcheon above water heater shall be
during the inspection. corrected.
r
Fail 903.3.3-Obstructed locations.
Automatic sprinklers shall be installed with regard to Location:Back stock area
obstructions that will delay activation or obstruct the water Comments:Remove water leak umbrella above shelving used for
distribution pattern and shall be in accordance with the previous roof water leak obstructing sprinkler coverage.Roof leak
applicable automatic sprinkler system standard that is being was reportedly repaired.
used.Automatic sprinklers shall be installed in or under
covered kiosks,displays,booths,concession stands or
equipment that exceeds 4 feet(1219 mm)in width.Not less
than a 3-foot(914 mm)clearance shall be maintained between
automatic sprinklers and the top of piles of combustible
fibers.Exception:Kitchen equipment under exhaust hoods
protected with a fire-extinguishing system in accordance with
Section 904.
GENERATED ON 6/4/26, 7:06 AM 5 OF 13
Fail 903.3.3-Obstructed locations.
Automatic sprinklers shall be installed with regard to Location:Back stock area
obstructions that will delay activation or obstruct the water Comments:Product on shelving and storage above the maximum
distribution pattern and shall be in accordance with the allowed 15 ft shall be lowered.
applicable automatic sprinkler system standard that is being
used.Automatic sprinklers shall be installed in or under
covered kiosks,displays,booths,concession stands or
equipment that exceeds 4 feet(1219 mm)in width.Not less
than a 3-foot(914 mm)clearance shall be maintained between
automatic sprinklers and the top of piles of combustible
fibers.Exception:Kitchen equipment under exhaust hoods
protected with a fire-extinguishing system in accordance with
Section 904.
Fire Service Features
;. .. Co- Description
Fail 509.2-Equipment access.
Approved access shall be provided and maintained for all fire Location:Back stock area-Sprinkler piping
protection system equipment to permit immediate safe Comments:Remove storage from within 36"of sprinkler piping
operation and maintenance of such equipment.Storage,trash equipment
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
1
1I.
i. i
-r. , t/1``
AYR
GENERATED ON 6/4/26, 7:06 AM 6 OF 13
Electrical Safety
s[atus Code Description
Fail 603.2.2-Unapproved conditionsOpen electrical terminations.
Open junction boxes and open-wiring splices shall be Location:Upper level"Hussman House"-Above"Rack A"
prohibited.Approved covers shall be provided for all switch Comments:Wires shall be properly capped with cover installed on
and electrical outlet boxes, box
•
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Cash recycler room
for permanent wiring and shall be listed and labeled in
accordance with UL 817.Extension cords and flexible Comments:Appliances including motors and/or heating elements
cordsshallaccordant not be affixed to structures,extended through shall be plugged directly to a permanent wall outlet.Remove cash
recycler from extension cord and power strip and relocate to plug
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or directly to wall outlet
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
GENERATED ON 6/4/26, 7:06 AM
7 OF 13
Fire Resistant Construction Maintenance
5[_tus Cafe Description
Fail 704.1-Maintaining protection.
Where required when the building was originally constructed, Location:Starbucks back storage room
materials and systems used to protect joints and voids in the Comments:Carefully remove paint covering fire rating door labels to
following locations shall be maintained.The materials and avoid removing label information.Missing or damaged labels
systems shall be securely attached to or bonded to the requires door to be re-certified as fire rated or replaced with
adjacent construction,without openings visible through the obtaining permit and inspection.Also,door is required to self-shut
construction.1.Joints in or between fire-resistance-rated and latch,remove obstructions to door closing and install fire rated
walls,floors or floorlceiling assemblies and roof or smoke seals on door frame.
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall.4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall.5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall.6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall.7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly.Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed.Where the system design number is known,the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
I�„,�
: : ':
,,,,,,_
4/l s%% 5_,.„
�t,I/yiJrri>u/,,
i.
,._,...,
, ,..,......
,,,,,,.: , ,
, , i,„„. „..,...,,______,„.„,, ,..
rl i
i/►.' It,
tom`
8 OF 7
GENERATED ON 6/4/26, 7:06 AM
Fail 704.1-Maintaining protection.
Where required when the building was originally constructed, Location:Cash office hallway entrance
materials and systems used to protect joints and voids in the Comments:Carefully remove paint covering fire rating door labels to
following locations shall be maintained.The materials and avoid removing label information.Missing or damaged labels
systems shall be securely attached to or bonded to the requires door to be re-certified as fire rated or replaced with
adjacent construction,without openings visible through the
obtaining permit and inspection.
construction.1.Joints in or between fire-resistance-rated
walls,floors or floorlceiling assemblies and roof or
rooflceiling assemblies.2.Joints in smoke barriers.3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall.4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall.5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall.6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall.7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly.Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed.Where the system design number is known,the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
1/4
�S Ni 0
11.
•
Ya cH
4'4
GENERATED ON 6/4/26, 7:06 AM 9 OF 13
Fail 704.1-Maintaining protection.
Where required when the building was originally constructed, Location:Control Room
materials and systems used to protect joints and voids in the Comments:Provide missing fire rated smoke seals on door frame
following locations shall be maintained.The materials and
systems shall be securely attached to or bonded to the
adjacent construction,without openings visible through the
construction.1.Joints in or between fire-resistance-rated
walls,floors or floorlceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall.4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall.5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall.6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall.7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly.Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed.Where the system design number is known,the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Fail 704.1-Maintaining protection.
Where required when the building was originally constructed, Location:Cash recycler room
materials and systems used to protect joints and voids in the Comments:Provide missing fire rated smoke seals on door frame
following locations shall be maintained.The materials and
systems shall be securely attached to or bonded to the
adjacent construction,without openings visible through the
construction.1.Joints in or between fire-resistance-rated
walls,floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall.4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall.5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall.6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall.7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly.Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed.Where the system design number is known,the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
GENERATED ON 6/4/26, 7:06 AM 10 OF 13
Fail 704.1-Maintaining protection.
Where required when the building was originally constructed, Location:Electrical equipment room near Cash Recycler
materials and systems used to protect joints and voids in the Comments:Provide missing fire rated smoke seals on door frame
following locations shall be maintained.The materials and
systems shall be securely attached to or bonded to the
adjacent construction,without openings visible through the
construction.1.Joints in or between fire-resistance-rated
walls,floors or floor/ceiling assemblies and roof or
rooflceiling assemblies.2.Joints in smoke barriers.3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall.4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall.5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall.6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall.7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly.Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed.Where the system design number is known,the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Fail 705.2.4-Door operation.
Swinging fire doors shall close from the full-open position Location:Cash office entrance hallway
and latch automatically. Comments:Repair or replace door that failed to self-shut and latch
today.Also,install fire rated smoke seals on door frame.
GENERATED ON 6/4/26, 7:06 AM 11 OF 13
Portable Fire Extingusihers
S:o: s Code Description
Fail 906.2-General requirements.
Portable fire extinguishers shall be selected,installed and Location:TSC area
maintained in accordance with this section and NFPA 10. Comments:Provide properly sized fire extinguisher in area hung on
Exceptions:1.The distance of travel to reach an extinguisher wall bracket no more than 5ft from floor to top of extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.In Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.
Fail 906.2-General requirements.
Portable fire extinguishers shall be selected,installed and Location:All extinguishers in building
maintained in accordance with this section and NFPA 10. Comments:Annual service to all extinguishers due in July 2026
Exceptions:1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.ln Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.
GENERATED ON 6/4/26, 7:06 AM 12 OF 13
`D Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $610.00
Invoice Number Check Number Transaction Number
N/A N/A NIA
GENERATED ON 6/4/26, 7:06 AM 13 OF 13
OF WA TF INVOICE DATE DUE DATE INVOICE# TOTAL DUE
0 06/10/2026 07/15/2026 2026-00000557 $610.00
.. ..
O
9S 1tf1��5
Customer#: 4661 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
TARGET STORE T1792 715 Mulberry St
PO BOX 111 WATERLOO, IA 50703
MINNEAPOLIS, MN 55440
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION-1501 E. SAN MARNAN DR- I FOR BILLING INQUIRY: (319)291-4323
06/01/2026
Description
Total Price
INSPECTION 100,000 $600.00
OCCUPANCY FEE
$10.00
CUSTOMER# I BILLING DATE' DUE DATE INVOICE#
4661 06/10/2026 07/15/2026 2026-00000557 CHARGES
$610.00
Less Prepayment $0.00
Total Due —÷ $610.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.