HomeMy WebLinkAboutCASEY'S GENERAL STORE Waterloo Fire Rescue
�•T Inspection Report
��� 425 E.3rd Street
Casey's General Store#2867-2424 Ranchero RD,BLDG 2867 Ranchero Rd,
Waterloo IA 50701
INSPECTION DETAILS
inspection Date Inspection Type Inspection Number
06/03/2026 Annual Inspection(1Yr) REINSPECTION IS 1 4' .ced 16971-R2
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA N/A N/A
Other Inspectors
NIA
SUMMARY OF INSPECTION
CGo 02 06
Passed codes Resolved violations Failed codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN
06/25/2026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-05/12/2026 @ 14:37
$80 annual inspection fee
BRAD BALDWIN-05/1212026 @ 14:37
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-05112/2026 @ 14:37
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-05112/2026 @ 14:37
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
BRAD BALDWIN-05/12/2026 @ 14:37
$100 re-inspection fee,failure to complete corrections on 5/12/26.Complete corrections to avoid possible fees at following inspections.
BRAD BALDWIN-06/04/2026 @ 07:55
$150 re-inspection fee for failure to complete corrections on scheduled 613/26 inspection.Complete corrections to avoid fees at following inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completededpost stinspection
Karri Dorsey 2026 Date: BRAD BALDWIN 06104/2026
GENERATED ON 6/4/26, 7:57 AM 1 OF 8
1
CHECKLISTS
GENERATED ON 6/4/26, 7:57 AM 2 OF 8
• Reinspection
Status Code Description
GENERATED ON 6/4/26, 7:57 AM 3 OF 8
Fail 1010.2.4-Locks and latches.
Locks and latches shall be permitted to prevent operation of Location:Main exit doors(west)
doors where any of the following exist:1.Places of detention Comments:Install permanent signage"THIS DOOR TO REMAIN
or restraint.2.In Group I-1,Condition 2 and Group I-2 UNLOCKED WHEN THIS SPACE IS OCCUPIED."Laminated paper will
occupancies where the clinical needs of persons receiving not be accepted.
care require containment or where persons receiving care
pose a security threat,provided that all clinical staff can
readily unlock doors at all times,and all such locks are keyed
to keys carried by all clinical staff at all times or all clinical
staff have the codes or other means necessary to operate the
locks at all times.2.3.In buildings in occupancy Group A
having an occupant load of 300 or less,Groups B,F,M and S,
and in places of religious worship,the main door or doors are
permitted to be equipped with key-operated locking devices
from the egress side provided:2.1.3.1.The locking device is
readily distinguishable as locked.2.2.3.2.A readily visible
durable sign is posted on the egress side on or adjacent to
the door stating:"THIS DOOR TO REMAIN UNLOCKED WHEN
THIS SPACE IS OCCUPIED."The sign shall be in letters 1 inch
(25 rnm)high on a contrasting background.2.3.3.3.The use
of the key-operated locking device is revocable by the fire
code official for due cause.3.4.Where egress doors are used
in pairs,approved automatic flush bolts shall be permitted to
be used,provided that the door leaf having the automatic
flush bolts does not have a doorknob or surface-mounted
hardware.4.5.Doors from individual dwelling or sleeping
units of Group R occupancies having an occupant load of 10
or less are permitted to be equipped with a night latch,dead
bolt or security chain,provided such devices are openable
from the inside without the use of a key or tool.5.6.Fire
doors after the minimum elevated temperature has disabled
the unlatching mechanism in accordance with listed fire door
test procedures.6.7.Doors serving roofs not intended to be
occupied shall be permitted to be locked,preventing entry to
the building from the roof.8.Other than egress courts,where
occupants must egress from an exterior space through the
building for means of egress,exit access doors shall be
permitted to be equipped with an approved locking device
where installed and operated in accordance with all of the
following:8.1.The maximum occupant load shall be posted
where required by Section 1004.9.Such sign shall be
permanently affixed inside the building and shall be posted in
a conspicuous space near all the exit access doorways.8.2.A
weatherproof telephone or two-way communication system
installed in accordance with Sections 1009.8.1 and 1009.8.2
shall be located adjacent to not less than one required exit
access door on the exterior side.8.3.The egress door locking
device is readily distinguishable as locked and shall be a key-
operated locking device.8.4.A clear window or glazed door
opening,not less than 5 square feet(0.46 m2)in area,shall
be provided at each exit access door to determine if there are
occupants using the outdoor area.8.5.A readily visible
durable sign shall be posted on the interior side on or
adjacent to each locked required exit access door serving the
exterior area stating: "THIS DOOR TO REMAIN UNLOCKED
WHEN THE OUTDOOR AREA IS OCCUPIED."The letters on
the sign shall be not less than 1 inch(25.4 mm)high on a
contrasting background.8.6.The occupant load of the
occupied exterior area shall not exceed 300 occupants in
accordance with Section 1004.9.Locking devices are
permitted on doors to balconies,decks or other exterior
spaces serving individual dwelling or sleeping units.
10.Locking devices are permitted on doors to balconies,
decks or other exterior spaces of 250 square feet(23.23
m2)or less,serving a private office space.
GENERATED ON 6/4/26, 7:57 AM 4 OF 8
r rt
V
•
5 OF 8
GENERATED ON 6/4/26, 7:57 AM
Fail 1010.2.4-Locks and latches.
Locks and latches shall be permitted to prevent operation of Location:North exit door near diesel pumps
doors where any of the following exist:1.places of detention Comments:Install permanent signage"THIS DOOR TO REMAIN
or restraint.2.In Group I-i,Condition 2 and Group 1-2 UNLOCKED WHEN THIS SPACE IS OCCUPIED."Laminated paper will
occupancies where the clinical needs of persons receiving not be accepted.
care require containment or where persons receiving care
pose a security threat,provided that all clinical staff can
readily unlock doors at all times,and all such locks are keyed
to keys carried by all clinical staff at all times or all clinical
staff have the codes or other means necessary to operate the
locks at all times.2.3.In buildings in occupancy Group A
having an occupant load of 300 or less,Groups B,F,M and S,
and in places of religious worship,the main door or doors are
permitted to be equipped with key-operated locking devices
from the egress side provided:2.1.3.1.The locking device is
readily distinguishable as locked.2.2.3.2.A readily visible
durable sign is posted on the egress side on or adjacent to
the door stating:"THIS DOOR TO REMAIN UNLOCKED WHEN
THIS SPACE IS OCCUPIED."The sign shall be in letters 1 inch
(25 mm)high on a contrasting background.2.3.3.3.The use
of the key-operated locking device is revocable by the fire
code official for due cause.3.4.Where egress doors are used
in pairs,approved automatic flush bolts shall be permitted to
be used,provided that the door leaf having the automatic
flush bolts does not have a doorknob or surface-mounted
hardware.4.5.Doors from individual dwelling or sleeping
units of Group R occupancies having an occupant load of 10
or less are permitted to be equipped with a night latch,dead
bolt or security chain,provided such devices are openable
from the inside without the use of a key or tool.5.6.Fire
doors after the minimum elevated temperature has disabled
the unlatching mechanism in accordance with listed fire door
test procedures.6.7.Doors serving roofs not intended to be
occupied shall be permitted to be locked,preventing entry to
the building from the roof.8.Other than egress courts,where
occupants must egress from an exterior space through the
building for means of egress,exit access doors shall be
permitted to be equipped with an approved locking device
where installed and operated in accordance with all of the
following:8.1.The maximum occupant load shall be posted
where required by Section 1004.9.Such sign shall be
permanently affixed inside the building and shall be posted in
a conspicuous space near all the exit access doorways.8.2.A
weatherproof telephone or two-way communication system
installed in accordance with Sections 1009.8.1 and 1009.8.2
shall be located adjacent to not less than one required exit
access door on the exterior side.8.3.The egress door locking
device is readily distinguishable as locked and shall be a key-
operated locking device.8.4.A clear window or glazed door
opening,not less than 5 square feet(0.46 m2)in area,shall
be provided at each exit access door to determine if there are
occupants using the outdoor area.8.5.A readily visible
durable sign shall be posted on the interior side on or
adjacent to each locked required exit access door serving the
exterior area stating:"THIS DOOR TO REMAIN UNLOCKED
WHEN THE OUTDOOR AREA IS OCCUPIED."The letters on
the sign shall be not less than 1 inch(25.4 mm)high on a
contrasting background.8.6.The occupant load of the
occupied exterior area shall not exceed 300 occupants in
accordance with Section 1004.9.Locking devices are
permitted on doors to balconies,decks or other exterior
spaces serving individual dwelling or sleeping units.
10.Locking devices are permitted on doors to balconies,
decks or other exterior spaces of 250 square feet(23.23
m2)or less,serving a private office space.
GENERATED ON 6/4/26, 7:57 AM 6 OF 8
Fail 102.4-Application of building code.
The design and construction of new structures shall comply Location:Waste cooking oil room near bathrooms
with the International Building Code,and any alterations, Comments:Licensed electrical contractor shall obtain permit and
additions,changes in use or changes in structures required inspection for outlet added,currently used for compressor,
by this code,which are within the scope of the International
Building Code,shall be made in accordance therewith. Additional comments:Permit obtain,contractor is required to obtain
inspection with electrical inspector
Fail 1203.2.6-Exit signs.
Emergency power shall be provided for exit signs as required Location:North exit
in Section 1013.6.3.The system shall be capable of powering
Comments:Repair or replace exit sign that failed to illuminate during
the required load for a duration of not less than 90 minutes. test.
Additional comments:"test"button missing from sign,unable to test
for proper function.
•
I
aim
Fail 1203.2.6-Exit signs.
Emergency power shall be provided for exit signs as required Location:Main exit(west)
in Section 1013.6.3.The system shall be capable of powering Comments:Repair or replace exit sign that failed to illuminate during
the required load for a duration of not less than 90 minutes. test.
Additional comments:"test"button missing from sign,unable to test
for proper function.
Fail 606.3.3-Cleaning.
Hoods,grease-removal devices,fans,ducts and other Location:Kitchen hood exhaust
appurtenances shall be cleaned at intervals as required by Comments:Exhaust system cleaning 75 days past due as of 4/20/26.
Sections 606.3.3.1 through 606.3.3.3. Provide cleaning and report to be uploaded to Compliance Engine
with any deficiencies corrected.
Additional comments:Nelbud tagged serviced in May 2026.Report
shall be uploaded to Compliance Engine including any deficiencies
corrected.Currently 120 days past due for report
GENERATED ON 6/4/26, 7:57 AM / OF 8
0 Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $150.00
Invoice Number Check Number Transaction Number
NIA NIA NIA
GENERATED ON 6/4/26, 7:57 AM 8 OF 8
OF W q INVOICE DATE DUE DATE INVOICE# TOTAL DUE
,� �� 06/10/2026 07/15/2026 2026-00000554 $150.00
0
01 O
Customer#: 15371 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
CASEY'S GENERAL STORE#2867 715 Mulberry St
1 SE CONVENIENCE BLVD WATERLOO, IA 50703
ANKENY, IA 50021
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION-2424 RANCHERO RD-06/03/2026 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
REINSPECTION 2 $150 00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
15371 06/10/2026 07/15/2026 2026-00000554 $150.00
Less Prepayment $0.00
Total Due-* $150.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.