HomeMy WebLinkAboutBROADWAY LIQUOR ,r�A,oG Waterloo Fire Rescue
N.**4 Inspection Report 425 E.3rd Street
•`,E Broadway Liquor-821 Broadway ST,BLDG 821 Broadway St,Waterloo IA 50703
INSPECTION DETAILS
Inspection Date Inspection Type �v Inspection Number
0410812026 Annual Inspection(lYr) * 4 ? 21675
Lead Inspector Shift Station Unit
BRAD BALDWIN N/A N/A N/A
Other Inspectors
N/A
SUMMARY OF INSPECTION
0 44Qs, 5 ® 25
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN
04/2912026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-04/0812026 @ 15:25
$80 annual inspection fee
BRAD BALDWIN-04/0812026 @ 15:39
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-04/08/2026 @ 15:39
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-04/0812026 @ 15:39
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completededpost stinspection
Muhammad Shahaz Date: BRAD BALDWIN 04108/2026
CHECKLISTS
GENERATED ON 4/8/26, 3:42 PM 1 OF 5
Additional Codes
s=dt-zs Code Description
Fail 603.1-General.
Electrical equipment,wiring and systems required by this Location:Kitchen food warmer
code or the International Building Code shall be installed, Comments:Remove food wanner plugged to power strip.Appliance
used and maintained in accordance with NFPA 70 and shall plug directly to wall outlet.
Sections 603.2 through 603.10.
�a cf
A
F
3
w
2 OF 5
GENERATED ON 4/8/26, 3:42 PM
Commercial Cooking Hood Suppression System
Star.,. Code D«e>cripoon
Fail 606.3.3-Cleaning.
(>: Hoods,grease-removal devices,fans,ducts and other Location:Kitchen hood exhaust
appurtenances shall be cleaned at intervals as required by Comments:Exhaust system cleaning 173 days past due as of 4/8126.
Sections 606.3.3.1 through 606.3.3.3. Provide cleaning and report to be uploaded to Compliance Engine
with any deficiencies corrected.Last tagged for service in April 2025
by AKA Services
Fail 606.3.3.1-Inspection.
Hoods,grease-removal devices,fans,ducts and other Location:Kitchen exhaust hood suppression system
appurtenances shall be inspected at intervals specified in Comments:Suppression system inspection 179 days past due as of
Table 606.3.3.1 or as approved by the fire code official. 4/8/26.Provide suppression system inspection report with any
Inspections shall be completed by qualified individuals. deficiencies corrected.Contractor must upload report to Compliance
Engine.Last tagged for service in April 2025
Fail 606.3.3.2-Grease accumulation.
If during the inspection it is found that hoods,grease-removal Location:Kitchen
devices,fans,ducts or other appurtenances have an Comments:Clean grease filters,currently dripping
grease.Excess
accumulation of grease,such components shall be cleaned in grease also noted on gas lines and wall behind cooking equipment
accordance with ANSI/IKECA C10.
a;
x .
s •
„ ,. ,, 4:ez:, ',.,.."'...-: '
GENERATED ON 4/8/26, 3:42 PM 3 OF 5
Portable Fire Extingusihers
Status Code Description
Fail 906.2-General requirements.
Portable fire extinguishers shall be selected,installed and Location:All fire extinguishers
maintained in accordance with this section and NFPA 10. Comments:Provide annual service to all extinguishers,currently due
Exceptions:1.The distance of travel to reach an extinguisher
now.
shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.In Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.
GENERATED ON 4/8/26, 3:42 P. 4 OF 5
a
o Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $80.00
Invoice Number Check Number Transaction Number
NIA NIA NIA
GENERATED ON 4/8/26, 3:42 PM 5 OF 5
OF W 4 . INVOICE DATE DUE DATE INVOICE# TOTAL DUE
yt:Z (0 06/10/2026 07/15/2026 2026-00000536 $80.00
.,rain.•.
• II 11 1 •1 •
T-- T 0
Customer#: 13529 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
BROADWAY LIQUOR 715 Mulberry St
821 BROADWAY ST WATERLOO, IA 50703
WATERLOO, IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION-821 BROADWAY ST-04/08/2026 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
13529 06/10/2026 07/15/2026 2026-00000536 $80.00
Less Prepayment $0.00
Total Due—> $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.