HomeMy WebLinkAboutKWIK TRIP #732 4P1011.00 Waterloo Fire Rescue
4:11 fr\ Inspection Report 425 E. 3rd Street
Kwik Trip #732 - 324 Fletcher AVE, BLDG 324 Fletcher Ave, Waterloo IA 50701
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
06108/2026 Annual Inspection (1Yr) NZel0 17419
Lead Inspector Shift Station Unit
BRAD BALDWIN N/A NIA N/A
Other Inspectors
N/A
SUMMARY OF INSPECTION
41 0 7 ® 28
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN 07101/2026
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 06/09/2026 @ 07:57
• $80 annual inspection fee
BRAD BALDWIN - 06/09/2026 @ 07:57
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 06109/2026 @ 07:57
• Provide corrections to avoid progressive re-inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 06/09/2026 @ 07:58
• If all corrections are made before the scheduled re-inspection date, you can call to set up an earlier re-inspection. Normal operating hours for
inspections & re-inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re-inspections. Re-
inspection fees start at $100, then $150, and $200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Alicia (2025) District Manager Date: BRAD BALDWIN 06/09/2026
CHECKLISTS
GENERATED ON 6/9/26, 8 :36 AM 1 OF 6
Additional Codes
Sta:us Code Description
Fail 2303.2-Emergency disconnect switches.
OAn approved emergency disconnect switch shall be provided Location:Interior&Exterior Fuel Emergency Shut-Off Button
at an approved location to stop the transfer of fuel to the fuel Locations
dispensers in the event of a fuel spill or other emergency.The Comments:Signage shall be installed in approved locations near
emergency disconnect switch for exterior fuel dispensers Shut Offs.
shall be provided with ready access and shall be located
within 100 feet(30 480 mm)of,but not less than 20 feet(6096
mm)from,the fuel dispensers.For interior fuel-dispensing
operations,the emergency disconnect switch shall be
provided with ready access and be installed at an approved
location.Such devices shall be distinctly labeled as:
"EMERGENCY FUEL SHUTOFF."Signs shall be
provided in approved locations.
Fail 603.1-General.
vElectrical equipment,wiring and systems required by this Location:Back stock area-CO2 compressor
code or the International Building Code shall be installed, Comments:Remove fountain drinks CO2 compressor plugged to
used and maintained in accordance with NFPA 70 and extension cord.Relocate to plug directly to wall outlet or add outlet,
Sections 603.2 through 603.10. adding outlet requires licensed electrical contractor obtaining permit
and inspection
2 OF 6
GENERATED ON 6/G/26, 8:36 AM
Electrical Safety
Status Code Description
Fail 603.2.2-Unapproved conditionsOpen electrical terminations.
OOpen junction boxes and open-wiring splices shall be Location:South exterior-Equipment labeled"Deli Freezer"
prohibited.Approved covers shall be provided for all switch
and electrical outlet boxes. Comments:Opening in box shall be corrected.
0.4. to
*, k,
x
t if A.. Fs' ...... ... ' ... .**'. 11%01110
t `
`®
Fail 603.4-Working space and clearancesclearance.
A working space of not Working space around electrical Location:Car wash-mechanical room
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or Comments:Remove obstructions to clearances from electric panel.
36"in front of and 30"horizontally shall be maintained clear from
less,and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts.The minimum required working space Panels.
shall be not less than 30 inches(762 mm)in width,36 inches
(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the
electrical service equipment is wider than 30 inches(762
mm),the minimum working space shall be not less than the
width of the equipment.Storage of materials shall not be
located within the designated working space.Exceptions:1.
Where other dimensions are required or allowed by NFPA 70.
2.Access openings into attics or under-floor areas that
provide a minimum clear opening of 22 inches(559 mm)by 30
inches(762 mm).
GENERATED ON 6/9/26, 9:36 AM
3 OF 6
Fail 603.4-Working space and clearancesclearance.
A working space of not Working space around electrical Location:Back stock area
equipment shall be provided in accordance with Section Comments:REPEAT VIOLATION:Remove all storage on floor in front
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or of electric panels.Approved marking paint or tape shall be installed
less,and Section 110.33 of NFPA 70 for electrical equipment on floor in front of panels noting"No Storage Allowed In This Area"
rated over 1,000 volts.The minimum required working space
shall be not less than 30 inches(762 mm)in width,36 inches
(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the
electrical service equipment is wider than 30 inches(762
mm),the minimum working space shall be not less than the
width of the equipment.Storage of materials shall not be
located within the designated working space.Exceptions:1.
Where other dimensions are required or allowed by NFPA 70.
2.Access openings into attics or under-floor areas that
provide a minimum clear opening of 22 inches(559 mm)by 30
inches(762 mm).
l 1
II ��f ^�/I ' . •
tf ti 1_ .i,! ,� I f
tr ti z
t k' _Yf
1
t I
: era,+
rkf •, ,boisib
: 4. . ; k
1_ if
GENERATED ON 6/9/26, 8:36 AM
Portable Fire Extingusihers
Status Code Description
Fail 906.2-General requirements.
Portable fire extinguishers shall be selected,installed and Location:All extinguishers
maintained in accordance with this section and NFPA 10. Comments:Provide annual service to all extinguishers in building.
Exceptions:1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.In Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.
Fail 906.6-Unobstructed and unobscured.
QPortable fire extinguishers shall not be obstructed or Location:CNG area near carwash
obscured from view.In rooms or areas in which visual Comments:Fire extinguisher sign faded shall be replaced.
obstruction cannot be completely avoided,means shall be
provided to indicate the locations of extinguishers.
GENERATED ON 6/9/26, 8:36 AM 5 OF 6
Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $80.00
Invoice Number Check Number Transaction Number
NIA NIA NIA
GENERATED ON 6/9/26, 8:36 AM 6 OF 6
Of WA .� INVOICE DATE DUE DATE INVOICE# TOTAL DUE
06/10/2026 07/15/2026 2026-00000567 $80.00
u O
• '
•
0/t11100
Customer#: 3360 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
KWIK STAR#732 715 Mulberry St
1626 OAK ST WATERLOO, IA 50703
LA CROSSE, WI 54602
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION-324 FLETCHER AVE-06/08/2026 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
3360 06/10/2026 07/15/2026 2026-00000567 $80.00
Less Prepayment $0.00
Total Due-+ $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.