HomeMy WebLinkAboutLIQUOR & TOBACCO OUTLET Waterloo Fire Rescue
—490
•N`°° Inspection Report
425 E.3rd Street
<,u. Liquor&Tobacco Outlet-2844 University AVE,BLDG 2844 University Ave,Waterloo
IA 50701
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
06/05/2026 Annual Inspection(1Yr) kr A gOW 16982
Lead Inspector Shift Station
Unit
BRAD BALDWIN N/A NIA NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
031 /08 ® 36
Passed codes Failed codes. N/A codes
NEXT STEPS
Please direct questions about your Inspection to:
Reinspection Date
BRAD BALDWIN
brad.baldwin@waterloo-ia.org,3192914319
07I01I2026
GENERAL NOTES
BRAD BALDWIN-06108/2026 @ 08:18
•$80 annual inspection fee
BRAD BALDWIN-06/08/2026 @ 08:18
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-06/08/2026 @ 08:18
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-06108/2026 @ 08:18
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
USMAN MAQBOLL(2025) Date: BRAD BALDWIN 06108/2026
CHECKLISTS
GENERATED ON 6/8/26, 9:00 AM
1 OF 7
1
Means of Egress
Status Code Description
Fail 1010.2.5-Bolt locks.
Manually operated flush bolts or surface bolts are not Location:Back exit
permitted.Exceptions:i.On doors not required for egress in Comments:Removing exit signage above back exit door will allow
individual dwelling units or sleeping units.2.Where a pair of bolt lock to remain.Bolt lock is not permitted on a marked exit.
doors serves a storage or equipment room,manually
operated edge-or surface-mounted bolts are permitted on the
inactive leaf.3.Where a pair of doors serves an occupant load
of less than 50 persons in a Group B,F or S occupancy,
manually operated edge-or surface-mounted bolts are
permitted on the inactive leaf.The inactive leaf shall not
contain doorknobs,panic bars or similar operating hardware.
4.Where a pair of doors serves a Group B,F or S occupancy,
manually operated edge-or surface-mounted bolts are
permitted on the inactive leaf provided that such inactive leaf
is not needed to meet egress capacity requirements and the
building is equipped throughout with an automatic sprinkler
system in accordance with Section 903.3.1.1.The inactive leaf
shall not contain doorknobs,panic bars or similar operating
hardware.5.Where a pair of doors serves patient care rooms
in Group 1-2 occupancies,self-latching edge-or surface-
mounted bolts are permitted on the inactive leaf provided that
the inactive leaf is not needed to meet egress capacity
requirements and the inactive leaf shall not contain
doorknobs,panic bars or similar operating hardware.
2 OF 7
GENERATED ON 6/8/26, 9:00 AM
- Additional Codes
Status Code Description
Fail 1010.2.4-Locks and latches.
OLocks and latches shall be permitted to prevent operation of Location:Front exit
doors where any of the following exist:1.Places of detention Comments:Install approved signage on door stating"This door shall
or restraint.2.In Group I-1,Condition 2 and Group 1-2
occupancies where the clinical needs of persons receiving remain unlocked during business hours"
care require containment or where persons receiving care
pose a security threat,provided that all clinical staff can
readily unlock doors at all times,and all such locks are keyed
to keys carried by all clinical staff at all times or all clinical
staff have the codes or other means necessary to operate the
locks at all times.2.3.In buildings in occupancy Group A
having an occupant load of 300 or less,Groups B,F,M and S,
and in places of religious worship,the main door or doors are
permitted to be equipped with key-operated locking devices
from the egress side provided:2.1.3.1.The locking device is
readily distinguishable as locked.2.2.3.2.A readily visible
durable sign is posted on the egress side on or adjacent to
the door stating:"THIS DOOR TO REMAIN UNLOCKED WHEN
THIS SPACE IS OCCUPIED."The sign shall be in letters 1 inch
(25 mm)high on a contrasting background.2.3.3.3.The use
of the key-operated locking device is revocable by the fire
code official for due cause.3.4.Where egress doors are used
in pairs,approved automatic flush bolts shall be permitted to
be used,provided that the door leaf having the automatic
flush bolts does not have a doorknob or surface-mounted
hardware.4.5.Doors from individual dwelling or sleeping
units of Group R occupancies having an occupant load of 10
or less are permitted to be equipped with a night latch,dead
bolt or security chain,provided such devices are openable
from the inside without the use of a key or tool.5.6.Fire
doors after the minimum elevated temperature has disabled
the unlatching mechanism in accordance with listed fire door
test procedures.6.7.Doors serving roofs not intended to be
occupied shall be permitted to be locked,preventing entry to
the building from the roof.8.Other than egress courts,where
occupants must egress from an exterior space through the
building for means of egress,exit access doors shall be
permitted to be equipped with an approved locking device
where installed and operated in accordance with all of the
following:8.1.The maximum occupant load shall be posted
where required by Section 1004.9.Such sign shall be
permanently affixed inside the building and shall be posted in
a conspicuous space near all the exit access doorways.8.2.A
weatherproof telephone or two-way communication system
installed in accordance with Sections 1009.8.1 and 1009.8.2
shall be located adjacent to not less than one required exit
access door on the exterior side.8.3.The egress door locking
device is readily distinguishable as locked and shall be a key-
operated locking device.8.4.A clear window or glazed door
opening,not less than 5 square feet(0.46 m2)in area,shall
be provided at each exit access door to determine if there are
occupants using the outdoor area.8.5.A readily visible
durable sign shall be posted on the interior side on or
adjacent to each locked required exit access door serving the
exterior area stating:"THIS DOOR TO REMAIN UNLOCKED
WHEN THE OUTDOOR AREA IS OCCUPIED."The letters on
the sign shall be not less than 1 inch(25.4 mm)high on a
contrasting background.8.6.The occupant load of the
occupied exterior area shall not exceed 300 occupants in
accordance with Section 1004.9.Locking devices are
permitted on doors to balconies,decks or other exterior
spaces serving individual dwelling or sleeping units.
10.Locking devices are permitted on doors to balconies,
decks or other exterior spaces of 250 square feet(23.23
m2)or less,serving a private office space.
GENERATED ON 6/8/26, 9:00 AM
3 OF 7
S
Emergency Equipment
Status Code Description
Fail 1203.2.6-Exit signs.
OEmergency power shall be provided for exit signs as required Location:Back exit
in Section 1013.6.3.The system shall be capable of powering Comments:Per(interim)Building Official Jennifer Sparks and
the required load for a duration of not less than 90 minutes. building occupancy:2nd exit not required.Would approve to remove
exit signage at back exit door and interior doorway.Recommendation
to relocate exit sign with arrow directing from back storage to front
exit egress path.
4 OF 7
GENERATED ON 6/8/26, 9:00 AM
. Electrical Safety
Status Code Description
Fail 603.2.2-Unapproved conditionsOpen electrical terminations.
OOpen junction boxes and open-wiring splices shall be Location:Outside back exit door
prohibited.Approved covers shall be provided for all switch
and electrical outlet boxes. Comments:Provide missing weather rated outlet cover
•
Fail 603.5.3-Installation.
Relocatable power tap cords shall not extend through walls, Location:Front wall
ceilings,floors,under doors or floor coverings,or be subject
Comments:Power strip zip tied to conduit shall be corrected.Power
to environmental or physical damage.
strip shall be properly mounted to avoid using wiring as support.
.4, }, j
1 .
Al2
•
ki
1
f'�
GENERATED ON 6/8/26, 9:00 AM
5 OF 7
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Behind counter on Marlboro display shelving
for permanent wiring and shall be listed and labeled in Comments:Remove extension cords to lighted signage.May replace
accordance with UL 817.Extension cords and flexible with power strip with manual reset properly mounted for low wattage
cordsshall not be affixed to structures,extended through usage only
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:ATM machine
for permanent wiring and shall be listed and labeled in Comments:Remove white extension cord to ATM machine.Would
accordance with UL 817.Extension cords and flexible approve to replace with power strip with manual reset properly
cordsshall not be affixed to structures,extended through mounted for low wattage usage only
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Portable Fire Extingusihers
Description
Fail 906.2-General requirements.
Portable fire extinguishers shall be selected,installed and Location:Fire extinguishers
maintained in accordance with this section and NFPA 10. Comments:Provide annual service to all extinguishers,currently
Exceptions:1.The distance of travel to reach an extinguisher past due as of May 2026
shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.In Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.
6 OF 7
GENERATED ON 6/8/26, 9:00 AM
•
Ed Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $80.00
Invoice Number Check Number Transaction Number
NIA NIA NIA
GENERATED ON 6/8/26, 9:00 AM 7 OF 7
W 4 rF INVOICE DATE DUE DATE INVOICE# TOTAL DUE
06/10/2026 07/15/2026 2026-00000534 $80.00
u /who !'fa Q
) O
1V17'3
Customer#: 14254 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
LIQUOR AND TOBACCO OUTLET 715 Mulberry St
2844 UNIVERSITY AV WATERLOO, IA 50703
WATERLOO, IA 50701
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION-2844 UNIVERSITY AVE- FOR BILLING INQUIRY: (319)291-4323
06/05/2026
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
14254 06/10/2026 07/15/2026 2026-00000534 $80.00
Less Prepayment $0.00
Total Due —> $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.